Crystal Reservoir Area
BFID: 190232
There is no accessible route to the element.
At least one accessible route shall connect accessible buildings, accessible facilities, accessible elements, and accessible spaces that are on the same site.
Citation:
2015 IBC Section 1104.2
At least one accessible route shall connect accessible buildings, accessible facilities, accessible elements and accessible spaces that are on the same site.
2010 ADAS Section 206.2.2
At least one accessible route shall connect accessible buildings, accessible facilities, accessible elements, and accessible spaces that are on the same site.
As Built:
These informational signs are on a grade of up to 8% in gravel that is not firm, stable or slip resistant.
Recommendation:
Either move signs or create accessible route to them or replicated information and place at accessible location.
Barrier Priority:
Important (2): Should be completed as soon as possible. (Includes findings that would remove barriers to the greatest number of people to your goods and services)
Department:
Parks & Recreation
Additional Finding Photos
BFID: 190233
The path of contains multiple issues and is not accessible. The upper two tables are near the parking area and restrooms. The lower table is some distance down a very inaccessible route that is up to 18% cross slope and 10% running slope.
The path of travel exceeds the maximum allowable cross and running slope requirements. It also contains changes in level and/or gaps that exceed the allowable maximum requirements. The path of travel does not meet the minimum width requirements for clearances, turning spaces, and/or passing spaces. The floor or ground surface is not firm, stable, and slip resistant.
Citation:
2010 ADAS Section 403.1
Walking surfaces that are a part of an accessible route shall comply with 403.
As Built:
There is no accessible route to the 3 picnic tables. At least one or 5% should be accessible.
Recommendation:
Do nothing since nearby at Pikes Peak Crystal Reservoir we have 7 on hard surface including 1 that is accessible.
Barrier Priority:
Low (4): Should be completed as soon as possible due to being a technical violation, but may not result in providing greater access to persons with disabilities. (Includes findings that are technically violations but provide a moderate to low increase in accessibility compared to the financial impact on the entity)
Department:
Parks & Recreation
Additional Finding Photos
BFID: 190234
The accessible route contains loose gravel and/or surface materials that do not provide for a stable, firm slip resistant surface.
Citation:
2010 ADAS Section 302.1
Floor and ground surfaces shall be stable, firm, and slip resistant and shall comply with 302.
As Built:
The sidewalk is not firm, stable or slip resistant.
Recommendation:
Create a barrier to keep loose gravel from going on the sidewalk.
Barrier Priority:
Low (4): Should be completed as soon as possible due to being a technical violation, but may not result in providing greater access to persons with disabilities. (Includes findings that are technically violations but provide a moderate to low increase in accessibility compared to the financial impact on the entity)
Department:
Parks & Recreation
BFID: 190235
There is no accessible route to the mono-filament receptacle..
At least one accessible route shall connect accessible buildings, accessible facilities, accessible elements, and accessible spaces that are on the same site.
Citation:
2015 IBC Section 1104.2
At least one accessible route shall connect accessible buildings, accessible facilities, accessible elements and accessible spaces that are on the same site.
2010 ADAS Section 206.2.2
At least one accessible route shall connect accessible buildings, accessible facilities, accessible elements, and accessible spaces that are on the same site.
As Built:
There is no accessible route to the mono-filament receptacle. It is 5'6" distance off the sidewalk and is on a slope over 5% with a 1-2" area of vertical displacement to get to it.
Recommendation:
Have this relocated next to accessible route and/or create a route to it.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
BFID: 190237
The accessible route has running slopes greater than 5% and has not been constructed as a ramp (i.e. handrails,edge protection, etc.). Cross slopes are greater than 2% across the width of the walk.
When the slope in the direction of travel of any walk exceeds 1 unit vertical in 20 units horizontal (5-percent slope), it must be constructed as a ramp. Surface cross slopes must not exceed 1 unit vertical in 48 units horizontal (2-percent slope).
Citation:
2010 ADAS Section 403.3
The running slope of walking surfaces shall not be steeper than 1:20. The cross slope of walking surfaces shall not be steeper than 1:48.
As Built:
The sidewalk pad turning space to reach the restrooms has a 3.3% cross slope and a 2.8% running slope.
Recommendation:
Redo this pad to 2% maximum in every direction.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Additional Finding Photos
BFID: 190238
The accessible route has running slopes greater than 5% and has not been constructed as a ramp (i.e. handrails,edge protection, etc.). Cross slopes are greater than 2% across the width of the walk.
When the slope in the direction of travel of any walk exceeds 1 unit vertical in 20 units horizontal (5-percent slope), it must be constructed as a ramp. Surface cross slopes must not exceed 1 unit vertical in 48 units horizontal (2-percent slope).
Citation:
2010 ADAS Section 403.3
The running slope of walking surfaces shall not be steeper than 1:20. The cross slope of walking surfaces shall not be steeper than 1:48.
As Built:
The sidewalk pads in front of the right set of men's and women's restrooms have 3 pads with high cross slopes. The corner upper connector has a 2.3% cross slope, the women's pad is 2.9% and the one in front of the men's is 3.4%. There is also an area of 3/4" of vertical displacement.
Recommendation:
Redo these pads to 2% maximum in every direction in front of the restrooms..
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Additional Finding Photos
BFID: 190239
The accessible route has running slopes greater than 5% and has not been constructed as a ramp (i.e. handrails,edge protection, etc.). Cross slopes are greater than 2% across the width of the walk.
When the slope in the direction of travel of any walk exceeds 1 unit vertical in 20 units horizontal (5-percent slope), it must be constructed as a ramp. Surface cross slopes must not exceed 1 unit vertical in 48 units horizontal (2-percent slope).
Citation:
2010 ADAS Section 403.3
The running slope of walking surfaces shall not be steeper than 1:20. The cross slope of walking surfaces shall not be steeper than 1:48.
As Built:
The sidewalk pads in front of the left set of men's and women's restrooms have 4 pads with high cross slopes. The corner upper connector has a 3.9% cross slope, the adjacent pad is 4.6%, the women's pad is 5.1% and the one in front of the men's is 5%.
Recommendation:
Fix the right set of restrooms and make these the non-accessible ones. Do nothing with this at this time.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Additional Finding Photos
BFID: 190240
The accessible route on the site has running slopes greater than 5% and has not been constructed as a ramp (i.e. handrails, edge protection, etc.).
When the slope in the direction of travel of any walk exceeds 1 unit vertical in 20 units horizontal (5-percent slope), it must be constructed as a ramp. Surface cross slopes must not exceed one unit vertical in 48 units horizontal (2-percent slope).
Citation:
2010 ADAS Section 403.3
The running slope of walking surfaces shall not be steeper than 1:20. The cross slope of walking surfaces shall not be steeper than 1:48.
As Built:
The sidewalk pads in front of the left set of men's and women's restrooms have 3 pads with high running slopes. The slopes range from 6.3-7.5%. The short adjacent connector has a 1" gap.
Recommendation:
Leave as is. Make the right set the accessible ones.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Additional Finding Photos
BFID: 190241
The accessible path of travel has cross slopes greater than 2%.
Surface cross slopes shall not exceed one unit vertical in 48 units horizontal (2-percent slope). When the slope in the direction of travel of any walk exceeds 1 unit vertical in 20 units horizontal (5-percent slope), it must be constructed as a ramp.
Citation:
2010 ADAS Section 403.3
The running slope of walking surfaces shall not be steeper than 1:20. The cross slope of walking surfaces shall not be steeper than 1:48.
As Built:
The main sidewalk leading to the pier has 8 pads from the first "right set" of restrooms to the turn area leading to the fish cleaning station that have slope issues. The cross slopes range from 2.3-5.9% and one running slope is 5.3%.
Recommendation:
Fix the 8 pads with cross slope issues.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Additional Finding Photos
BFID: 190242
The accessible route has running slopes greater than 5% and has not been constructed as a ramp (i.e. handrails,edge protection, etc.). Cross slopes are greater than 2% across the width of the walk.
When the slope in the direction of travel of any walk exceeds 1 unit vertical in 20 units horizontal (5-percent slope), it must be constructed as a ramp. Surface cross slopes must not exceed 1 unit vertical in 48 units horizontal (2-percent slope).
Citation:
2010 ADAS Section 403.3
The running slope of walking surfaces shall not be steeper than 1:20. The cross slope of walking surfaces shall not be steeper than 1:48.
As Built:
The main sidewalk turn area to go to the fish cleaning station has 2 pads with a 6% running slope and a 4.8% cross slope and the other has a 5% running slope and a 3.8% cross slope. Further there is a 1" gap in this area.
Recommendation:
Redo this to make the turn area 2% or less in every direction. Take care of the gap in the re-pour.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Additional Finding Photos
BFID: 190243
The accessible route has running slopes greater than 5% and has not been constructed as a ramp (i.e. handrails,edge protection, etc.). Cross slopes are greater than 2% across the width of the walk.
When the slope in the direction of travel of any walk exceeds 1 unit vertical in 20 units horizontal (5-percent slope), it must be constructed as a ramp. Surface cross slopes must not exceed 1 unit vertical in 48 units horizontal (2-percent slope).
Citation:
2010 ADAS Section 403.3
The running slope of walking surfaces shall not be steeper than 1:20. The cross slope of walking surfaces shall not be steeper than 1:48.
As Built:
The sidewalk leading to the fish cleaning station has 4 pads with very high cross slopes and 1 with a high running slope. The running slope is 6%, the cross slopes range from 4-10.9% cross slope.
Recommendation:
Redo the first 4 pads leading down to make under 5% running slope and 2% cross slope.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
BFID: 190244
The work surface is not within the allowable range.
The tops of work surfaces provided for public use or common use shall be 28 inches minimum and 34 inches maximum above the finish floor or ground.
Citation:
2010 ADAS Section 902.3
The tops of dining surfaces and work surfaces shall be 28 inches (710 mm) minimum and 34 inches (865 mm) maximum above the finish floor or ground.
As Built:
The fish cleaning station is 35-36" high from the surface. Ideally it should be 34" or less.
Recommendation:
Lower to 34" maximum from floor. It appears it is adjustable. If not leave as is.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
BFID: 190245
The accessible route on the site has running slopes greater than 5% and has not been constructed as a ramp (i.e. handrails, edge protection, etc.).
When the slope in the direction of travel of any walk exceeds 1 unit vertical in 20 units horizontal (5-percent slope), it must be constructed as a ramp. Surface cross slopes must not exceed one unit vertical in 48 units horizontal (2-percent slope).
Citation:
2010 ADAS Section 403.3
The running slope of walking surfaces shall not be steeper than 1:20. The cross slope of walking surfaces shall not be steeper than 1:48.
As Built:
The sidewalk leading to the fishing piers have 23 pads with running slopes ranging from 5.1-9.3%. It is in the 7-8% range at the turn point into the bridge. The range prior to the bridge is 6.3-9.3% and the range after the bridge is 5.1 to 7.2%.
Recommendation:
Put in ramp to make this an accessible route. This will be difficult to do in this space and will require multiple landings with handrails.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
BFID: 190246
The accessible route has running slopes greater than 5% and has not been constructed as a ramp (i.e. handrails,edge protection, etc.). Cross slopes are greater than 2% across the width of the walk.
When the slope in the direction of travel of any walk exceeds 1 unit vertical in 20 units horizontal (5-percent slope), it must be constructed as a ramp. Surface cross slopes must not exceed 1 unit vertical in 48 units horizontal (2-percent slope).
Citation:
2010 ADAS Section 403.3
The running slope of walking surfaces shall not be steeper than 1:20. The cross slope of walking surfaces shall not be steeper than 1:48.
As Built:
The turning area going to a bridge and then the first pier has a 6.6% running slope and 6.7% cross slope, the next pad has a 6.1 % running slope and 3.7% cross slope and another pad with a 6.1% running slope.
Recommendation:
The turning area needs to be 2% maximum in all directions, the pads should be under 5% running slopes and a 2% cross slope.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Additional Finding Photos
BFID: 190247
The accessible path of travel has cross slopes greater than 2%.
Surface cross slopes shall not exceed one unit vertical in 48 units horizontal (2-percent slope). When the slope in the direction of travel of any walk exceeds 1 unit vertical in 20 units horizontal (5-percent slope), it must be constructed as a ramp.
Citation:
2010 ADAS Section 403.3
The running slope of walking surfaces shall not be steeper than 1:20. The cross slope of walking surfaces shall not be steeper than 1:48.
As Built:
The sidewalk leading to the second fishing pier has 13 pads with cross slopes between 2.7-5.3%. There is also an area of 3/4" vertical displacement.
Recommendation:
Fix all pads to 2% cross slope.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Additional Finding Photos
BFID: 190248
The accessible path of travel has cross slopes greater than 2%.
Surface cross slopes shall not exceed one unit vertical in 48 units horizontal (2-percent slope). When the slope in the direction of travel of any walk exceeds 1 unit vertical in 20 units horizontal (5-percent slope), it must be constructed as a ramp.
Citation:
2010 ADAS Section 403.3
The running slope of walking surfaces shall not be steeper than 1:20. The cross slope of walking surfaces shall not be steeper than 1:48.
As Built:
The sidewalk leading to the second fishing pier has 9 out of 10 pads with running and / or cross slope issues. The 6 running slopes issues range from 5.2-11.9% and the 6 cross slope issues range from 2.7-5.5%.
Recommendation:
Fix all pads to 2% cross slope and under 5% running slope. If not feasible then make proper ramps.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Additional Finding Photos
BFID: 190250
The curb or barrier does not extend 2 inches minimum above the surface.
Where compliant railings, guards, or handrails are provided, edge protection shall also be provided.
Curbs or barriers shall extend 2 inches minimum above the surface of the fishing pier or platform or The ground or deck surface shall extend 12 inches minimum beyond the inside face of the railing. Toe clearance shall be provided and shall be 30 inches wide minimum and 9 inches minimum above the ground or deck surface beyond the railing.
Citation:
2010 ADAS Section 1005.3.1
Curbs or barriers shall extend 2 inches (51 mm) minimum above the surface of the fishing pier or platform.
As Built:
We frequently have 1-6" gaps of edge protection surrounding the pier. These should not be. We need full coverage where we have railings.
Recommendation:
Add in additional protection around the pier.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Additional Finding Photos
BFID: 190249
The handrail is too high.
At least 25 percent of the railings, guards, or handrails shall be 34 inches maximum above the ground or deck surface.
Citation:
2010 ADAS Section 1005.2.1
At least 25 percent of the railings, guards, or handrails shall be 34 inches (865 mm) maximum above the ground or deck surface.
As Built:
The railing all measures 43" high.
Recommendation:
Lower multiple areas to 34" high.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Additional Finding Photos
BFID: 190251
The accessible route on the site has running slopes greater than 5% and has not been constructed as a ramp (i.e. handrails, edge protection, etc.).
When the slope in the direction of travel of any walk exceeds 1 unit vertical in 20 units horizontal (5-percent slope), it must be constructed as a ramp. Surface cross slopes must not exceed one unit vertical in 48 units horizontal (2-percent slope).
Citation:
2010 ADAS Section 403.3
The running slope of walking surfaces shall not be steeper than 1:20. The cross slope of walking surfaces shall not be steeper than 1:48.
As Built:
The bridge grade is up to 6.7% running slope. The bridge lacks edge protection and appropriate handrails.
Recommendation:
Add edge protection, handrails and level landings on each side of the bridge.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Additional Finding Photos
BFID: 190252
The accessible route on the site has running slopes greater than 5% and has not been constructed as a ramp (i.e. handrails, edge protection, etc.).
When the slope in the direction of travel of any walk exceeds 1 unit vertical in 20 units horizontal (5-percent slope), it must be constructed as a ramp. Surface cross slopes must not exceed one unit vertical in 48 units horizontal (2-percent slope).
Citation:
2010 ADAS Section 403.3
The running slope of walking surfaces shall not be steeper than 1:20. The cross slope of walking surfaces shall not be steeper than 1:48.
As Built:
The route from the bridge to the boat slip has 11 pads between 6-8.7% running slope.
Recommendation:
Eventually create an accessible route to the boat slip. This will require adding ramp provisions and level landings this distance. This should be feasible to accomplish.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Additional Finding Photos
BFID: 190253
The element projects more than 4 inches into the circulation path.
Wall-mounted objects that have leading edges between 27 inches and 80 inches from the floor must not project more than 4 inches into the circulation path. Protruding objects that extend to the floor or within 27 inches of the floor are cane detectable and are therefore not hazardous. Where it is necessary or desirable to have objects protrude from the wall, a manner of cane detection must be provided.
Citation:
2010 ADAS Section 307.2
Objects with leading edges more than 27 inches (685 mm) and not more than 80 inches (2030 mm) above the finish floor or ground shall protrude 4 inches (100 mm) maximum horizontally into the circulation path.
As Built:
The route from the bridge to the boat slip has many areas where trees project into the route of travel.
Recommendation:
Trim back and / or remove some trees out of the path of travel.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
BFID: 190254
The minimum number of boarding piers are not accessible.
There are multiple boating piers on launch ramps and 0 boating piers designated as accessible.
Where boarding piers are provided at boat launch ramps, at least 5 percent, but no fewer than one, of the boarding piers be accessible.
Citation:
2010 ADAS Section 235.3
Where boarding piers are provided at boat launch ramps, at least 5 percent, but no fewer than one, of the boarding piers shall comply with 1003.3.2.
As Built:
The route to the boat slip has an 9.5" high step at the gangway. This may be because of low water levels.
Recommendation:
If step due to low water levels then do nothing at this time.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Crystal Reservoir Restrooms
BFID: 190220
A compliant room identification sign is missing on the strike side of the door.
Wall signs identifying permanent rooms and spaces of a building shall be a horizontal format and the characters raised 1/32 inch minimum and shall be sans serif uppercase characters a minimum of 5/8 inch and a maximum of 2 inches high. Contracted Grade 2 Braille shall be in a horizontal format and shall be placed a minimum of 3/8 inch and a maximum of 1/2 inch directly below the tactile characters; flush left or centered. Signs with raised characters or Braille shall be located 48 inches minimum above the finish floor or ground surface, measured from the baseline of the lowest tactile character and 60 inches maximum above the finish floor or ground surface, measured from the baseline of the highest tactile character.
Citation:
2010 ADAS Section 216.2
Interior and exterior signs identifying permanent rooms and spaces shall comply with 703.1, 703.2, and 703.5. Where pictograms are provided as designations of permanent interior rooms and spaces, the pictograms shall comply with 703.6 and shall have text descriptors complying with 703.2 and 703.5.
As Built:
There is no accessible sign for the left set men's restroom. It isn't Braille or tactile and posted too high and in the wrong area.
Recommendation:
N/A - Refer to Finding
Department:
Parks & Recreation
BFID: 190222
The door has a locking mechanism that requires tight grasping, pinching or twisting of the wrist.
Door locking mechanisms should be push button and release upon activation of the door hardware.
Citation:
2010 ADAS Section 309.4
Operable parts shall be operable with one hand and shall not require tight grasping, pinching, or twisting of the wrist. The force required to activate operable parts shall be 5 pounds (22.2 N) maximum.
As Built:
The door requires pinching, twisting and grasping in the left set men's restroom.
Recommendation:
Leave as is. Make the right set the accessible ones.
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes findings that have a high financial impact on the entity in relationship to the degree of access provided)
Department:
Parks & Recreation
BFID: 190224
The shelving projects more than 4 inches into the circulation path.
Wall-mounted objects that have leading edges between 27 inches and 80 inches from the floor must not project more than 4 inches into the circulation path. Protruding objects that extend to the floor or within 27 inches of the floor are cane detectable and are therefore not hazardous. Where it is necessary or desirable to have objects protrude from the wall, a manner of cane detection must be provided.
Citation:
2010 ADAS Section 307.2
Objects with leading edges more than 27 inches (685 mm) and not more than 80 inches (2030 mm) above the finish floor or ground shall protrude 4 inches (100 mm) maximum horizontally into the circulation path.
As Built:
The shelving is 41" high and projects 8" from the wall in the path of travel to use the toilet in the left set men's restroom.
Recommendation:
Leave as is. Make the right set the accessible ones.
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes findings that have a high financial impact on the entity in relationship to the degree of access provided)
Department:
Parks & Recreation
Additional Finding Photos
BFID: 190221
A compliant room identification sign is missing on the strike side of the door.
Wall signs identifying permanent rooms and spaces of a building shall be a horizontal format and the characters raised 1/32 inch minimum and shall be sans serif uppercase characters a minimum of 5/8 inch and a maximum of 2 inches high. Contracted Grade 2 Braille shall be in a horizontal format and shall be placed a minimum of 3/8 inch and a maximum of 1/2 inch directly below the tactile characters; flush left or centered. Signs with raised characters or Braille shall be located 48 inches minimum above the finish floor or ground surface, measured from the baseline of the lowest tactile character and 60 inches maximum above the finish floor or ground surface, measured from the baseline of the highest tactile character.
Citation:
2010 ADAS Section 216.2
Interior and exterior signs identifying permanent rooms and spaces shall comply with 703.1, 703.2, and 703.5. Where pictograms are provided as designations of permanent interior rooms and spaces, the pictograms shall comply with 703.6 and shall have text descriptors complying with 703.2 and 703.5.
As Built:
There is no accessible sign for the left set women's restroom. It isn't Braille or tactile and posted too high and in the wrong area.
Recommendation:
Leave as is. Make the right set the accessible ones.
Department:
Parks & Recreation
BFID: 190223
The door has a locking mechanism that requires tight grasping, pinching or twisting of the wrist.
Door locking mechanisms should be push button and release upon activation of the door hardware.
Citation:
2010 ADAS Section 309.4
Operable parts shall be operable with one hand and shall not require tight grasping, pinching, or twisting of the wrist. The force required to activate operable parts shall be 5 pounds (22.2 N) maximum.
As Built:
The door requires pinching, twisting and grasping in the left set women's restroom.
Recommendation:
Leave as is. Make the right set the accessible ones.
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes findings that have a high financial impact on the entity in relationship to the degree of access provided)
Department:
Parks & Recreation
BFID: 190225
The shelving projects more than 4 inches into the circulation path.
Wall-mounted objects that have leading edges between 27 inches and 80 inches from the floor must not project more than 4 inches into the circulation path. Protruding objects that extend to the floor or within 27 inches of the floor are cane detectable and are therefore not hazardous. Where it is necessary or desirable to have objects protrude from the wall, a manner of cane detection must be provided.
Citation:
2010 ADAS Section 307.2
Objects with leading edges more than 27 inches (685 mm) and not more than 80 inches (2030 mm) above the finish floor or ground shall protrude 4 inches (100 mm) maximum horizontally into the circulation path.
As Built:
The shelving is 41" high and projects 8" from the wall in the path of travel to use the toilet in the left set women's restroom.
Recommendation:
Leave as is. Make the right set the accessible ones.
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes findings that have a high financial impact on the entity in relationship to the degree of access provided)
Department:
Parks & Recreation
Additional Finding Photos
BFID: 190226
A compliant room identification sign is missing on the strike side of the door.
Wall signs identifying permanent rooms and spaces of a building shall be a horizontal format and the characters raised 1/32 inch minimum and shall be sans serif uppercase characters a minimum of 5/8 inch and a maximum of 2 inches high. Contracted Grade 2 Braille shall be in a horizontal format and shall be placed a minimum of 3/8 inch and a maximum of 1/2 inch directly below the tactile characters; flush left or centered. Signs with raised characters or Braille shall be located 48 inches minimum above the finish floor or ground surface, measured from the baseline of the lowest tactile character and 60 inches maximum above the finish floor or ground surface, measured from the baseline of the highest tactile character.
Citation:
2010 ADAS Section 216.2
Interior and exterior signs identifying permanent rooms and spaces shall comply with 703.1, 703.2, and 703.5. Where pictograms are provided as designations of permanent interior rooms and spaces, the pictograms shall comply with 703.6 and shall have text descriptors complying with 703.2 and 703.5.
As Built:
There is no accessible sign for the right set men's restroom. It isn't Braille or tactile and posted too high and in the wrong area.
Recommendation:
Install proper ADA sign on the latch side of the door with top edge set at 60". Keep current signage where it is.
Department:
Parks & Recreation
BFID: 190228
The door has a locking mechanism that requires tight grasping, pinching or twisting of the wrist.
Door locking mechanisms should be push button and release upon activation of the door hardware.
Citation:
2010 ADAS Section 309.4
Operable parts shall be operable with one hand and shall not require tight grasping, pinching, or twisting of the wrist. The force required to activate operable parts shall be 5 pounds (22.2 N) maximum.
As Built:
The door requires pinching, twisting and grasping in the right set men's restroom.
Recommendation:
Add additional easy to operate lock that doesn't require pinching, twisting and grasping.
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes findings that have a high financial impact on the entity in relationship to the degree of access provided)
Department:
Parks & Recreation
BFID: 190230
The shelving projects more than 4 inches into the circulation path.
Wall-mounted objects that have leading edges between 27 inches and 80 inches from the floor must not project more than 4 inches into the circulation path. Protruding objects that extend to the floor or within 27 inches of the floor are cane detectable and are therefore not hazardous. Where it is necessary or desirable to have objects protrude from the wall, a manner of cane detection must be provided.
Citation:
2010 ADAS Section 307.2
Objects with leading edges more than 27 inches (685 mm) and not more than 80 inches (2030 mm) above the finish floor or ground shall protrude 4 inches (100 mm) maximum horizontally into the circulation path.
As Built:
The shelving is 41" high and projects 8" from the wall in the path of travel to use the toilet in the right set men's restroom.
Recommendation:
Move the shelving to the rear wall, set at 47"adjacent and slightly over (as much as necessary) rear grab bar and next to wall where door is. This will get it out of the stall entry and route of travel.
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes findings that have a high financial impact on the entity in relationship to the degree of access provided)
Department:
Parks & Recreation
Additional Finding Photos
BFID: 190227
A compliant room identification sign is missing on the strike side of the door.
Wall signs identifying permanent rooms and spaces of a building shall be a horizontal format and the characters raised 1/32 inch minimum and shall be sans serif uppercase characters a minimum of 5/8 inch and a maximum of 2 inches high. Contracted Grade 2 Braille shall be in a horizontal format and shall be placed a minimum of 3/8 inch and a maximum of 1/2 inch directly below the tactile characters; flush left or centered. Signs with raised characters or Braille shall be located 48 inches minimum above the finish floor or ground surface, measured from the baseline of the lowest tactile character and 60 inches maximum above the finish floor or ground surface, measured from the baseline of the highest tactile character.
Citation:
2010 ADAS Section 216.2
Interior and exterior signs identifying permanent rooms and spaces shall comply with 703.1, 703.2, and 703.5. Where pictograms are provided as designations of permanent interior rooms and spaces, the pictograms shall comply with 703.6 and shall have text descriptors complying with 703.2 and 703.5.
As Built:
There is no accessible sign for the right set women's restroom. It isn't Braille or tactile and posted too high and in the wrong area.
Recommendation:
Install proper ADA sign on the latch side of the door with top edge set at 60". Keep current signage where it is.
Department:
Parks & Recreation
BFID: 190229
The door has a locking mechanism that requires tight grasping, pinching or twisting of the wrist.
Door locking mechanisms should be push button and release upon activation of the door hardware.
Citation:
2010 ADAS Section 309.4
Operable parts shall be operable with one hand and shall not require tight grasping, pinching, or twisting of the wrist. The force required to activate operable parts shall be 5 pounds (22.2 N) maximum.
As Built:
The door requires pinching, twisting and grasping in the right set women's restroom.
Recommendation:
Add additional easy to operate lock that doesn't require pinching, twisting and grasping.
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes findings that have a high financial impact on the entity in relationship to the degree of access provided)
Department:
Parks & Recreation
BFID: 190231
The shelving projects more than 4 inches into the circulation path.
Wall-mounted objects that have leading edges between 27 inches and 80 inches from the floor must not project more than 4 inches into the circulation path. Protruding objects that extend to the floor or within 27 inches of the floor are cane detectable and are therefore not hazardous. Where it is necessary or desirable to have objects protrude from the wall, a manner of cane detection must be provided.
Citation:
2010 ADAS Section 307.2
Objects with leading edges more than 27 inches (685 mm) and not more than 80 inches (2030 mm) above the finish floor or ground shall protrude 4 inches (100 mm) maximum horizontally into the circulation path.
As Built:
The shelving is 41" high and projects 8" from the wall in the path of travel to use the toilet in the right set women's restroom.
Recommendation:
Move the shelving to the rear wall, set at 47"adjacent and slightly over (as much as necessary) rear grab bar and next to wall where door is. This will get it out of the stall entry and route of travel.
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes findings that have a high financial impact on the entity in relationship to the degree of access provided)
Department:
Parks & Recreation
Additional Finding Photos
North Catamount Reservoir Area Near Fishing Pier
BFID: 190202
The surfaces of the accessible parking spaces and access aisles are not firm, stable, and slip resistant.
Floor and ground surfaces shall be stable, firm, and slip resistant
Parking spaces and access aisles serving them shall comply with 302. Access aisles shall be at the same level as the parking spaces they serve. Changes in level are not permitted.
Citation:
2010 ADAS Section 302.1
Floor and ground surfaces shall be stable, firm, and slip resistant and shall comply with 302.
2010 ADAS Section 502.4
Parking spaces and access aisles serving them shall comply with 302. Access aisles shall be at the same level as the parking spaces they serve. Changes in level are not permitted.
As Built:
The accessible parking stalls and access aisle is gravel.
Recommendation:
Create a hard surface accessible parking area.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
BFID: 190203
The striping for the accessible parking stall's loading/unloading access aisle is missing.
Access aisles shall be marked so as to discourage parking in them.
Citation:
2010 ADAS Section 502.3.3
Access aisles shall be marked so as to discourage parking in them.
As Built:
The accessible parking stall and access aisle is gravel and therefor not marked.
Recommendation:
Properly mark space and access aisle once made a hard surface.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
BFID: 190204
The parking sign is mounted too low.
Parking space identification signs shall include the International Symbol of Accessibility. Signs identifying van parking spaces shall contain the designation "van accessible." Signs shall be 60 inches minimum above the finish floor or ground surface measured to the bottom of the sign.
Citation:
2010 ADAS Section 502.6
Parking space identification signs shall include the International Symbol of Accessibility complying with 703.7.2.1. Signs identifying van parking spaces shall contain the designation "van accessible." Signs shall be 60 inches (1525 mm) minimum above the finish floor or ground surface measured to the bottom of the sign.
As Built:
The accessible parking stall signs are 38" to the base.
Recommendation:
Raise the sign so that when the van sign is also installed it will be 60" to the base. The base of the regular sign will need to be around 64".
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Additional Finding Photos
BFID: 190205
The van stall is missing a sign identifying it as a van accessible stall.
Parking space identification signs shall include the International Symbol of Accessibility. Signs identifying van parking spaces shall contain the designation "van accessible."
Citation:
2010 ADAS Section 502.6
Parking space identification signs shall include the International Symbol of Accessibility complying with 703.7.2.1. Signs identifying van parking spaces shall contain the designation "van accessible." Signs shall be 60 inches (1525 mm) minimum above the finish floor or ground surface measured to the bottom of the sign.
As Built:
The accessible parking stall lacks van signage.
Recommendation:
Add Van Sign.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
BFID: 190211
There is no accessible route from the parking area to the sidewalk.
At least one accessible route shall connect accessible buildings, accessible facilities, accessible elements, and accessible spaces that are on the same site.
Citation:
2015 IBC Section 1104.2
At least one accessible route shall connect accessible buildings, accessible facilities, accessible elements and accessible spaces that are on the same site.
2010 ADAS Section 206.2.2
At least one accessible route shall connect accessible buildings, accessible facilities, accessible elements, and accessible spaces that are on the same site.
As Built:
We lack an accessible walkway from the parking area to the sidewalk which leads to the fishing pier.
Recommendation:
Create an accessible route to the sidewalk from the future hard surface parking.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
BFID: 190212
The accessible route contains loose gravel and/or surface materials that do not provide for a stable, firm slip resistant surface.
Citation:
2010 ADAS Section 302.1
Floor and ground surfaces shall be stable, firm, and slip resistant and shall comply with 302.
As Built:
The first pad contains a lot of loose gravel.
Recommendation:
Create barrier to resolve this. It is likely much of this would cease to be an issue once accessible route is created.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
BFID: 190213
The accessible route on the site has running slopes greater than 5% and has not been constructed as a ramp (i.e. handrails, edge protection, etc.). This area runs until the bench.
When the slope in the direction of travel of any walk exceeds 1 unit vertical in 20 units horizontal (5-percent slope), it must be constructed as a ramp. Surface cross slopes must not exceed one unit vertical in 48 units horizontal (2-percent slope).
Citation:
2010 ADAS Section 403.3
The running slope of walking surfaces shall not be steeper than 1:20. The cross slope of walking surfaces shall not be steeper than 1:48.
As Built:
After the first pad, 21 out of 24 pads exceed 5%. The range is 5.4-7.8. Most pads are in the mid-6% range to 7%. There are no ramp provisions. Also, in the stretch there are 2 gaps which are approximately 3/4" wide.
Recommendation:
Take out and re-grade this area and create proper ramps.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Additional Finding Photos
BFID: 190214
The accessible path of travel has cross slopes greater than 2%.
Surface cross slopes shall not exceed one unit vertical in 48 units horizontal (2-percent slope). When the slope in the direction of travel of any walk exceeds 1 unit vertical in 20 units horizontal (5-percent slope), it must be constructed as a ramp.
Citation:
2010 ADAS Section 403.3
The running slope of walking surfaces shall not be steeper than 1:20. The cross slope of walking surfaces shall not be steeper than 1:48.
As Built:
After the bench, the next 3 pads have cross slopes of 2.4, 2.3 and 3.3% respectively.
Recommendation:
Replace to at or under 2% cross slope.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
BFID: 190215
The accessible route has running slopes greater than 5% and has not been constructed as a ramp (i.e. handrails,edge protection, etc.). Cross slopes are greater than 2% across the width of the walk.
When the slope in the direction of travel of any walk exceeds 1 unit vertical in 20 units horizontal (5-percent slope), it must be constructed as a ramp. Surface cross slopes must not exceed 1 unit vertical in 48 units horizontal (2-percent slope).
Citation:
2010 ADAS Section 403.3
The running slope of walking surfaces shall not be steeper than 1:20. The cross slope of walking surfaces shall not be steeper than 1:48.
As Built:
The next 5 pads up to the gangplank - 4 have running slopes between 5.3 -11.3% and 4 have cross slopes between 3.4-4.3%, along with an area of 3.4" vertical displacement.
Recommendation:
Replace all of these pads to proper dimensions.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Additional Finding Photos
BFID: 190216
The handrail is too high.
At least 25 percent of the railings, guards, or handrails shall be 34 inches maximum above the ground or deck surface.
Citation:
2010 ADAS Section 1005.2.1
At least 25 percent of the railings, guards, or handrails shall be 34 inches (865 mm) maximum above the ground or deck surface.
As Built:
The railing all measures 43" high.
Recommendation:
Lower multiple areas to 34" high.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
BFID: 190217
The curb or barrier does not extend 2 inches minimum above the surface.
Where compliant railings, guards, or handrails are provided, edge protection shall also be provided.
Curbs or barriers shall extend 2 inches minimum above the surface of the fishing pier or platform or The ground or deck surface shall extend 12 inches minimum beyond the inside face of the railing. Toe clearance shall be provided and shall be 30 inches wide minimum and 9 inches minimum above the ground or deck surface beyond the railing.
Citation:
2010 ADAS Section 1005.3.1
Curbs or barriers shall extend 2 inches (51 mm) minimum above the surface of the fishing pier or platform.
As Built:
We frequently have 1-6" gaps of edge protection surrounding the pier. These should not be. We need full coverage where we have railings.
Recommendation:
Add in additional protection around the pier.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
BFID: 190218
There is no accessible route to the mono-filament receptacle..
At least one accessible route shall connect accessible buildings, accessible facilities, accessible elements, and accessible spaces that are on the same site.
Citation:
2015 IBC Section 1104.2
At least one accessible route shall connect accessible buildings, accessible facilities, accessible elements and accessible spaces that are on the same site.
2010 ADAS Section 206.2.2
At least one accessible route shall connect accessible buildings, accessible facilities, accessible elements, and accessible spaces that are on the same site.
As Built:
There is no accessible route to the mono-filament receptacle. It is a 15' distance over rough terrain and high slopes to reach it.
Recommendation:
Have this relocated next to accessible route and/or create a route to it.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
BFID: 190219
The mono-filament receptacle is positioned too high for either a side or front approach.
Where a clear floor or ground space allows a parallel approach to an element and the side reach is unobstructed, the high side reach shall be 48 inches maximum and the low side reach shall be 15 inches minimum above the finish floor or ground.
Where a forward reach is unobstructed, the high forward reach shall be 48 inches maximum and the low forward reach shall be 15 inches minimum above the finish floor or ground.
Citation:
2010 ADAS Section 308.1
Reach ranges shall comply with 308.
As Built:
There is no accessible route to the mono-filament receptacle. It is 70" to the operable portion.
Recommendation:
Lower to 48" maximum above ground surface.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
North Catamount Reservoir Area Near Restrooms
BFID: 190208
There are no accessible parking stalls in this parking facility.
Each lot where parking is provided for the public as clients, guests or employees, shall provide accessible parking and shall be located on the shortest accessible route of travel from adjacent parking to an accessible entrance.
There are a total of (61) parking stalls in the parking lot that could be reasonably associated with this facility. There should be a minimum of (3) accessible stalls with a minimum of (1) being designed as van accessible. It should be noted 2 marked accessible parking spaces are 600 feet apart from this parking facility to allow closer access to the fishing pier.
Citation:
2015 IBC Section 1106.1
Where parking is provided, accessible parking spaces shall be provided in compliance with Table 1106.1, except as required by Sections 1106.2 through 1106.4. Where more than one parking facility is provided on a site, the number of parking spaces required to be accessible shall be calculated separately for each parking facility.
2010 ADAS Section 208.2
Parking spaces complying with 502 shall be provided in accordance with Table 208.2 except as required by 208.2.1, 208.2.2, and 208.2.3. Where more than one parking facility is provided on a site, the number of accessible spaces provided on the site shall be calculated according to the number of spaces required for each parking facility.
As Built:
The parking facility near the restrooms and picnic tables has no marked accessible spaces.
Recommendation:
Add 1 van accessible parking stall and access aisle at this facility.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Additional Finding Photos
BFID: 190206
The public/common use restrooms serving the facility are not on an accessible route.
Bathing and toilet facilities that serve buildings, facilities or portions of buildings or facilities that are required to be accessible to persons with disabilities, shall be on an accessible route.
Citation:
2015 IBC Section 1109.2
Each toilet room and bathing room shall be accessible. Where a floor level is not required to be connected by an accessible route, the only toilet rooms or bathing rooms provided within the facility shall not be located on the inaccessible floor. Except as provided for in Sections 1109.2.2 and 1109.2.3, at least one of each type of fixture, element, control or dispenser in each accessible toilet room and bathing room shall be accessible.
2010 ADAS Section 213.1
Where toilet facilities and bathing facilities are provided, they shall comply with 213. Where toilet facilities and bathing facilities are provided in facilities permitted by 206.2.3 Exceptions 1 and 2 not to connect stories by an accessible route, toilet facilities and bathing facilities shall be provided on a story connected by an accessible route to an accessible entrance.
As Built:
The parking area lacks an accessible route to the sidewalk.
Recommendation:
Create an accessible route from the parking area to the sidewalk that connects to the restroom facilities.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Additional Finding Photos
BFID: 190209
The accessible path of travel between the building entrance and the accessible parking has cross slopes greater than 2%.
Surface cross slopes shall not exceed 1 unit vertical in 48 units horizontal (2-percent slope).
Citation:
2010 ADAS Section 403.3
The running slope of walking surfaces shall not be steeper than 1:20. The cross slope of walking surfaces shall not be steeper than 1:48.
As Built:
The sidewalk serving the restrooms from the parking area have 4 pads which exceed 2% cross slope. 2-5 to 3.3% is the range. Two of them are also turning areas to enter and exit the restrooms.
Recommendation:
Replace the 4 pads.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Additional Finding Photos
BFID: 190210
The accessible route between the building entrance and the accessible parking has running slopes greater than 5% and has not been constructed as a ramp (i.e. handrails, edge protection, etc.).
When the slope in the direction of travel of any walk exceeds 1 unit vertical in 20 units horizontal (5-percent slope), it must be constructed as a ramp. Surface cross slopes must not exceed one unit vertical in 48 units horizontal (2-percent slope).
Citation:
2010 ADAS Section 403.3
The running slope of walking surfaces shall not be steeper than 1:20. The cross slope of walking surfaces shall not be steeper than 1:48.
As Built:
The sidewalk serving the restrooms from the parking area have 3 pads which exceed 5% running slope. 7-11.8% is the range. Further there is a 5" curb from the parking area using this route.
Recommendation:
Do nothing, this is not feasible to make right. The accessible route will need to be on the other side where the grade is less and there is more room.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Additional Finding Photos
BFID: 190207
The paths to picnic tables contains multiple issues and is not accessible. We have two picnic tables and neither is accessible.
The path of travel exceeds the maximum allowable cross and running slope requirements. It also contains changes in level and/or gaps that exceed the allowable maximum requirements. The path of travel does not meet the minimum width requirements for clearances, turning spaces, and/or passing spaces. The floor or ground surface is not firm, stable, and slip resistant.
Citation:
2010 ADAS Section 403.1
Walking surfaces that are a part of an accessible route shall comply with 403.
As Built:
There is no accessible route to the picnic tables. At least one or 5% should be accessible.
Recommendation:
Explore creating hard surface accessible route with pad underneath to 1 of the picnic tables.
Barrier Priority:
Low (4): Should be completed as soon as possible due to being a technical violation, but may not result in providing greater access to persons with disabilities. (Includes findings that are technically violations but provide a moderate to low increase in accessibility compared to the financial impact on the entity)
Department:
Parks & Recreation
Additional Finding Photos
North Catamount Reservoir Restrooms
BFID: 190188
A compliant room identification sign is missing on the strike side of the door.
Wall signs identifying permanent rooms and spaces of a building shall be a horizontal format and the characters raised 1/32 inch minimum and shall be sans serif uppercase characters a minimum of 5/8 inch and a maximum of 2 inches high. Contracted Grade 2 Braille shall be in a horizontal format and shall be placed a minimum of 3/8 inch and a maximum of 1/2 inch directly below the tactile characters; flush left or centered. Signs with raised characters or Braille shall be located 48 inches minimum above the finish floor or ground surface, measured from the baseline of the lowest tactile character and 60 inches maximum above the finish floor or ground surface, measured from the baseline of the highest tactile character.
Citation:
2010 ADAS Section 216.2
Interior and exterior signs identifying permanent rooms and spaces shall comply with 703.1, 703.2, and 703.5. Where pictograms are provided as designations of permanent interior rooms and spaces, the pictograms shall comply with 703.6 and shall have text descriptors complying with 703.2 and 703.5.
As Built:
There is no accessible sign for the men's restroom. It isn't Braille or tactile and posted too high and in the wrong area.
Recommendation:
Install proper ADA sign on the latch side of the door with top edge set at 60".
Department:
Parks & Recreation
BFID: 190190
The hand sanitizer dispenser's operation mechanism is too high off the floor.
Dispensers must have all operable parts a maximum of 48 inches above the floor.
Citation:
2010 ADAS Section 308.2.1
Where a forward reach is unobstructed, the high forward reach shall be 48 inches (1220 mm) maximum and the low forward reach shall be 15 inches (380 mm) minimum above the finish floor or ground.
As Built:
The hand sanitizer is 59" to the operable part in the men's restroom.
Recommendation:
Lower to at or under 48".
Department:
Parks & Recreation
BFID: 190192
The shelving projects more than 4 inches into the circulation path.
Wall-mounted objects that have leading edges between 27 inches and 80 inches from the floor must not project more than 4 inches into the circulation path. Protruding objects that extend to the floor or within 27 inches of the floor are cane detectable and are therefore not hazardous. Where it is necessary or desirable to have objects protrude from the wall, a manner of cane detection must be provided.
Citation:
2010 ADAS Section 307.2
Objects with leading edges more than 27 inches (685 mm) and not more than 80 inches (2030 mm) above the finish floor or ground shall protrude 4 inches (100 mm) maximum horizontally into the circulation path.
As Built:
The shelving is 42" high and projects 8" from the wall in the path of travel to use the toilet in the men's restroom.
Recommendation:
Move the shelving further down the sidewall so that it is against the back wall. This will get it out of the stall entry and route of travel.
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes findings that have a high financial impact on the entity in relationship to the degree of access provided)
Department:
Parks & Recreation
BFID: 190196
The door has a locking mechanism that requires tight grasping, pinching or twisting of the wrist.
Door locking mechanisms should be push button and release upon activation of the door hardware.
Citation:
2010 ADAS Section 309.4
Operable parts shall be operable with one hand and shall not require tight grasping, pinching, or twisting of the wrist. The force required to activate operable parts shall be 5 pounds (22.2 N) maximum.
As Built:
The door requires pinching, twisting and grasping in the men's restroom.
Recommendation:
Add additional easy to operate lock that doesn't require pinching, twisting and grasping.
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes findings that have a high financial impact on the entity in relationship to the degree of access provided)
Department:
Parks & Recreation
BFID: 190197
The coat hook is installed greater than 48 inches above the finished floor.
Where a forward reach is unobstructed, the high forward reach shall be 48 inches maximum above the finished floor.
Citation:
2010 ADAS Section 308.2.1
Where a forward reach is unobstructed, the high forward reach shall be 48 inches (1220 mm) maximum and the low forward reach shall be 15 inches (380 mm) minimum above the finish floor or ground.
As Built:
The coat hook is mounted at 63" to the useable portion in the men's restroom.
Recommendation:
Add additional coat hook at under 48" to the operable portion.
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes findings that have a high financial impact on the entity in relationship to the degree of access provided)
Department:
Parks & Recreation
BFID: 190200
The compartment door is not self closing.
The water closet compartment shall be equipped with a door that has an automatic-closing device.
Citation:
2010 ADAS Section 604.8.1.2
Toilet compartment doors, including door hardware, shall comply with 404 except that if the approach is to the latch side of the compartment door, clearance between the door side of the compartment and any obstruction shall be 42 inches (1065 mm) minimum. Doors shall be located in the front partition or in the side wall or partition farthest from the water closet. Where located in the front partition, the door opening shall be 4 inches (100 mm) maximum from the side wall or partition farthest from the water closet. Where located in the side wall or partition, the door opening shall be 4 inches (100 mm) maximum from the front partition. The door shall be self-closing. A door pull complying with 404.2.7 shall be placed on both sides of the door near the latch. Toilet compartment doors shall not swing into the minimum required compartment area.
As Built:
The door doesn't self-close or have a handle in the men's restroom.
Recommendation:
Install an interior door handle and springs that allow the door to self-close.
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes findings that have a high financial impact on the entity in relationship to the degree of access provided)
Department:
Parks & Recreation
BFID: 190199
The rim of the urinal is too high.
Wall-hung urinals must be provided with an elongated rim projecting a minimum of 13 1/2 inches from the wall and a maximum of 17 inches above the floor.
Citation:
2010 ADAS Section 605.2
Urinals shall be the stall-type or the wall-hung type with the rim 17 inches (430 mm) maximum above the finish floor or ground. Urinals shall be 13 1/2 inches (345 mm) deep minimum measured from the outer face of the urinal rim to the back of the fixture.
As Built:
The urinal is 20" in the men's restroom.
Recommendation:
Move the urinal down at least 3".
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes findings that have a high financial impact on the entity in relationship to the degree of access provided)
Department:
Parks & Recreation
BFID: 190187
A compliant room identification sign is missing on the strike side of the door.
Wall signs identifying permanent rooms and spaces of a building shall be a horizontal format and the characters raised 1/32 inch minimum and shall be sans serif uppercase characters a minimum of 5/8 inch and a maximum of 2 inches high. Contracted Grade 2 Braille shall be in a horizontal format and shall be placed a minimum of 3/8 inch and a maximum of 1/2 inch directly below the tactile characters; flush left or centered. Signs with raised characters or Braille shall be located 48 inches minimum above the finish floor or ground surface, measured from the baseline of the lowest tactile character and 60 inches maximum above the finish floor or ground surface, measured from the baseline of the highest tactile character.
Citation:
2010 ADAS Section 216.2
Interior and exterior signs identifying permanent rooms and spaces shall comply with 703.1, 703.2, and 703.5. Where pictograms are provided as designations of permanent interior rooms and spaces, the pictograms shall comply with 703.6 and shall have text descriptors complying with 703.2 and 703.5.
As Built:
There is no accessible sign for the women's restroom. It isn't Braille or tactile and posted too high and in the wrong area.
Recommendation:
Install proper ADA sign on the latch side of the door with top edge set at 60".
Department:
Parks & Recreation
BFID: 190189
The hand sanitizer dispenser's operation mechanism is too high off the floor.
Dispensers must have all operable parts a maximum of 48 inches above the floor.
Citation:
2010 ADAS Section 308.2.1
Where a forward reach is unobstructed, the high forward reach shall be 48 inches (1220 mm) maximum and the low forward reach shall be 15 inches (380 mm) minimum above the finish floor or ground.
As Built:
The hand sanitizer is 60" to the operable part in the women's restroom.
Recommendation:
Lower to at or under 48".
Department:
Parks & Recreation
BFID: 190191
The shelving projects more than 4 inches into the circulation path.
Wall-mounted objects that have leading edges between 27 inches and 80 inches from the floor must not project more than 4 inches into the circulation path. Protruding objects that extend to the floor or within 27 inches of the floor are cane detectable and are therefore not hazardous. Where it is necessary or desirable to have objects protrude from the wall, a manner of cane detection must be provided.
Citation:
2010 ADAS Section 307.2
Objects with leading edges more than 27 inches (685 mm) and not more than 80 inches (2030 mm) above the finish floor or ground shall protrude 4 inches (100 mm) maximum horizontally into the circulation path.
As Built:
The shelving is 42" high and projects 8" from the wall in the path of travel to use the toilet in the women's restroom.
Recommendation:
Move the shelving further down the sidewall so that it is against the back wall. This will get it out of the stall entry and route of travel.
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes findings that have a high financial impact on the entity in relationship to the degree of access provided)
Department:
Parks & Recreation
BFID: 190195
The door has a locking mechanism that requires tight grasping, pinching or twisting of the wrist.
Door locking mechanisms should be push button and release upon activation of the door hardware.
Citation:
2010 ADAS Section 309.4
Operable parts shall be operable with one hand and shall not require tight grasping, pinching, or twisting of the wrist. The force required to activate operable parts shall be 5 pounds (22.2 N) maximum.
As Built:
The door requires pinching, twisting and grasping in the women's restroom.
Recommendation:
Add additional easy to operate lock that doesn't require pinching, twisting and grasping.
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes findings that have a high financial impact on the entity in relationship to the degree of access provided)
Department:
Parks & Recreation
BFID: 190198
The coat hook is installed greater than 48 inches above the finished floor.
Where a forward reach is unobstructed, the high forward reach shall be 48 inches maximum above the finished floor.
Citation:
2010 ADAS Section 308.2.1
Where a forward reach is unobstructed, the high forward reach shall be 48 inches (1220 mm) maximum and the low forward reach shall be 15 inches (380 mm) minimum above the finish floor or ground.
As Built:
The coat hook is mounted at 62" to the useable portion in the women's restroom.
Recommendation:
Add additional coat hook at under 48" to the operable portion.
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes findings that have a high financial impact on the entity in relationship to the degree of access provided)
Department:
Parks & Recreation
BFID: 190201
The compartment door is not self closing.
The water closet compartment shall be equipped with a door that has an automatic-closing device.
Citation:
2010 ADAS Section 604.8.1.2
Toilet compartment doors, including door hardware, shall comply with 404 except that if the approach is to the latch side of the compartment door, clearance between the door side of the compartment and any obstruction shall be 42 inches (1065 mm) minimum. Doors shall be located in the front partition or in the side wall or partition farthest from the water closet. Where located in the front partition, the door opening shall be 4 inches (100 mm) maximum from the side wall or partition farthest from the water closet. Where located in the side wall or partition, the door opening shall be 4 inches (100 mm) maximum from the front partition. The door shall be self-closing. A door pull complying with 404.2.7 shall be placed on both sides of the door near the latch. Toilet compartment doors shall not swing into the minimum required compartment area.
As Built:
The door doesn't self-close or have a handle in the women's restroom.
Recommendation:
Install an interior door handle and springs that allow the door to self-close.
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes findings that have a high financial impact on the entity in relationship to the degree of access provided)
Department:
Parks & Recreation
South Catamount Reservoir Area
BFID: 190155
The surfaces of the accessible parking spaces and access aisles are not firm, stable, and slip resistant.
Floor and ground surfaces shall be stable, firm, and slip resistant
Parking spaces and access aisles serving them shall comply with 302. Access aisles shall be at the same level as the parking spaces they serve. Changes in level are not permitted.
Citation:
2010 ADAS Section 302.1
Floor and ground surfaces shall be stable, firm, and slip resistant and shall comply with 302.
2010 ADAS Section 502.4
Parking spaces and access aisles serving them shall comply with 302. Access aisles shall be at the same level as the parking spaces they serve. Changes in level are not permitted.
As Built:
The accessible parking stall and access aisle is gravel.
Recommendation:
Create a hard surface accessible parking area.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
BFID: 190156
The striping for the accessible parking stall's loading/unloading access aisle is missing.
Access aisles shall be marked so as to discourage parking in them.
Citation:
2010 ADAS Section 502.3.3
Access aisles shall be marked so as to discourage parking in them.
As Built:
The accessible parking stall and access aisle is gravel and therefor not marked.
Recommendation:
Properly mark space and access aisle once made a hard surface.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
BFID: 190158
The parking sign is mounted too low.
Parking space identification signs shall include the International Symbol of Accessibility. Signs identifying van parking spaces shall contain the designation "van accessible." Signs shall be 60 inches minimum above the finish floor or ground surface measured to the bottom of the sign.
Citation:
2010 ADAS Section 502.6
Parking space identification signs shall include the International Symbol of Accessibility complying with 703.7.2.1. Signs identifying van parking spaces shall contain the designation "van accessible." Signs shall be 60 inches (1525 mm) minimum above the finish floor or ground surface measured to the bottom of the sign.
As Built:
The accessible parking stall sign was 44 1/2" and now it is 55" to the base.
Recommendation:
Raise the sign so that when the van sign is also installed it will be 60" to the base. The base of the regular sign will need to be around 64".
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Additional Finding Photos
BFID: 190157
The van stall is missing a sign identifying it as a van accessible stall.
Parking space identification signs shall include the International Symbol of Accessibility. Signs identifying van parking spaces shall contain the designation "van accessible."
Citation:
2010 ADAS Section 502.6
Parking space identification signs shall include the International Symbol of Accessibility complying with 703.7.2.1. Signs identifying van parking spaces shall contain the designation "van accessible." Signs shall be 60 inches (1525 mm) minimum above the finish floor or ground surface measured to the bottom of the sign.
As Built:
The accessible parking stall lacks van signage.
Recommendation:
Add Van Sign.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
BFID: 190159
The accessible path of travel has cross slopes greater than 2%.
Surface cross slopes shall not exceed one unit vertical in 48 units horizontal (2-percent slope). When the slope in the direction of travel of any walk exceeds 1 unit vertical in 20 units horizontal (5-percent slope), it must be constructed as a ramp.
Citation:
2010 ADAS Section 403.3
The running slope of walking surfaces shall not be steeper than 1:20. The cross slope of walking surfaces shall not be steeper than 1:48.
As Built:
The sidewalk adjacent to the parking area and in front of the restrooms all has cross slope exceeding 2%. Starting with the bottom and running to building and over to the men's entrance they are 3.1, 2.8, 3.3, 4, and 4.4% cross slope.
Recommendation:
Replace all pads to 2% in all directions as each pad is a pivot area.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
BFID: 190185
The path of contains multiple issues and is not accessible. The upper two tables are near the parking area and restrooms. The lower table is some distance down a very inaccessible route that is up to 18% cross slope and 10% running slope.
The path of travel exceeds the maximum allowable cross and running slope requirements. It also contains changes in level and/or gaps that exceed the allowable maximum requirements. The path of travel does not meet the minimum width requirements for clearances, turning spaces, and/or passing spaces. The floor or ground surface is not firm, stable, and slip resistant.
Citation:
2010 ADAS Section 403.1
Walking surfaces that are a part of an accessible route shall comply with 403.
As Built:
There is no accessible route to the picnic tables. At least one or 5% should be accessible.
Recommendation:
Explore creating hard surface accessible route with pad underneath to 1 of the upper picnic tables.
Barrier Priority:
Low (4): Should be completed as soon as possible due to being a technical violation, but may not result in providing greater access to persons with disabilities. (Includes findings that are technically violations but provide a moderate to low increase in accessibility compared to the financial impact on the entity)
Department:
Parks & Recreation
Additional Finding Photos
BFID: 190186
There is no accessible route to the fishing areas.
At least one accessible route shall connect accessible buildings, accessible facilities, accessible elements, and accessible spaces that are on the same site.
Citation:
2015 IBC Section 1104.2
At least one accessible route shall connect accessible buildings, accessible facilities, accessible elements and accessible spaces that are on the same site.
2010 ADAS Section 206.2.2
At least one accessible route shall connect accessible buildings, accessible facilities, accessible elements, and accessible spaces that are on the same site.
As Built:
There is no accessible route to the fishing areas.
Recommendation:
Do nothing except post that accessible fishing area is at North Catamount. The posting should also be on the website and other materials. This area is not feasible to fix.
Barrier Priority:
Important (2): Should be completed as soon as possible. (Includes findings that would remove barriers to the greatest number of people to your goods and services)
Department:
Parks & Recreation
Additional Finding Photos
South Catamount Reservoir Restrooms
BFID: 190177
A compliant room identification sign is missing on the strike side of the door.
Wall signs identifying permanent rooms and spaces of a building shall be a horizontal format and the characters raised 1/32 inch minimum and shall be sans serif uppercase characters a minimum of 5/8 inch and a maximum of 2 inches high. Contracted Grade 2 Braille shall be in a horizontal format and shall be placed a minimum of 3/8 inch and a maximum of 1/2 inch directly below the tactile characters; flush left or centered. Signs with raised characters or Braille shall be located 48 inches minimum above the finish floor or ground surface, measured from the baseline of the lowest tactile character and 60 inches maximum above the finish floor or ground surface, measured from the baseline of the highest tactile character.
Citation:
2010 ADAS Section 216.2
Interior and exterior signs identifying permanent rooms and spaces shall comply with 703.1, 703.2, and 703.5. Where pictograms are provided as designations of permanent interior rooms and spaces, the pictograms shall comply with 703.6 and shall have text descriptors complying with 703.2 and 703.5.
As Built:
There is no accessible sign for the women's restroom. It isn't Braille or tactile and posted too high and in the wrong area.
Recommendation:
Install proper ADA sign on the latch side of the door with top edge set at 60".
Department:
Parks & Recreation
BFID: 190193
The door has a locking mechanism that requires tight grasping, pinching or twisting of the wrist.
Door locking mechanisms should be push button and release upon activation of the door hardware.
Citation:
2010 ADAS Section 309.4
Operable parts shall be operable with one hand and shall not require tight grasping, pinching, or twisting of the wrist. The force required to activate operable parts shall be 5 pounds (22.2 N) maximum.
As Built:
The door requires pinching, twisting and grasping in the women's restroom.
Recommendation:
Add additional easy to operate lock that doesn't require pinching, twisting and grasping.
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes findings that have a high financial impact on the entity in relationship to the degree of access provided)
Department:
Parks & Recreation
BFID: 190179
The hand sanitizer dispenser's operation mechanism is too high off the floor.
Dispensers must have all operable parts a maximum of 48 inches above the floor.
Citation:
2010 ADAS Section 308.2.1
Where a forward reach is unobstructed, the high forward reach shall be 48 inches (1220 mm) maximum and the low forward reach shall be 15 inches (380 mm) minimum above the finish floor or ground.
As Built:
The hand sanitizer is 55" to the operable part in the women's restroom.
Recommendation:
Lower to at or under 48".
Department:
Parks & Recreation
BFID: 190181
The toilet paper is not installed within the compliant range in front of the toilet.
Toilet paper dispensers shall be 7 inches minimum and 9 inches maximum in front of the water closet measured to the centerline of the dispenser. The outlet of the dispenser shall be 15 inches minimum and 48 inches maximum above the finish floor and shall not be located behind grab bars. Dispensers shall not be of a type that controls delivery or that does not allow continuous paper flow. There shall be a clearance of 1 1/2 inches minimum below the grab bar.
Citation:
2010 ADAS Section 604.7
Toilet paper dispensers shall comply with 309.4 and shall be 7 inches (180 mm) minimum and 9 inches (230 mm) maximum in front of the water closet measured to the centerline of the dispenser. The outlet of the dispenser shall be 15 inches (380 mm) minimum and 48 inches (1220 mm) maximum above the finish floor and shall not be located behind grab bars. Dispensers shall not be of a type that controls delivery or that does not allow continuous paper flow.
As Built:
The toilet paper dispenser is 19" to the center from the front of the toilet in the women's restroom.
Recommendation:
Move over to 8" to the center of the dispenser to the front of the toilet.
Department:
Parks & Recreation
BFID: 190183
The shelving projects more than 4 inches into the circulation path.
Wall-mounted objects that have leading edges between 27 inches and 80 inches from the floor must not project more than 4 inches into the circulation path. Protruding objects that extend to the floor or within 27 inches of the floor are cane detectable and are therefore not hazardous. Where it is necessary or desirable to have objects protrude from the wall, a manner of cane detection must be provided.
Citation:
2010 ADAS Section 307.2
Objects with leading edges more than 27 inches (685 mm) and not more than 80 inches (2030 mm) above the finish floor or ground shall protrude 4 inches (100 mm) maximum horizontally into the circulation path.
As Built:
The shelving is 42" high and projects 8" from the wall in the path of travel to use the toilet in the women's restroom.
Recommendation:
Move the shelving to the sidewall adjacent to the back grab bar next to the sanitizer.
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes findings that have a high financial impact on the entity in relationship to the degree of access provided)
Department:
Parks & Recreation
Additional Finding Photos
BFID: 190178
A compliant room identification sign is missing on the strike side of the door.
Wall signs identifying permanent rooms and spaces of a building shall be a horizontal format and the characters raised 1/32 inch minimum and shall be sans serif uppercase characters a minimum of 5/8 inch and a maximum of 2 inches high. Contracted Grade 2 Braille shall be in a horizontal format and shall be placed a minimum of 3/8 inch and a maximum of 1/2 inch directly below the tactile characters; flush left or centered. Signs with raised characters or Braille shall be located 48 inches minimum above the finish floor or ground surface, measured from the baseline of the lowest tactile character and 60 inches maximum above the finish floor or ground surface, measured from the baseline of the highest tactile character.
Citation:
2010 ADAS Section 216.2
Interior and exterior signs identifying permanent rooms and spaces shall comply with 703.1, 703.2, and 703.5. Where pictograms are provided as designations of permanent interior rooms and spaces, the pictograms shall comply with 703.6 and shall have text descriptors complying with 703.2 and 703.5.
As Built:
There is no accessible sign for the men's restroom. It isn't Braille or tactile and posted too high and in the wrong area.
Recommendation:
Install proper ADA sign on the latch side of the door with top edge set at 60".
Department:
Parks & Recreation
BFID: 190194
The door has a locking mechanism that requires tight grasping, pinching or twisting of the wrist.
Door locking mechanisms should be push button and release upon activation of the door hardware.
Citation:
2010 ADAS Section 309.4
Operable parts shall be operable with one hand and shall not require tight grasping, pinching, or twisting of the wrist. The force required to activate operable parts shall be 5 pounds (22.2 N) maximum.
As Built:
The door requires pinching, twisting and grasping in the men's restroom.
Recommendation:
Add additional easy to operate lock that doesn't require pinching, twisting and grasping.
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes findings that have a high financial impact on the entity in relationship to the degree of access provided)
Department:
Parks & Recreation
BFID: 190180
The hand sanitizer dispenser's operation mechanism is too high off the floor.
Dispensers must have all operable parts a maximum of 48 inches above the floor.
Citation:
2010 ADAS Section 308.2.1
Where a forward reach is unobstructed, the high forward reach shall be 48 inches (1220 mm) maximum and the low forward reach shall be 15 inches (380 mm) minimum above the finish floor or ground.
As Built:
The hand sanitizer is 53" to the operable part in the men's restroom.
Recommendation:
Lower to at or under 48".
Department:
Parks & Recreation
BFID: 190182
The toilet paper is not installed within the compliant range in front of the toilet.
Toilet paper dispensers shall be 7 inches minimum and 9 inches maximum in front of the water closet measured to the centerline of the dispenser. The outlet of the dispenser shall be 15 inches minimum and 48 inches maximum above the finish floor and shall not be located behind grab bars. Dispensers shall not be of a type that controls delivery or that does not allow continuous paper flow. There shall be a clearance of 1 1/2 inches minimum below the grab bar.
Citation:
2010 ADAS Section 604.7
Toilet paper dispensers shall comply with 309.4 and shall be 7 inches (180 mm) minimum and 9 inches (230 mm) maximum in front of the water closet measured to the centerline of the dispenser. The outlet of the dispenser shall be 15 inches (380 mm) minimum and 48 inches (1220 mm) maximum above the finish floor and shall not be located behind grab bars. Dispensers shall not be of a type that controls delivery or that does not allow continuous paper flow.
As Built:
The toilet paper dispenser is 18 1/2" to the center from the front of the men's restroom.
Recommendation:
Move over to 8" to the center of the dispenser to the front of the toilet.
Department:
Parks & Recreation
BFID: 190184
The shelving projects more than 4 inches into the circulation path.
Wall-mounted objects that have leading edges between 27 inches and 80 inches from the floor must not project more than 4 inches into the circulation path. Protruding objects that extend to the floor or within 27 inches of the floor are cane detectable and are therefore not hazardous. Where it is necessary or desirable to have objects protrude from the wall, a manner of cane detection must be provided.
Citation:
2010 ADAS Section 307.2
Objects with leading edges more than 27 inches (685 mm) and not more than 80 inches (2030 mm) above the finish floor or ground shall protrude 4 inches (100 mm) maximum horizontally into the circulation path.
As Built:
The shelving is 41 1/2" high and projects 8" from the wall in the path of travel to use the toilet in the men's restroom.
Recommendation:
Move the shelving to the sidewall between 40-48 to the top edge adjacent to the back grab bar next to the sanitizer.
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes findings that have a high financial impact on the entity in relationship to the degree of access provided)
Department:
Parks & Recreation
Additional Finding Photos