Site Accessibility Evaluation

Americans with Disabilities Act
Title II (Public Services: State and Local Government)
Evaluation PU18-0045 Cover Photo
Fire Station 20
6755 Rangewood Dr
Colorado Springs, CO 80918
Accessibility Evaluation
Inspection Date: 10/30/2021
Inspectors: Robert Hernandez
Prepared By
City of Colorado Springs Logo
City of Colorado Springs
(719) 385 - 5175
https://coloradosprings.gov/
Report Date: 01/17/2025

FOR RECORD:

FROM: Robert L. Hernandez, Title II ADA/Section 504 – Manager

DATE: 01/17/2025

SUBJECT: Fire Station 20 Self-Evaluation

1. On 10/30/2021, Title II ADA / Section 504 Coordinator(s) from the Office of Accessibility performed a Title II - Americans with Disabilities Act (ADA) Self-Evaluation. This evaluation was performed in accordance with 1991/2010 ADA Standards for Accessible Design.

2. Priorities for removing barriers are assigned in accordance with the ADA Checklist for Existing Facilities, promulgated by the ADA National Network. The checklist follows the four priorities listed in the Department of Justice ADA Title III regulations. These priorities are equally applicable to state and local government facilities:

Priority 1 - Accessible approach and entrance
Priority 2 - Access to goods and services
Priority 3 - Access to public toilet rooms
Priority 4 - Access to other items such as water fountains and public telephones

3. Corrective actions to findings were / will be submitted to the City maintenance work request system and will be managed in accordance with the City Transition Plan. Note: Recommended corrections may be modified where appropriate. Corrections are developed in consideration of the “Program Access” provisions of Title II, where applicable.

4. A copy of this report will be maintained by the Office of Accessibility. Updates to the findings included in this report will be available at the following link: https://access6.bluedag.com/access/barriers/GfhHF91nlvMItTaD4rVzj85XBKNZxywJ. Alternatively, this link is available from the Office of Accessibility’s webpage on the City of Colorado Springs website.


City of Colorado Springs Title II ADA/Section 504 – Manager
30 S. Nevada Ave, Suite 301
Colorado Springs, CO 80903
ADACompliance@coloradosprings.gov


Atch 1. City of Colorado Springs, ADA Self-Evaluation Report

Sincerely,


Robert Hernandez

Findings

Exterior - Parking

BFID: 184353

The access aisle is 4'-9" wide. There are two signed accessible parking spaces. The left one is marked as van accessible and is 9'-0" wide. The right space is 9'-1" (if the gutter pan is included), however, there is a 2" gap at the gutter pan the entire length of the space.

The accessible spaces are required to be 8'-0" wide. The access aisle for a van accessible space is required to be 8'-0" wide, or the parking space may be 11'-0" wide and the access aisle 5'-0" wide.
Citation:
2010 ADAS Section 502.2 Exception
Van parking spaces shall be permitted to be 96 inches (2440 mm) wide minimum where the access aisle is 96 inches (2440 mm) wide minimum.

Recommendation:
Restripe the parking to the appropriate widths. The access aisle will need to be 5' wide.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
CSFD
Finding 184353 Main Photo
Image that depicts the citation requirements of the code or standard
Additional Finding Photos
Finding 184353 Additional Photo
Finding 184353 Additional Photo

BFID: 185840

If you include the gutter pan, the right AC space would be 9’1” wide, however, there is a 2”
gap creating a 3” deep hole the length of the space.

Each parking space must be at least 8' feet wide and shall be marked to define the width.

The measurements of parking spaces and access aisles shall be made from the centerline of the markings. Where the parking space is not adjacent to another parking space or access aisle, the measurement shall be permitted to include the full width of the line defining the parking space.
Citation:
2010 ADAS Section 502.2
Car parking spaces shall be 96 inches (2440 mm) wide minimum and van parking spaces shall be 132 inches (3350 mm) wide minimum, shall be marked to define the width, and shall have an adjacent access aisle complying with 502.3.

Recommendation:
Fill the gap as we are limited on space. This will need to be 8' wide.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
CSFD
Image of finding
Image that depicts the citation requirements of the code or standard
Additional Finding Photos
Finding 185840 Additional Photo

BFID: 192305

The accessible parking stall is not wide enough - it is 9' and must be 11' given the current curb ramp placement in relation to the access aisle.

This parking space must be at least 11 feet wide and shall be marked to define the width. The measurements of parking spaces and access aisles shall be made from the centerline of the markings.

Alternatively, the stall can be 8 feet wide minimum and the access aisle may be 8 feet wide - this would be preferable if the curb ramp is moved over.

The measurements of parking spaces and access aisles shall be made from the centerline of the markings. Where the parking space is not adjacent to another parking space or access aisle, the measurement shall be permitted to include the full width of the line defining the parking space.
Citation:
2010 ADAS Section 502.2
Car parking spaces shall be 96 inches (2440 mm) wide minimum and van parking spaces shall be 132 inches (3350 mm) wide minimum, shall be marked to define the width, and shall have an adjacent access aisle complying with 502.3.

Recommendation:
Restripe to 11' wide.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
CSFD
Image of finding
Image that depicts the citation requirements of the code or standard

BFID: 192306

The cross slopes (narrow dimension) and/or running slopes (long dimension) of the accessible stall exceeds 2%.

The running slope and the cross slope in an accessible parking stall and the access aisle must not exceed 2%.
Citation:
2010 ADAS Section 502.4
Parking spaces and access aisles serving them shall comply with 302. Access aisles shall be at the same level as the parking spaces they serve. Changes in level are not permitted.

Recommendation:
Re-asphalt to correct to under 2% in all directions.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
CSFD
Image of finding
Image that depicts the citation requirements of the code or standard

BFID: 192309

The cross slope (narrow dimension) of the parking stall exceeds 2%.

The running and cross slope in an accessible parking stall and the access aisle must not exceed 2%.
Citation:
2010 ADAS Section 502.4
Parking spaces and access aisles serving them shall comply with 302. Access aisles shall be at the same level as the parking spaces they serve. Changes in level are not permitted.

Recommendation:
Re-asphalt to reduce the slope to at or under 2% in all directions.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
CSFD
Image of finding
Image that depicts the citation requirements of the code or standard

BFID: 192310

The cross slope (narrow dimension) of the parking stall exceeds 2%.

The running and cross slope in an accessible parking stall and the access aisle must not exceed 2%.
Citation:
2010 ADAS Section 502.4
Parking spaces and access aisles serving them shall comply with 302. Access aisles shall be at the same level as the parking spaces they serve. Changes in level are not permitted.

Recommendation:
Re-asphalt to reduce the slope to at or under 2% in all directions.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
CSFD
Image of finding
Image that depicts the citation requirements of the code or standard

BFID: 192311

The accessible parking signage is mounted higher than 7'-0" to the bottom of the lowest sign.
Citation:
2010 ADAS Section 502.6
Parking space identification signs shall include the International Symbol of Accessibility complying with 703.7.2.1. Signs identifying van parking spaces shall contain the designation "van accessible." Signs shall be 60 inches (1525 mm) minimum above the finish floor or ground surface measured to the bottom of the sign.

Recommendation:
Lower the signage to between 5'-0" and 7'-0" to the bottom of the lowest sign.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
CSFD
Image of finding

BFID: 184354

The concrete expansion joint is spaced greater than a 1/2 inch.

Openings in floor or ground surfaces shall not allow passage of a sphere more than 1/2 inch diameter. Elongated openings shall be placed so that the long dimension is perpendicular to the dominant direction of travel.
Citation:
2010 ADAS Section 302.3
Openings in floor or ground surfaces shall not allow passage of a sphere more than 1/2 inch (13 mm) diameter except as allowed in 407.4.3, 409.4.3, 410.4, 810.5.3 and 810.10. Elongated openings shall be placed so that the long dimension is perpendicular to the dominant direction of travel.

Recommendation:
Fill the gap.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
CSFD
Finding 184354 Main Photo
Additional Finding Photos
Finding 184354 Additional Photo
Finding 184354 Additional Photo
Finding 184354 Additional Photo

Exterior - Accessible Routes

BFID: 184356

There are multiple issues with this curb ramp including Multiple high slope issues - both running and cross slopes.
Citation:
2010 ADAS Section 406
Curb Ramps

Recommendation:
Remove and replace the curb ramp. We need to reposition further south to ensure the ramp entry and striping line up.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
CSFD
Finding 184356 Main Photo
Additional Finding Photos
Finding 184356 Additional Photo
Finding 184356 Additional Photo
Finding 184356 Additional Photo
Finding 184356 Additional Photo

BFID: 184357

There are a crack and divot in the sidewalk greater than a 1/2 inch.

Openings in floor or ground surfaces shall not allow passage of a sphere more than 1/2 inch diameter. Elongated openings shall be placed so that the long dimension is perpendicular to the dominant direction of travel.
Citation:
2010 ADAS Section 302.3
Openings in floor or ground surfaces shall not allow passage of a sphere more than 1/2 inch (13 mm) diameter except as allowed in 407.4.3, 409.4.3, 410.4, 810.5.3 and 810.10. Elongated openings shall be placed so that the long dimension is perpendicular to the dominant direction of travel.

Recommendation:
Tear out and repour.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
CSFD
Image of finding
Additional Finding Photos
Finding 184357 Additional Photo

BFID: 192313

The accessible route between the building entrance and the accessible parking has running slopes greater than 5% and has not been constructed as a ramp (i.e. handrails, edge protection, etc.).

When the slope in the direction of travel of any walk exceeds 1 unit vertical in 20 units horizontal (5-percent slope), it must be constructed as a ramp. Surface cross slopes must not exceed one unit vertical in 48 units horizontal (2-percent slope).
Citation:
2010 ADAS Section 403.3
The running slope of walking surfaces shall not be steeper than 1:20. The cross slope of walking surfaces shall not be steeper than 1:48.

Recommendation:
Replace all pads to at or under 5%. determine if feasible to make slope 2% in all directions at the turning pad.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
CSFD
Image of finding
Image that depicts the citation requirements of the code or standard

BFID: 192314

There is no accessible route of travel from the public way.

At least one accessible route shall be provided within the site from accessible parking spaces and accessible passenger loading zones; public streets and sidewalks; and public transportation stops to the accessible building or facility they serve.
Citation:
2010 ADAS Section 206.2.1
At least one accessible route shall be provided within the site from accessible parking spaces and accessible passenger loading zones; public streets and sidewalks; and public transportation stops to the accessible building or facility entrance they serve.

Recommendation:
Determine where to add an accessible route. It probably will need to occur near where the above picture is.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
CSFD
Image of finding
Image that depicts the citation requirements of the code or standard
Additional Finding Photos
Finding 192314 Additional Photo
Finding 192314 Additional Photo

BFID: 192323

There are multiple issues with this curb ramp including: vertical displacement from ramp face to landing, no level landing, and a high running slope.
Citation:
2010 ADAS Section 406
Curb Ramps

Recommendation:
Remove and replace the curb ramp.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
CSFD
Image of finding
Additional Finding Photos
Finding 192323 Additional Photo

BFID: 192319

The accessible path of travel has cross slopes greater than 2%.

Surface cross slopes shall not exceed one unit vertical in 48 units horizontal (2-percent slope). When the slope in the direction of travel of any walk exceeds 1 unit vertical in 20 units horizontal (5-percent slope), it must be constructed as a ramp.
Citation:
2010 ADAS Section 403.3
The running slope of walking surfaces shall not be steeper than 1:20. The cross slope of walking surfaces shall not be steeper than 1:48.

Recommendation:
N/A - Refer to Finding
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
CSFD
Image of finding
Image that depicts the citation requirements of the code or standard
Additional Finding Photos
Finding 192319 Additional Photo

BFID: 184362

There are multiple issues with this curb ramp including: There are no domes, the landing for the left flare has a 2.6% cross slope, the central bottom landing has a 5.9% slope one way and 2.8% slope the other, the right flare has a 14.4% running slope and no level landing - the top landing has a 4.9% running slope. There is also 1" vertical displacement where the gutter slope meets the road.
Citation:
2010 ADAS Section 406
Curb Ramps

Recommendation:
Remove and replace the curb ramp.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
CSFD
Finding 184362 Main Photo
Additional Finding Photos
Finding 184362 Additional Photo
Finding 184362 Additional Photo
Finding 184362 Additional Photo

BFID: 184361

There is a gap between the concrete and asphalt within the crosswalk.

In addition, there is 4% cross slope in this crossing.
Citation:
2010 ADAS Section 303.3
Changes in level between 1/4 inch (6.4 mm) high minimum and 1/2 inch (13 mm) high maximum shall be beveled with a slope not steeper than 1:2.

Recommendation:
Fill the gap - cut out and patch back.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
CSFD
Corrected Condition:
The asphalt was taken out and patched back.
Image of finding
Finding 184361 Corrected Photo

BFID: 184360

There are multiple issues with this curb ramp including: there are no domes, vertical displacement at the top and bottom of the ramp face, and no level landing.
Citation:
2010 ADAS Section 406
Curb Ramps

Recommendation:
Remove and replace the curb ramp.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
CSFD
Image of finding
Additional Finding Photos
Finding 184360 Additional Photo
Finding 184360 Additional Photo
Finding 184360 Additional Photo

BFID: 192324

There are multiple issues with this curb ramp including: vertical displacement from ramp face to the gutter face, no level landing, and a high running slope.
Citation:
2010 ADAS Section 406
Curb Ramps

Recommendation:
Remove and replace the curb ramp.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
CSFD
Image of finding
Additional Finding Photos
Finding 192324 Additional Photo

BFID: 184359

There is a gap between the concrete and asphalt within the crosswalk.

In addition, there is a 4% cross slope in this crossing.
Citation:
2010 ADAS Section 303.3
Changes in level between 1/4 inch (6.4 mm) high minimum and 1/2 inch (13 mm) high maximum shall be beveled with a slope not steeper than 1:2.

Recommendation:
Fill the gap. The pavement was removed and replaced to make a level walking surface.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
CSFD
Corrected Condition:
The area was cut out and patched back.
Image of finding
Finding 184359 Corrected Photo

BFID: 184358

The curb ramp on the accessible route contains cross slopes greater than 2%.

Surface cross slopes shall not exceed one unit vertical in 48 units horizontal (2-percent slope).
Citation:
2010 ADAS Section 405.3
Cross slope of ramp runs shall not be steeper than 1:48.

2010 ADAS Section 406.1
Curb ramps on accessible routes shall comply with 406, 405.2 through 405.5, and 405.10.

Recommendation:
Remove and replace the curb ramp unless the slope is needed to blend the ramp into the road grade.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
CSFD
Image of finding
Additional Finding Photos
Finding 184358 Additional Photo

BFID: 184363

The detectable warning is missing at the curb ramp and it has other significant issues.

Curb ramps shall have a detectable warning that extends the full width of the curb ramp, excluding the flared sides, 24 inch minimum in the direction of travel.
Citation:
2011 PROWAG Section R208.1
Detectable warning surfaces complying with R305 shall be provided at the following locations on pedestrian access routes and at transit stops:
1. Curb ramps and blended transitions at pedestrian street crossings;
2. Pedestrian refuge islands;
3. Pedestrian at-grade rail crossings not located within a street or highway;
4. Boarding platforms at transit stops for buses and rail vehicles where the edges of the boarding platform are not protected by screens or guards; and
5. Boarding and alighting areas at sidewalk or street level transit stops for rail vehicles where the side of the boarding and alighting areas facing the rail vehicles is not protected by screens or guards.Advisory R208.1 Where Required. On pedestrian access routes, detectable warning surfaces indicate the boundary between pedestrian and vehicular routes where there is a flush rather than a curbed connection. Detectable warning surfaces should not be provided at crossings of residential driveways since the pedestrian right-of-way continues across residential driveway aprons. However, where commercial driveways are provided with yield or stop control, detectable warning surfaces should be provided at the junction between the pedestrian route and the vehicular route. Where pedestrian at-grade rail crossings are located within a street or highway, detectable warning surfaces at the curb ramps or blended transitions make a second set of detectable warning surfaces at the rail crossing unnecessary.
Detectable warning surfaces are not intended to provide wayfinding for pedestrians who are blind or have low vision. Wayfinding can be made easier by:
•Sidewalks that provide a clear path free of street furniture;
•Visual contrast between walking and non-walking areas (e.g., planted borders);
•Route edges that are clear and detectable by cane;
•Direct pedestrian street crossings and curb ramps that are in-line with direction of travel;
•Small corner radiuses that permit pedestrian street crossings to be as short and direct as possible;
•Orthogonal intersections that facilitate navigation using parallel and perpendicular vehicle sound cues;
•and barriers where pedestrian travel or crossing is not permitted.

Recommendation:
Replace this ramp.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
CSFD
Image of finding
Image that depicts the citation requirements of the code or standard

Exterior - Entrance

BFID: 184364

The walkway contains abrupt vertical edges and/or variations over a 1/4 inch.

1/4 inch is the maximum vertical rise. Changes in level between 1/4 inch and 1/2 inch must be beveled at 1:2 or less.

Changes in level greater than 1/2 inch must be by way of a ramp.
Citation:
2010 ADAS Section 303.3
Changes in level between 1/4 inch (6.4 mm) high minimum and 1/2 inch (13 mm) high maximum shall be beveled with a slope not steeper than 1:2.

2010 ADAS Section 303.2
Changes in level of 1/4 inch (6.4 mm) high maximum shall be permitted to be vertical.

Recommendation:
Grind to level or fill as need to reduce vertical displacement.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
CSFD
Image of finding
Image that depicts the citation requirements of the code or standard
Additional Finding Photos
Finding 184364 Additional Photo

Men's Restroom

BFID: 184365

The wall sign is mounted too high.

Tactile Characters on signs shall be located 48 inches minimum above the finish floor or ground surface, measured from the baseline of the lowest tactile character and 60 inches maximum above the finish floor or ground surface, measured from the baseline of the highest tactile character. Mounting location shall be determined so that a person may approach within 3 inches of signage without encountering protruding objects and shall be located so that a clear floor space of 18 inches minimum by 18 inches minimum, centered on the tactile Characters, is provided beyond the arc of any door swing between the closed position and 45 degree open position.
Citation:
2010 ADAS Section 703.4.1
Tactile characters on signs shall be located 48 inches (1220 mm) minimum above the finish floor or ground surface, measured from the baseline of the lowest tactile character and 60 inches (1525 mm) maximum above the finish floor or ground surface, measured from the baseline of the highest tactile character.

Recommendation:
Lower the sign to 60" to the top edge.
Barrier Priority:
Important (2): Should be completed as soon as possible. (Includes findings that would remove barriers to the greatest number of people to your goods and services)
Department:
CSFD
Image of finding
Image that depicts the citation requirements of the code or standard

BFID: 184367

The door exceeds the maximum pressure to open the door.

Interior doors shall have a maximum opening force of 5 pounds.

These forces do not apply to the force required to retract latch bolts or disengage other devices that hold the door or gate in a closed position. Door closers and gate closers shall be adjusted so that from an open position of 90 degrees, the time required to move the door to a position of 12 degrees from the latch is 5 seconds minimum.

Door and gate spring hinges shall be adjusted so that from the open position of 70 degrees, the door or gate shall move to the closed position in 1.5 seconds minimum.
Citation:
2010 ADAS Section 404.2.9
Fire doors shall have a minimum opening force allowable by the appropriate administrative authority. The force for pushing or pulling open a door or gate other than fire doors shall be as follows: 1. Interior hinged doors and gates: 5 pounds (22.2 N) maximum. 2. Sliding or folding doors: 5 pounds (22.2 N) maximum. These forces do not apply to the force required to retract latch bolts or disengage other devices that hold the door or gate in a closed position.

Recommendation:
Adjust the door closer.
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes findings that have a high financial impact on the entity in relationship to the degree of access provided)
Department:
CSFD
Finding 184367 Main Photo
Additional Finding Photos
Finding 184367 Additional Photo

BFID: 184369

The mirror is mounted too high.

Mirrors must have the bottom edge of the reflecting surface a maximum of 40 inches above the floor if above a sink or counter. Mirrors not located above lavatories or countertops shall be installed with the bottom edge of the reflecting surface 35 inches maximum above the finish floor or ground.
Citation:
2010 ADAS Section 603.3
Mirrors located above lavatories or countertops shall be installed with the bottom edge of the reflecting surface 40 inches (1015 mm) maximum above the finish floor or ground. Mirrors not located above lavatories or countertops shall be installed with the bottom edge of the reflecting surface 35 inches (890 mm) maximum above the finish floor or ground.

Recommendation:
Lower the mirror, or add a full length mirror with the bottom edge no higher than 35".
Barrier Priority:
N/A
Department:
CSFD
Finding 184369 Main Photo
Image that depicts the citation requirements of the code or standard
Additional Finding Photos
Finding 184369 Additional Photo

BFID: 184371

The rear grab bar is too high.

Grab bars shall be installed in a horizontal position, 33 inches minimum and 36 inches maximum above the finish floor measured to the top of the gripping surface and the space between the grab bar and the top of the tank shall be 1-1/2 inches minimum.
Citation:
2010 ADAS Section 609.4
Grab bars shall be installed in a horizontal position, 33 inches (840 mm) minimum and 36 inches (915 mm) maximum above the finish floor measured to the top of the gripping surface, except that at water closets for children's use complying with 604.9, grab bars shall be installed in a horizontal position 18 inches (455 mm) minimum and 27 inches (685 mm) maximum above the finish floor measured to the top of the gripping surface. The height of the lower grab bar on the back wall of a bathtub shall comply with 607.4.1.1 or 607.4.2.1.

Recommendation:
Lower the grab bar.
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes findings that have a high financial impact on the entity in relationship to the degree of access provided)
Department:
CSFD
Finding 184371 Main Photo
Image that depicts the citation requirements of the code or standard
Additional Finding Photos
Finding 184371 Additional Photo

BFID: 184373

The side grab bar is too high.

Grab bars shall be installed in a horizontal position, 33 inches minimum and 36 inches maximum above the finish floor measured to the top of the gripping surface and the space between the grab bar and the top of the tank shall be 1-1/2 inches minimum.
Citation:
2010 ADAS Section 609.4
Grab bars shall be installed in a horizontal position, 33 inches (840 mm) minimum and 36 inches (915 mm) maximum above the finish floor measured to the top of the gripping surface, except that at water closets for children's use complying with 604.9, grab bars shall be installed in a horizontal position 18 inches (455 mm) minimum and 27 inches (685 mm) maximum above the finish floor measured to the top of the gripping surface. The height of the lower grab bar on the back wall of a bathtub shall comply with 607.4.1.1 or 607.4.2.1.

Recommendation:
Lower the grab bar.
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes findings that have a high financial impact on the entity in relationship to the degree of access provided)
Department:
CSFD
Finding 184373 Main Photo
Image that depicts the citation requirements of the code or standard
Additional Finding Photos
Finding 184373 Additional Photo

BFID: 194769

The toilet is not located within the range allowed from the side wall or partition.

The centerline of the toilet must be 16 to 18 inches from the side wall.
Citation:
2010 ADAS Section 604.2
The water closet shall be positioned with a wall or partition to the rear and to one side. The centerline of the water closet shall be 16 inches (405 mm) minimum to 18 inches (455 mm) maximum from the side wall or partition, except that the water closet shall be 17 inches (430 mm) minimum and 19 inches (485 mm) maximum from the side wall or partition in the ambulatory accessible toilet compartment specified in 604.8.2. Water closets shall be arranged for a left-hand or right-hand approach.

Recommendation:
Remove and reset toilet to compliance.
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes findings that have a high financial impact on the entity in relationship to the degree of access provided)
Department:
CSFD
Image of finding
Image that depicts the citation requirements of the code or standard

BFID: 194770

The clear floor space only allows for a forward approach and the element is out of reach range.

Where a forward reach is unobstructed, the high forward reach shall be 48 inches maximum and the low forward reach shall be 15 inches minimum above the finish floor or ground.
Citation:
2010 ADAS Section 308.2.1
Where a forward reach is unobstructed, the high forward reach shall be 48 inches (1220 mm) maximum and the low forward reach shall be 15 inches (380 mm) minimum above the finish floor or ground.

Recommendation:
Lower dispenser to compliance.
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes findings that have a high financial impact on the entity in relationship to the degree of access provided)
Department:
CSFD
Image of finding
Image that depicts the citation requirements of the code or standard

Women's Restroom

BFID: 184366

The wall sign is mounted too high.

Tactile Characters on signs shall be located 48 inches minimum above the finish floor or ground surface, measured from the baseline of the lowest tactile character and 60 inches maximum above the finish floor or ground surface, measured from the baseline of the highest tactile character. Mounting location shall be determined so that a person may approach within 3 inches of signage without encountering protruding objects and shall be located so that a clear floor space of 18 inches minimum by 18 inches minimum, centered on the tactile Characters, is provided beyond the arc of any door swing between the closed position and 45 degree open position.
Citation:
2010 ADAS Section 703.4.1
Tactile characters on signs shall be located 48 inches (1220 mm) minimum above the finish floor or ground surface, measured from the baseline of the lowest tactile character and 60 inches (1525 mm) maximum above the finish floor or ground surface, measured from the baseline of the highest tactile character.

Recommendation:
Lower the sign to 60" to the top edge.
Barrier Priority:
Important (2): Should be completed as soon as possible. (Includes findings that would remove barriers to the greatest number of people to your goods and services)
Department:
CSFD
Finding 184366 Main Photo
Image that depicts the citation requirements of the code or standard
Additional Finding Photos
Finding 184366 Additional Photo

BFID: 184368

The door exceeds the maximum pressure to open the door.

Interior doors shall have a maximum opening force of 5 pounds.

These forces do not apply to the force required to retract latch bolts or disengage other devices that hold the door or gate in a closed position. Door closers and gate closers shall be adjusted so that from an open position of 90 degrees, the time required to move the door to a position of 12 degrees from the latch is 5 seconds minimum.

Door and gate spring hinges shall be adjusted so that from the open position of 70 degrees, the door or gate shall move to the closed position in 1.5 seconds minimum.
Citation:
2010 ADAS Section 404.2.9
Fire doors shall have a minimum opening force allowable by the appropriate administrative authority. The force for pushing or pulling open a door or gate other than fire doors shall be as follows: 1. Interior hinged doors and gates: 5 pounds (22.2 N) maximum. 2. Sliding or folding doors: 5 pounds (22.2 N) maximum. These forces do not apply to the force required to retract latch bolts or disengage other devices that hold the door or gate in a closed position.

Recommendation:
Adjust the door closer.
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes findings that have a high financial impact on the entity in relationship to the degree of access provided)
Department:
CSFD
Finding 184368 Main Photo
Additional Finding Photos
Finding 184368 Additional Photo

BFID: 184370

The mirror is mounted too high.

Mirrors must have the bottom edge of the reflecting surface a maximum of 40 inches above the floor if above a sink or counter. Mirrors not located above lavatories or countertops shall be installed with the bottom edge of the reflecting surface 35 inches maximum above the finish floor or ground.
Citation:
2010 ADAS Section 603.3
Mirrors located above lavatories or countertops shall be installed with the bottom edge of the reflecting surface 40 inches (1015 mm) maximum above the finish floor or ground. Mirrors not located above lavatories or countertops shall be installed with the bottom edge of the reflecting surface 35 inches (890 mm) maximum above the finish floor or ground.

Recommendation:
Lower the mirror, or add a full length mirror with the bottom edge no higher than 35".
Barrier Priority:
N/A
Department:
CSFD
Finding 184370 Main Photo
Image that depicts the citation requirements of the code or standard
Additional Finding Photos
Finding 184370 Additional Photo

BFID: 184372

The rear grab bar is too high.

Grab bars shall be installed in a horizontal position, 33 inches minimum and 36 inches maximum above the finish floor measured to the top of the gripping surface and the space between the grab bar and the top of the tank shall be 1-1/2 inches minimum.
Citation:
2010 ADAS Section 609.4
Grab bars shall be installed in a horizontal position, 33 inches (840 mm) minimum and 36 inches (915 mm) maximum above the finish floor measured to the top of the gripping surface, except that at water closets for children's use complying with 604.9, grab bars shall be installed in a horizontal position 18 inches (455 mm) minimum and 27 inches (685 mm) maximum above the finish floor measured to the top of the gripping surface. The height of the lower grab bar on the back wall of a bathtub shall comply with 607.4.1.1 or 607.4.2.1.

Recommendation:
Lower the grab bar.
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes findings that have a high financial impact on the entity in relationship to the degree of access provided)
Department:
CSFD
Finding 184372 Main Photo
Image that depicts the citation requirements of the code or standard
Additional Finding Photos
Finding 184372 Additional Photo

BFID: 184374

The side grab bar is too high.

Grab bars shall be installed in a horizontal position, 33 inches minimum and 36 inches maximum above the finish floor measured to the top of the gripping surface and the space between the grab bar and the top of the tank shall be 1-1/2 inches minimum.
Citation:
2010 ADAS Section 609.4
Grab bars shall be installed in a horizontal position, 33 inches (840 mm) minimum and 36 inches (915 mm) maximum above the finish floor measured to the top of the gripping surface, except that at water closets for children's use complying with 604.9, grab bars shall be installed in a horizontal position 18 inches (455 mm) minimum and 27 inches (685 mm) maximum above the finish floor measured to the top of the gripping surface. The height of the lower grab bar on the back wall of a bathtub shall comply with 607.4.1.1 or 607.4.2.1.

Recommendation:
Lower the grab bar.
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes findings that have a high financial impact on the entity in relationship to the degree of access provided)
Department:
CSFD
Finding 184374 Main Photo
Image that depicts the citation requirements of the code or standard
Additional Finding Photos
Finding 184374 Additional Photo

BFID: 191334

The flush handle is located on the wrong side of the toilet.

Controls shall be operable with one hand and shall not require tight grasping, pinching, or twisting. Controls for the flush valves shall be mounted on the wide side of toilet areas, no more than 48 inches above the floor.
Citation:
2010 ADAS Section 604.6
Flush controls shall be hand operated or automatic. Hand operated flush controls shall comply with 309. Flush controls shall be located on the open side of the water closet except in ambulatory accessible compartments complying with 604.8.2.

Recommendation:
Change the tank to relocate the flush.
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes findings that have a high financial impact on the entity in relationship to the degree of access provided)
Department:
CSFD
Image of finding

BFID: 194771

The clear floor space only allows for a forward approach and the element is out of reach range.

Where a forward reach is unobstructed, the high forward reach shall be 48 inches maximum and the low forward reach shall be 15 inches minimum above the finish floor or ground.
Citation:
2010 ADAS Section 308.2.1
Where a forward reach is unobstructed, the high forward reach shall be 48 inches (1220 mm) maximum and the low forward reach shall be 15 inches (380 mm) minimum above the finish floor or ground.

Recommendation:
Remove and re-install the dispenser to compliance.
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes findings that have a high financial impact on the entity in relationship to the degree of access provided)
Department:
CSFD
Image of finding
Image that depicts the citation requirements of the code or standard

BFID: 191335

The paper towel dispenser projects more than 4 inches into the circulation path.

Wall-mounted objects that have leading edges between 27 inches and 80 inches from the floor must not project more than 4 inches into the circulation path. Protruding objects that extend to the floor or within 27 inches of the floor are cane detectable and are therefore not hazardous. Where it is necessary or desirable to have objects protrude from the wall, a manner of cane detection must be provided.
Citation:
2010 ADAS Section 307.2
Objects with leading edges more than 27 inches (685 mm) and not more than 80 inches (2030 mm) above the finish floor or ground shall protrude 4 inches (100 mm) maximum horizontally into the circulation path.

Recommendation:
Relocated the paper towel dispenser.
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes findings that have a high financial impact on the entity in relationship to the degree of access provided)
Department:
CSFD
Image of finding
Image that depicts the citation requirements of the code or standard

Interior - Community Room

BFID: 184375

Compliant room identification signs are missing on the strike side of the door.
Where a tactile sign is provided at double doors with one active leaf, the sign shall be located on the inactive leaf. Where a tactile sign is provided at double doors with two active leafs, the sign shall be located to the right of the right hand door. Where there is no wall space at the latch side of a single door or at the right side of double doors, signs shall be located on the nearest adjacent wall.

Wall signs identifying permanent rooms and spaces of a building shall be in a horizontal format and the characters raised 1/32 inch minimum and shall be sans serif uppercase characters a minimum of 5/8 inch and a maximum of 2 inches high. Contracted Grade 2 Braille shall be in a horizontal format and shall be placed a minimum of 3/8 inch and a maximum of 1/2 inch directly below the tactile characters; flush left or centered. Dots shall be 1/10 inch on center in each cell with 2/10-inch space between cells, measured from the second column of dots in the first cell to the first column of dots in the second cell. Dots shall be raised a minimum of 1/40 inch above the background. Braille dots shall be domed or rounded. Signs with raised characters or Braille shall be located 48 inches minimum above the finish floor or ground surface, measured from the baseline of the lowest tactile character and 60 inches maximum above the finish floor or ground surface, measured from the baseline of the highest tactile character.
Citation:
2010 ADAS Section 216.2
Interior and exterior signs identifying permanent rooms and spaces shall comply with 703.1, 703.2, and 703.5. Where pictograms are provided as designations of permanent interior rooms and spaces, the pictograms shall comply with 703.6 and shall have text descriptors complying with 703.2 and 703.5.

2010 ADAS Section 703.4.2
Where a tactile sign is provided at a door, the sign shall be located alongside the door at the latch side. Where a tactile sign is provided at double doors with one active leaf, the sign shall be located on the inactive leaf. Where a tactile sign is provided at double doors with two active leafs, the sign shall be located to the right of the right hand door. Where there is no wall space at the latch side of a single door or at the right side of double doors, signs shall be located on the nearest adjacent wall. Signs containing tactile characters shall be located so that a clear floor space of 18 inches (455 mm) minimum by 18 inches (455 mm) minimum, centered on the tactile characters, is provided beyond the arc of any door swing between the closed position and 45 degree open position.

Recommendation:
Install compliant signage. Due to the soda machine being located on the right side of the doors, place the signage on the left side at 60" maximum to the top edge.
Barrier Priority:
Important (2): Should be completed as soon as possible. (Includes findings that would remove barriers to the greatest number of people to your goods and services)
Department:
CSFD
Image of finding
Image that depicts the citation requirements of the code or standard

BFID: 184376

The door must have a smooth surface within 10 inches of the floor on the push side.

Swinging door surfaces within 10 inches of the finish floor or ground measured vertically must have a smooth surface on the push side extending the full width of the door. Parts creating horizontal or vertical joints in these surfaces shall be within 1/16 inch of the same plane as the other. All gates, including ticket gates, shall meet all applicable specifications for doors.
Citation:
2010 ADAS Section 404.2.10
Swinging door and gate surfaces within 10 inches (255 mm) of the finish floor or ground measured vertically shall have a smooth surface on the push side extending the full width of the door or gate. Parts creating horizontal or vertical joints in these surfaces shall be within 1/16 inch (1.6 mm) of the same plane as the other. Cavities created by added kick plates shall be capped.

Recommendation:
Explore alternate door locking mechanism that will allow for a smooth kick plate. Take off door stops.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
CSFD
Image of finding
Image that depicts the citation requirements of the code or standard

BFID: 184377

The paper towel and wipes dispensers are positioned too high for either a side or front approach.

Where a clear floor or ground space allows a parallel approach to an element and the side reach is unobstructed, the high side reach shall be 48 inches maximum and the low side reach shall be 15 inches minimum above the finish floor or ground.

Where a forward reach is unobstructed, the high forward reach shall be 48 inches maximum and the low forward reach shall be 15 inches minimum above the finish floor or ground.
Citation:
2010 ADAS Section 308.1
Reach ranges shall comply with 308.

Recommendation:
Relocate the dispensers so that operable feature is under 48".
Barrier Priority:
Low (4): Should be completed as soon as possible due to being a technical violation, but may not result in providing greater access to persons with disabilities. (Includes findings that are technically violations but provide a moderate to low increase in accessibility compared to the financial impact on the entity)
Department:
CSFD
Image of finding
Image that depicts the citation requirements of the code or standard

BFID: 184378

The route contains openings greater than 1/2 inch.

Openings in floor or ground surfaces shall not allow passage of a sphere more than 1/2 inch diameter. Elongated openings shall be placed so that the long dimension is perpendicular to the dominant direction of travel.
Citation:
2010 ADAS Section 302.3
Openings in floor or ground surfaces shall not allow passage of a sphere more than 1/2 inch (13 mm) diameter except as allowed in 407.4.3, 409.4.3, 410.4, 810.5.3 and 810.10. Elongated openings shall be placed so that the long dimension is perpendicular to the dominant direction of travel.

Recommendation:
Replace access panel or cap that fills the hole.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
CSFD
Finding 184378 Main Photo
Additional Finding Photos
Finding 184378 Additional Photo