Accessible Routes
BFID: 189198
There are no on-street accessible parking stalls. However, none of the on-street parking is marked.
Where on-street parking is provided on the block perimeter and the parking is marked, accessible parking spaces shall be provided.
Citation:
2011 PROWAG Section R214
Where on-street parking is provided on the block perimeter and the parking is marked or metered, accessible parking spaces complying with R309 (On-Street Parking Spaces) shall be provided in accordance with Table R214 (Scoping - On-Street Parking Spaces).
As Built:
There are no designated accessible parking spaces on the streets around the park.
Recommendation:
Mark an accessible parking space near a curb ramp into the park.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Additional Finding Photos
BFID: 192507
There are multiple issues with this curb ramp including:
No detectable warnings.
An exposed bollard base.
A gutter pan with an 11.6% counterslope.
Sediment in the gutter pan.
Citation:
2010 ADAS Section 406
Curb Ramps
As Built:
There are multiple issues with this vehicle entrance which serves as a curb ramp into the park from Chapman Dr.
Recommendation:
Remove and replace the curb ramp.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Additional Finding Photos
BFID: 192508
The accessible path of travel has cross slopes greater than 2%.
Surface cross slopes shall not exceed one unit vertical in 48 units horizontal (2-percent slope). When the slope in the direction of travel of any walk exceeds 1 unit vertical in 20 units horizontal (5-percent slope), it must be constructed as a ramp.
Citation:
2010 ADAS Section 403.3
The running slope of walking surfaces shall not be steeper than 1:20. The cross slope of walking surfaces shall not be steeper than 1:48.
As Built:
Along this stretch of the accessible route that runs between turns on the triangular convergence of paths near the curb ramp off Chapman Dr., there is one pad of concrete with excessive cross-slope measuring 3%.
Recommendation:
Remove and replace pad of concrete to compliance.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Additional Finding Photos
BFID: 192509
The T-shaped or circular turning space has excessive slopes.
Surface slopes greater than 1:48 (2.08%) are not permitted.
Citation:
2010 ADAS Section 304.2
Floor or ground surfaces of a turning space shall comply with 302. Changes in level are not permitted.
2010 ADAS Section 304.2 Exception
Slopes not steeper than 1:48 shall be permitted.
As Built:
The turn at the north end of the triangular convergence of paths near the curb ramp off Chapman Dr, has a slope of 4%.
Recommendation:
Remove and replace concrete at this turn.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Additional Finding Photos
BFID: 192510
The accessible path of travel has cross slopes greater than 2%.
Surface cross slopes shall not exceed one unit vertical in 48 units horizontal (2-percent slope). When the slope in the direction of travel of any walk exceeds 1 unit vertical in 20 units horizontal (5-percent slope), it must be constructed as a ramp.
Citation:
2010 ADAS Section 403.3
The running slope of walking surfaces shall not be steeper than 1:20. The cross slope of walking surfaces shall not be steeper than 1:48.
As Built:
This stretch of accessible route that runs between turns on the triangular convergence of paths near the curb ramp off Chapman Dr, has one pad of concrete with high cross slope measuring 3.6%.
Recommendation:
Remove and replace concrete to compliance.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
BFID: 192511
The walkway contains abrupt vertical edges and/or variations over a 1/2 inch.
1/4 inch is the maximum vertical rise. Changes in level between 1/4 inch and 1/2 inch must be beveled at 1:2 or less.
Changes in level greater than 1/2 inch must be by way of a ramp.
Citation:
2010 ADAS Section 303.3
Changes in level between 1/4 inch (6.4 mm) high minimum and 1/2 inch (13 mm) high maximum shall be beveled with a slope not steeper than 1:2.
2010 ADAS Section 303.2
Changes in level of 1/4 inch (6.4 mm) high maximum shall be permitted to be vertical.
As Built:
There is a 1/2" vertical displacement between pads near the turn just east of the porta potty shelter.
Recommendation:
Do nothing as this can be remedied when the turn concrete is replaced. See the following finding for recommendation and cost.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Additional Finding Photos
BFID: 192512
The T-shaped or circular turning space has excessive slopes.
Surface slopes greater than 1:48 (2.08%) are not permitted.
Citation:
2010 ADAS Section 304.2
Floor or ground surfaces of a turning space shall comply with 302. Changes in level are not permitted.
2010 ADAS Section 304.2 Exception
Slopes not steeper than 1:48 shall be permitted.
As Built:
The turn just east of the porta-potty shelter has a slope of 2.8%.
Recommendation:
Remove and replace concrete at this turn to compliance.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
BFID: 192513
The accessible route has running slopes greater than 5% and has not been constructed as a ramp (i.e. handrails,edge protection, etc.). Cross slopes are greater than 2% across the width of the walk.
When the slope in the direction of travel of any walk exceeds 1 unit vertical in 20 units horizontal (5-percent slope), it must be constructed as a ramp. Surface cross slopes must not exceed 1 unit vertical in 48 units horizontal (2-percent slope).
Citation:
2010 ADAS Section 403.3
The running slope of walking surfaces shall not be steeper than 1:20. The cross slope of walking surfaces shall not be steeper than 1:48.
As Built:
The route that runs from the Chapman Dr. near Lacy Ln at the northeast corner of the park down to the turn just north of the porta-potty shelter has 13 pads with high cross slope up to 5.4%, four of which also have high running slope measuring up to 6.2%.
Recommendation:
Remove and replace concrete to compliance. Re-grade to achieve a compliant running slope.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
BFID: 192514
The surface of the pedestrian access route has vertical discontinuities greater than 1/2 inch or between 1/4 inch and 1/2 inch that are not beveled.
Vertical surface discontinuities shall be 0.5 inch maximum. Vertical surface discontinuities between 0.25 inch and 0.5 inch shall be beveled with a slope not steeper than 50 percent. The bevel shall be applied across the entire vertical surface discontinuity.
Citation:
2011 PROWAG Section R302.7.2
Vertical surface discontinuities shall be 13 mm (0.5 in) maximum. Vertical surface discontinuities between 6.4 mm (0.25 in) and 13 mm (0.5 in) shall be beveled with a slope not steeper than 50 percent. The bevel shall be applied across the entire vertical surface discontinuity.Advisory R302.7.2 Vertical Surface Discontinuities. The allowance for vertical surface discontinuities is for occasional expansion joints and objects such as utility covers, vault frames, and gratings that cannot be located in another portion of the sidewalk outside the pedestrian access route. However, objects such as utility covers, vault frames, and gratings should not be located on curb ramp runs, blended transitions, turning spaces, or gutter areas within the pedestrian access route. This may not always be possible in alterations, but should be avoided wherever possible. Vertical surface discontinuities between unit pavers should be minimized.
As Built:
On the route that runs from Champan Dr near Lacy Ln at the northeast corner of the park, down to the turn just north of the porta-potty structure there are two areas with vertical displacement measuring 1/2" - one a divot near Chapman and Lacy Ln and a displacement between pads around the midway point along the route.
Recommendation:
Do nothing as both of these discontinuities are associated with pads that will need to be replaced due to high cross-slopes. See the previous finding for the associated cost.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Additional Finding Photos
BFID: 192515
The accessible path of travel has cross slopes greater than 2%.
Surface cross slopes shall not exceed one unit vertical in 48 units horizontal (2-percent slope). When the slope in the direction of travel of any walk exceeds 1 unit vertical in 20 units horizontal (5-percent slope), it must be constructed as a ramp.
Citation:
2010 ADAS Section 403.3
The running slope of walking surfaces shall not be steeper than 1:20. The cross slope of walking surfaces shall not be steeper than 1:48.
As Built:
The section of the accessible route that runs between the porta-potty shelter and the turn at the climbing rock has three pads of concrete with a high cross-slope measuring up to 3.3%.
Recommendation:
Remove and replace concrete to compliance.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
BFID: 192516
The T-shaped or circular turning space has excessive slopes.
Surface slopes greater than 1:48 (2.08%) are not permitted.
Citation:
2010 ADAS Section 304.2
Floor or ground surfaces of a turning space shall comply with 302. Changes in level are not permitted.
2010 ADAS Section 304.2 Exception
Slopes not steeper than 1:48 shall be permitted.
As Built:
The turning space on the east side of the climbing rock has a slope of 4.8%.
Recommendation:
Remove and replace concrete at this turn to compliance.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Additional Finding Photos
BFID: 192517
The T-shaped or circular turning space has excessive slopes.
Surface slopes greater than 1:48 (2.08%) are not permitted.
Citation:
2010 ADAS Section 304.2
Floor or ground surfaces of a turning space shall comply with 302. Changes in level are not permitted.
2010 ADAS Section 304.2 Exception
Slopes not steeper than 1:48 shall be permitted.
As Built:
The turning space on the south side of the climbing rock has a slope of 7.9%.
Recommendation:
Remove and replace concrete at this turn to compliance.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
BFID: 192518
The T-shaped or circular turning space has excessive slopes.
Surface slopes greater than 1:48 (2.08%) are not permitted.
Citation:
2010 ADAS Section 304.2
Floor or ground surfaces of a turning space shall comply with 302. Changes in level are not permitted.
2010 ADAS Section 304.2 Exception
Slopes not steeper than 1:48 shall be permitted.
As Built:
The turning space on the west side of the climbing rock has a slope of 6.6%.
Recommendation:
Remove and replace concrete at this turn to compliance.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Additional Finding Photos
BFID: 192519
The accessible path of travel has cross slopes greater than 2%.
Surface cross slopes shall not exceed one unit vertical in 48 units horizontal (2-percent slope). When the slope in the direction of travel of any walk exceeds 1 unit vertical in 20 units horizontal (5-percent slope), it must be constructed as a ramp.
Citation:
2010 ADAS Section 403.3
The running slope of walking surfaces shall not be steeper than 1:20. The cross slope of walking surfaces shall not be steeper than 1:48.
As Built:
The section of accessible route that runs between turns on the north side of the climbing rock has four pads of concrete with excessive cross slope measuring up to 5.6%.
Recommendation:
Remove and replace concrete to compliance.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Additional Finding Photos
BFID: 192520
The walkway contains abrupt vertical edges and/or variations over a 1/2 inch.
1/4 inch is the maximum vertical rise. Changes in level between 1/4 inch and 1/2 inch must be beveled at 1:2 or less.
Changes in level greater than 1/2 inch must be by way of a ramp.
Citation:
2010 ADAS Section 303.3
Changes in level between 1/4 inch (6.4 mm) high minimum and 1/2 inch (13 mm) high maximum shall be beveled with a slope not steeper than 1:2.
2010 ADAS Section 303.2
Changes in level of 1/4 inch (6.4 mm) high maximum shall be permitted to be vertical.
As Built:
A sunken pad of concrete located on the north end of the climbing rock has resulted in 1" vertical displacements on either end of the pad.
Recommendation:
Replace the sunken pad to compliance. The cost is included in the work detailed in the previous finding.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
BFID: 192521
The accessible path of travel has cross slopes greater than 2%.
Surface cross slopes shall not exceed one unit vertical in 48 units horizontal (2-percent slope). When the slope in the direction of travel of any walk exceeds 1 unit vertical in 20 units horizontal (5-percent slope), it must be constructed as a ramp.
Citation:
2010 ADAS Section 403.3
The running slope of walking surfaces shall not be steeper than 1:20. The cross slope of walking surfaces shall not be steeper than 1:48.
As Built:
The section of the accessible route that runs between turns on the east side of the climbing rock has two pads of concrete with excessive cross-slope measuring up to 5.8%.
Recommendation:
Remove and replace concrete to compliance.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Additional Finding Photos
BFID: 192522
The accessible route has running slopes greater than 5% and has not been constructed as a ramp (i.e. handrails,edge protection, etc.). Cross slopes are greater than 2% across the width of the walk.
When the slope in the direction of travel of any walk exceeds 1 unit vertical in 20 units horizontal (5-percent slope), it must be constructed as a ramp. Surface cross slopes must not exceed 1 unit vertical in 48 units horizontal (2-percent slope).
Citation:
2010 ADAS Section 403.3
The running slope of walking surfaces shall not be steeper than 1:20. The cross slope of walking surfaces shall not be steeper than 1:48.
As Built:
The section of the accessible route that runs between turns on the west side of the climbing rock has five pads of concrete with excessive cross-slope measuring up to 6.2% and two additional pads with excessive running-slope measuring 5.9% and 8.4%
Recommendation:
Remove and replace pads to compliance. Re-grade the section to achieve a compliant running slope.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Additional Finding Photos
BFID: 192523
The walking surface has gaps over 1/2" wide.
Citation:
2010 ADAS Section 302.3
Openings in floor or ground surfaces shall not allow passage of a sphere more than 1/2 inch (13 mm) diameter except as allowed in 407.4.3, 409.4.3, 410.4, 810.5.3 and 810.10. Elongated openings shall be placed so that the long dimension is perpendicular to the dominant direction of travel.
As Built:
On this section of route to the west of the climbing rock there is a 1" gap between pads in one location and another 1/2" wide crack causing a 1/2" vertical displacement a few pads over.
Recommendation:
Remove and replace pads at these locations. The cost is included in the work detailed in the previous finding as these pads also have excessive cross-slopes.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Additional Finding Photos
BFID: 192524
The accessible route has running slopes greater than 5% and has not been constructed as a ramp (i.e. handrails,edge protection, etc.). Cross slopes are greater than 2% across the width of the walk.
When the slope in the direction of travel of any walk exceeds 1 unit vertical in 20 units horizontal (5-percent slope), it must be constructed as a ramp. Surface cross slopes must not exceed 1 unit vertical in 48 units horizontal (2-percent slope).
Citation:
2010 ADAS Section 403.3
The running slope of walking surfaces shall not be steeper than 1:20. The cross slope of walking surfaces shall not be steeper than 1:48.
As Built:
The section of accessible route that runs between the climbing rock and the skate park/basketball court has eight pads of concrete with high cross slope and/or running slope. Cross slope measures as high as 4.8% while curnning slope is 6.4% and 7% on two of those pads.
Recommendation:
Remove and replace concrete to compliance. Re-grade to achieve compliant running slope.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
BFID: 192525
The T-shaped or circular turning space has excessive slopes.
Surface slopes greater than 1:48 (2.08%) are not permitted.
Citation:
2010 ADAS Section 304.2
Floor or ground surfaces of a turning space shall comply with 302. Changes in level are not permitted.
2010 ADAS Section 304.2 Exception
Slopes not steeper than 1:48 shall be permitted.
As Built:
The turn into the skate park or basketball court from the east side has a slope of 3.9%.
Recommendation:
Remove and replace concrete at this turn.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
BFID: 192526
The T-shaped or circular turning space has excessive slopes.
Surface slopes greater than 1:48 (2.08%) are not permitted.
Citation:
2010 ADAS Section 304.2
Floor or ground surfaces of a turning space shall comply with 302. Changes in level are not permitted.
2010 ADAS Section 304.2 Exception
Slopes not steeper than 1:48 shall be permitted.
As Built:
The turning into the skate park/basketball court from the west side has a slope of 2.9%.
Recommendation:
Remove and replace concrete at this turn to compliance.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
BFID: 192528
The accessible route has running slopes greater than 5% and has not been constructed as a ramp (i.e. handrails,edge protection, etc.). Cross slopes are greater than 2% across the width of the walk.
When the slope in the direction of travel of any walk exceeds 1 unit vertical in 20 units horizontal (5-percent slope), it must be constructed as a ramp. Surface cross slopes must not exceed 1 unit vertical in 48 units horizontal (2-percent slope).
Citation:
2010 ADAS Section 403.3
The running slope of walking surfaces shall not be steeper than 1:20. The cross slope of walking surfaces shall not be steeper than 1:48.
As Built:
On the section of accessible route that runs from the west turn into the skatepark west to the turn at the triangular convergence of paths there are seven pads of concrete with high cross slope and/or running slopes. Cross slopes are as high as 6.2% and running slope measures up to 6.3% on two of those pads.
Recommendation:
Remove and replace pads to compliance.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
BFID: 192529
The walkway contains abrupt vertical edges and/or variations over a 1/2 inch.
1/4 inch is the maximum vertical rise. Changes in level between 1/4 inch and 1/2 inch must be beveled at 1:2 or less.
Changes in level greater than 1/2 inch must be by way of a ramp.
Citation:
2010 ADAS Section 303.3
Changes in level between 1/4 inch (6.4 mm) high minimum and 1/2 inch (13 mm) high maximum shall be beveled with a slope not steeper than 1:2.
2010 ADAS Section 303.2
Changes in level of 1/4 inch (6.4 mm) high maximum shall be permitted to be vertical.
As Built:
On the section of route that runs from the west entrance to the skate park west to the triangular convergence of paths there is a 3/4" vertical displacement between pads.
Recommendation:
Remove and replace heaving pad. Please see previous finding for cost estimate as it also has excessive cross slope.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
BFID: 192530
The T-shaped or circular turning space has excessive slopes.
Surface slopes greater than 1:48 (2.08%) are not permitted.
Citation:
2010 ADAS Section 304.2
Floor or ground surfaces of a turning space shall comply with 302. Changes in level are not permitted.
2010 ADAS Section 304.2 Exception
Slopes not steeper than 1:48 shall be permitted.
As Built:
This turn located on the northeast end of the triangular convergence of paths on the west side of the park has a slope of 4.8%.
Recommendation:
Remove and replace concrete at this turn to compliance.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Additional Finding Photos
BFID: 192531
The T-shaped or circular turning space has excessive slopes.
Surface slopes greater than 1:48 (2.08%) are not permitted.
Citation:
2010 ADAS Section 304.2
Floor or ground surfaces of a turning space shall comply with 302. Changes in level are not permitted.
2010 ADAS Section 304.2 Exception
Slopes not steeper than 1:48 shall be permitted.
As Built:
This turn located on the west end of the triangular convergence of paths on the west side of the park has a slope of 6.9%.
Recommendation:
Remove and replace concrete at this turn to compliance.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Additional Finding Photos
BFID: 192532
The T-shaped or circular turning space has excessive slopes.
Surface slopes greater than 1:48 (2.08%) are not permitted.
Citation:
2010 ADAS Section 304.2
Floor or ground surfaces of a turning space shall comply with 302. Changes in level are not permitted.
2010 ADAS Section 304.2 Exception
Slopes not steeper than 1:48 shall be permitted.
As Built:
This turn located on the south end of the triangular convergence of paths on the west side of the park has a slope of 5.4%.
Recommendation:
Remove and replace concrete at this turn to compliance.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Additional Finding Photos
BFID: 192533
The accessible path of travel has cross slopes greater than 2%.
Surface cross slopes shall not exceed one unit vertical in 48 units horizontal (2-percent slope). When the slope in the direction of travel of any walk exceeds 1 unit vertical in 20 units horizontal (5-percent slope), it must be constructed as a ramp.
Citation:
2010 ADAS Section 403.3
The running slope of walking surfaces shall not be steeper than 1:20. The cross slope of walking surfaces shall not be steeper than 1:48.
As Built:
This section of route that runs between turns on the triangular convergence of paths on the west side of the park has three pads of concrete with high cross slope measuring between 3.5% and 5.5%.
Recommendation:
Remove and replace pads to compliance.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
BFID: 192534
The accessible path of travel has cross slopes greater than 2%.
Surface cross slopes shall not exceed one unit vertical in 48 units horizontal (2-percent slope). When the slope in the direction of travel of any walk exceeds 1 unit vertical in 20 units horizontal (5-percent slope), it must be constructed as a ramp.
Citation:
2010 ADAS Section 403.3
The running slope of walking surfaces shall not be steeper than 1:20. The cross slope of walking surfaces shall not be steeper than 1:48.
As Built:
This section of route that runs between turns on the triangular convergence of paths on the west side of the park has two pads of concrete with high cross slope measuring up to 2.8%.
Recommendation:
Remove and replace pads to compliance.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Additional Finding Photos
BFID: 192535
The accessible route has running slopes greater than 5% and has not been constructed as a ramp (i.e. handrails,edge protection, etc.). Cross slopes are greater than 2% across the width of the walk.
When the slope in the direction of travel of any walk exceeds 1 unit vertical in 20 units horizontal (5-percent slope), it must be constructed as a ramp. Surface cross slopes must not exceed 1 unit vertical in 48 units horizontal (2-percent slope).
Citation:
2010 ADAS Section 403.3
The running slope of walking surfaces shall not be steeper than 1:20. The cross slope of walking surfaces shall not be steeper than 1:48.
As Built:
This section of route that runs between turns on the triangular convergence of paths on the west side of the park has three pads of concrete with high running slope measuring up to 6%. Two of those also have high cross slope up to 4.5%.
Recommendation:
Remove and replace pads to compliant. Remove and replace adjacent pad(s) if necessary to achieve a compliant running slope.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
BFID: 192536
The accessible route has running slopes greater than 5% and has not been constructed as a ramp (i.e. handrails,edge protection, etc.). Cross slopes are greater than 2% across the width of the walk.
When the slope in the direction of travel of any walk exceeds 1 unit vertical in 20 units horizontal (5-percent slope), it must be constructed as a ramp. Surface cross slopes must not exceed 1 unit vertical in 48 units horizontal (2-percent slope).
Citation:
2010 ADAS Section 403.3
The running slope of walking surfaces shall not be steeper than 1:20. The cross slope of walking surfaces shall not be steeper than 1:48.
As Built:
The accessible route that leads from the triangular convergence of paths on the west side of the park west to the apartment complex has 15 pads of concrete with high cross slope measuring up to 3.8%. One of those also has high running slope of 6.6%. This path dead ends at a metal fence with no gate. There is no access to the apartment complex from this route.
Recommendation:
Do nothing at this time as the route does not provide access to the apartment complex nor any other elements.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Additional Finding Photos
BFID: 192538
The accessible route has running slopes greater than 5% and has not been constructed as a ramp (i.e. handrails,edge protection, etc.). Cross slopes are greater than 2% across the width of the walk.
When the slope in the direction of travel of any walk exceeds 1 unit vertical in 20 units horizontal (5-percent slope), it must be constructed as a ramp. Surface cross slopes must not exceed 1 unit vertical in 48 units horizontal (2-percent slope).
Citation:
2010 ADAS Section 403.3
The running slope of walking surfaces shall not be steeper than 1:20. The cross slope of walking surfaces shall not be steeper than 1:48.
As Built:
The section of accessible route that runs from the triangular convergence of paths on the west side of the park south to the turn to the path that leads to the apartments near the playground has 11 pads of concrete with high cross slope measuring up to 4.8%. One of those pads also has a running slope of 5.7%.
Recommendation:
Remove and replace concrete to compliance.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
BFID: 192541
The walkway contains abrupt vertical edges and/or variations over a 1/2 inch.
1/4 inch is the maximum vertical rise. Changes in level between 1/4 inch and 1/2 inch must be beveled at 1:2 or less.
Changes in level greater than 1/2 inch must be by way of a ramp.
Citation:
2010 ADAS Section 303.3
Changes in level between 1/4 inch (6.4 mm) high minimum and 1/2 inch (13 mm) high maximum shall be beveled with a slope not steeper than 1:2.
2010 ADAS Section 303.2
Changes in level of 1/4 inch (6.4 mm) high maximum shall be permitted to be vertical.
As Built:
There is a 3/4" vertical displacement between pads on the route that runs from the triangular convergence of paths on the west side of the park south to the playground.
Recommendation:
Remove and replace the high pad. Please see the previous finding for cost as the pad also has a high cross slope.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
BFID: 192539
The T-shaped or circular turning space has excessive slopes.
Surface slopes greater than 1:48 (2.08%) are not permitted.
Citation:
2010 ADAS Section 304.2
Floor or ground surfaces of a turning space shall comply with 302. Changes in level are not permitted.
2010 ADAS Section 304.2 Exception
Slopes not steeper than 1:48 shall be permitted.
As Built:
The turn near to the apartment complex near the west side of the playground has a slope of 5.7%.
Recommendation:
Remove and replace concrete at this turn to compliance.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
BFID: 192537
The accessible route has running slopes greater than 5% and has not been constructed as a ramp (i.e. handrails,edge protection, etc.). Cross slopes are greater than 2% across the width of the walk.
When the slope in the direction of travel of any walk exceeds 1 unit vertical in 20 units horizontal (5-percent slope), it must be constructed as a ramp. Surface cross slopes must not exceed 1 unit vertical in 48 units horizontal (2-percent slope).
Citation:
2010 ADAS Section 403.3
The running slope of walking surfaces shall not be steeper than 1:20. The cross slope of walking surfaces shall not be steeper than 1:48.
As Built:
The accessible route that leads from the playground west to the apartment complex at the southwest corner of the park has 17 pads of concrete with high cross slope measuring up to 4.1%. Five of those also have high running slope of 6.7%. This path dead-ends at a metal and chainlink fence with no gate (someone has disconnected the section of fence to allow for an opening). Currently there is no access to the apartment complex from this route.
Recommendation:
Do nothing at this time as the route does not provide access to the apartment complex nor any other elements. Contact the appropriate department to explore whether or not this will be open for access to the apartments or fenced off permanently like the other route to the north.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Additional Finding Photos
BFID: 192546
The T-shaped or circular turning space has excessive slopes.
Surface slopes greater than 1:48 (2.08%) are not permitted.
Citation:
2010 ADAS Section 304.2
Floor or ground surfaces of a turning space shall comply with 302. Changes in level are not permitted.
2010 ADAS Section 304.2 Exception
Slopes not steeper than 1:48 shall be permitted.
As Built:
The turn at the east end of the playground where the path forks to the north toward the climbing rock or east toward Chapman Dr. has a slope of 4%.
Recommendation:
Remove and replace concrete at this turn.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Additional Finding Photos
BFID: 192545
The accessible route has running slopes greater than 5% and has not been constructed as a ramp (i.e. handrails,edge protection, etc.). Cross slopes are greater than 2% across the width of the walk.
When the slope in the direction of travel of any walk exceeds 1 unit vertical in 20 units horizontal (5-percent slope), it must be constructed as a ramp. Surface cross slopes must not exceed 1 unit vertical in 48 units horizontal (2-percent slope).
Citation:
2010 ADAS Section 403.3
The running slope of walking surfaces shall not be steeper than 1:20. The cross slope of walking surfaces shall not be steeper than 1:48.
As Built:
On the route that runs from the playground north to the turn at the climbing rock there are four pads with high running slope up to 6.3%, and two additional pads of concrete with excessive cross slope up to 3.5%.
Recommendation:
Remove and replace concrete to compliance.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Additional Finding Photos
BFID: 192547
The walkway contains abrupt vertical edges and/or variations over a 1/2 inch.
1/4 inch is the maximum vertical rise. Changes in level between 1/4 inch and 1/2 inch must be beveled at 1:2 or less.
Changes in level greater than 1/2 inch must be by way of a ramp.
Citation:
2010 ADAS Section 303.3
Changes in level between 1/4 inch (6.4 mm) high minimum and 1/2 inch (13 mm) high maximum shall be beveled with a slope not steeper than 1:2.
2010 ADAS Section 303.2
Changes in level of 1/4 inch (6.4 mm) high maximum shall be permitted to be vertical.
As Built:
On the route that runs from the turn at the east side of the playground north toward the climbing rock there is a 3/4" vertical displacement between pads.
Recommendation:
Remove and replace the low pad as it also has a high cross slope. This work and the associated cost have already been documented in the previous finding.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
BFID: 192548
The accessible path of travel has cross slopes greater than 2%.
Surface cross slopes shall not exceed one unit vertical in 48 units horizontal (2-percent slope). When the slope in the direction of travel of any walk exceeds 1 unit vertical in 20 units horizontal (5-percent slope), it must be constructed as a ramp.
Citation:
2010 ADAS Section 403.3
The running slope of walking surfaces shall not be steeper than 1:20. The cross slope of walking surfaces shall not be steeper than 1:48.
As Built:
This section of accessible route that runs from the playground east/southeast to Chapman Dr. has five pads of concrete with high cross slope measuring up to 4.3%.
Recommendation:
Remove and replace pads to compliance.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
BFID: 192549
The T-shaped or circular turning space has excessive slopes.
Surface slopes greater than 1:48 (2.08%) are not permitted.
Citation:
2010 ADAS Section 304.2
Floor or ground surfaces of a turning space shall comply with 302. Changes in level are not permitted.
2010 ADAS Section 304.2 Exception
Slopes not steeper than 1:48 shall be permitted.
As Built:
This turn toward the playground on the route along Chapman Dr. has a slope of 3.8%.
Recommendation:
Remove and replace concrete to compliance.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Additional Finding Photos
BFID: 192550
The accessible path of travel has cross slopes greater than 2%.
Surface cross slopes shall not exceed one unit vertical in 48 units horizontal (2-percent slope). When the slope in the direction of travel of any walk exceeds 1 unit vertical in 20 units horizontal (5-percent slope), it must be constructed as a ramp.
Citation:
2010 ADAS Section 403.3
The running slope of walking surfaces shall not be steeper than 1:20. The cross slope of walking surfaces shall not be steeper than 1:48.
As Built:
On the route that runs along Chapman Dr. stretching from the south end of the park north to the turn at the porta-potty shelter there are 16 pads of concrete with excessive cross slope as high as 6%.
Recommendation:
Remove and replace concrete to compliance.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
BFID: 192551
The walkway contains abrupt vertical edges and/or variations over a 1/2 inch.
1/4 inch is the maximum vertical rise. Changes in level between 1/4 inch and 1/2 inch must be beveled at 1:2 or less.
Changes in level greater than 1/2 inch must be by way of a ramp.
Citation:
2010 ADAS Section 303.3
Changes in level between 1/4 inch (6.4 mm) high minimum and 1/2 inch (13 mm) high maximum shall be beveled with a slope not steeper than 1:2.
2010 ADAS Section 303.2
Changes in level of 1/4 inch (6.4 mm) high maximum shall be permitted to be vertical.
As Built:
On the section of accessible route that runs from the south end of the park at Chapman Dr. north to the turn toward the playground there are three vertical displacements between 3/4" and 1" between pads of concrete.
Recommendation:
Remove and replace pads as all three also have excessive cross slope and are documented in the previous finding. Costs are included in the previous finding.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation