Site Accessibility Evaluation

Americans with Disabilities Act
Title II (Public Services: State and Local Government)
Evaluation PU18-000091 Cover Photo
Wilson Ranch Community Park
2335 Allegheny Dr
Northwest Colorado Springs, CO 80919
Accessibility Evaluation
Inspection Date: 09/26/2024
Inspectors: Robert Hernandez
Prepared By
City of Colorado Springs Logo
City of Colorado Springs
(719) 385 - 5175
https://coloradosprings.gov/
Report Date: 02/11/2025

FOR RECORD:

FROM: Robert L. Hernandez, Title II ADA/Section 504 – Manager

DATE: 02/11/2025

SUBJECT: Wilson Ranch Community Park Self-Evaluation

1. On 09/26/2024, Title II ADA / Section 504 Coordinator(s) from the Office of Accessibility performed a Title II - Americans with Disabilities Act (ADA) Self-Evaluation. This evaluation was performed in accordance with 1991/2010 ADA Standards for Accessible Design.

2. Priorities for removing barriers are assigned in accordance with the ADA Checklist for Existing Facilities, promulgated by the ADA National Network. The checklist follows the four priorities listed in the Department of Justice ADA Title III regulations. These priorities are equally applicable to state and local government facilities:

Priority 1 - Accessible approach and entrance
Priority 2 - Access to goods and services
Priority 3 - Access to public toilet rooms
Priority 4 - Access to other items such as water fountains and public telephones

3. Corrective actions to findings were / will be submitted to the City maintenance work request system and will be managed in accordance with the City Transition Plan. Note: Recommended corrections may be modified where appropriate. Corrections are developed in consideration of the “Program Access” provisions of Title II, where applicable.

4. A copy of this report will be maintained by the Office of Accessibility. Updates to the findings included in this report will be available at the following link: https://access6.bluedag.com/access/barriers/GfhHF91nlvMItTaD4rVzj85XBKNZxywJ. Alternatively, this link is available from the Office of Accessibility’s webpage on the City of Colorado Springs website.


City of Colorado Springs Title II ADA/Section 504 – Manager
30 S. Nevada Ave, Suite 301
Colorado Springs, CO 80903
ADACompliance@coloradosprings.gov


Atch 1. City of Colorado Springs, ADA Self-Evaluation Report

Sincerely,


Robert Hernandez

Findings

Exterior - Parking

BFID: 186331

The accessible parking stall is not wide enough.

Each parking space must be at least 8' feet wide and shall be marked to define the width.

The measurements of parking spaces and access aisles shall be made from the centerline of the markings. Where the parking space is not adjacent to another parking space or access aisle, the measurement shall be permitted to include the full width of the line defining the parking space.

Alternatively, the stall can be 11 feet wide minimum and the access aisle may be 5 feet wide.
Citation:
2010 ADAS Section 502.2
Car parking spaces shall be 96 inches (2440 mm) wide minimum and van parking spaces shall be 132 inches (3350 mm) wide minimum, shall be marked to define the width, and shall have an adjacent access aisle complying with 502.3.

Recommendation:
After filling the gap between the gutter and paving, restripe the parking space to 8'-0" wide.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Finding 186331 Main Photo
Image that depicts the citation requirements of the code or standard
Additional Finding Photos
Image of narrow accessible parking

BFID: 186333

The parking sign is mounted too low.

Parking space identification signs shall include the International Symbol of Accessibility. Signs identifying van parking spaces shall contain the designation "van accessible." Signs shall be 60 inches minimum above the finish floor or ground surface measured to the bottom of the sign.
Citation:
2010 ADAS Section 502.6
Parking space identification signs shall include the International Symbol of Accessibility complying with 703.7.2.1. Signs identifying van parking spaces shall contain the designation "van accessible." Signs shall be 60 inches (1525 mm) minimum above the finish floor or ground surface measured to the bottom of the sign.

Recommendation:
Increase the height of the sign to 5'-0" to 7'-0" to the bottom of the sign.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Finding 186333 Main Photo
Image that depicts the citation requirements of the code or standard
Additional Finding Photos
Image of accessible parking signage mounted too low

BFID: 186334

The access aisle is not a minimum 8 feet to the centerline of the stripe.

The accessible parking stall access aisle must be a minimum of 8 feet wide measured from centerline to centerline.

Where parking spaces or access aisles are not adjacent to another parking space or access aisle, measurements shall be permitted to include the full width of the line defining the parking space or access aisle.

Alternatively, the stall can be 11 feet wide and the access aisle may be 5 feet wide.
Citation:
2010 ADAS Section 502.2 Exception
Van parking spaces shall be permitted to be 96 inches (2440 mm) wide minimum where the access aisle is 96 inches (2440 mm) wide minimum.

Recommendation:
After the paving is fixed at the gutter line, restripe the access aisle to 8'-0" wide.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Finding 186334 Main Photo
Image that depicts the citation requirements of the code or standard
Additional Finding Photos
Image of narrow access aisle
Finding 186334 Additional Photo

BFID: 190648

The access aisle contains abrupt edges and surface irregularities over 1/4 inches.

Parking spaces and access aisles serving them shall be stable, firm, and slip-resistant. Access aisles shall be at the same level as the parking spaces they serve. Changes in level are not permitted and shall not be sloped steeper than 2% in any direction.
Citation:
2010 ADAS Section 502.4
Parking spaces and access aisles serving them shall comply with 302. Access aisles shall be at the same level as the parking spaces they serve. Changes in level are not permitted.

Recommendation:
Cut out and patch this back flush.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Image of finding
Image that depicts the citation requirements of the code or standard

BFID: 186336 - Sign was added to compliance.

The required parking signage is missing.

Parking space identification signs shall include the International Symbol of Accessibility (ISA). Signs identifying van parking spaces shall contain the designation "van accessible." All signs shall be 60 inches minimum above the finish floor or ground surface measured to the bottom of the sign.
Citation:
2010 ADAS Section 502.6
Parking space identification signs shall include the International Symbol of Accessibility complying with 703.7.2.1. Signs identifying van parking spaces shall contain the designation "van accessible." Signs shall be 60 inches (1525 mm) minimum above the finish floor or ground surface measured to the bottom of the sign.

Recommendation:
Install accessible parking signage.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Corrected Condition:
N/A
Finding 186336 Main Photo
Finding 186336 Corrected Photo

BFID: 186337 - Sign was added to compliance.

The required parking signage is missing.

Parking space identification signs shall include the International Symbol of Accessibility (ISA). Signs identifying van parking spaces shall contain the designation "van accessible." All signs shall be 60 inches minimum above the finish floor or ground surface measured to the bottom of the sign.
Citation:
2010 ADAS Section 502.6
Parking space identification signs shall include the International Symbol of Accessibility complying with 703.7.2.1. Signs identifying van parking spaces shall contain the designation "van accessible." Signs shall be 60 inches (1525 mm) minimum above the finish floor or ground surface measured to the bottom of the sign.

Recommendation:
Install accessible parking signage.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Corrected Condition:
N/A
Finding 186337 Main Photo
Finding 186337 Corrected Photo

BFID: 190662

The parking sign is mounted too low.

Parking space identification signs shall include the International Symbol of Accessibility. Signs identifying van parking spaces shall contain the designation "van accessible." Signs shall be 60 inches minimum above the finish floor or ground surface measured to the bottom of the sign.
Citation:
2010 ADAS Section 502.6
Parking space identification signs shall include the International Symbol of Accessibility complying with 703.7.2.1. Signs identifying van parking spaces shall contain the designation "van accessible." Signs shall be 60 inches (1525 mm) minimum above the finish floor or ground surface measured to the bottom of the sign.

Recommendation:
Increase the height of the sign to 5'-0" to 7'-0" to the bottom of the sign.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Corrected Condition:
Sign was raised to compliance.
Image of finding
Finding 190662 Corrected Photo

BFID: 190646

The access aisle is not a minimum 5 feet wide.

An accessible parking stall's access aisle must be a minimum of 5 feet wide measured from centerline to centerline.

Where the access aisle is not adjacent to another parking space or access aisle, measurements shall be permitted to include the full width of the line defining the access aisle.
Citation:
2010 ADAS Section 502.3.1
Access aisles serving car and van parking spaces shall be 60 inches (1525 mm) wide minimum.

Recommendation:
Restripe to make at least 5' wide.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Finding 190646 Main Photo
Image that depicts the citation requirements of the code or standard
Additional Finding Photos
Finding 190646 Additional Photo

BFID: 190647

The access aisle contains abrupt edges and surface irregularities over a 1/4 inches.

Parking spaces and access aisles serving them shall be stable, firm, and slip resistant. Access aisles shall be at the same level as the parking spaces they serve. Changes in level are not permitted and shall not be sloped steeper than 2% in any direction.
Citation:
2010 ADAS Section 502.4
Parking spaces and access aisles serving them shall comply with 302. Access aisles shall be at the same level as the parking spaces they serve. Changes in level are not permitted.

Recommendation:
Cut out and patch back flush.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Image of finding
Image that depicts the citation requirements of the code or standard

BFID: 190649

Restripe the accessible parking.
Citation:
2010 ADAS Section 208
Parking Spaces

Recommendation:
Restripe the parking lot.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Corrected Condition:
Lot was re-striped.
Image of finding
Finding 190649 Corrected Photo

Exterior - Accessible Routes

BFID: 186339

There are multiple issues with this curb ramp including High running and cross slopes in the level landing and wings and high areas of vertical displacement.
Citation:
2010 ADAS Section 406
Curb Ramps

Recommendation:
Remove and replace the curb ramp.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Finding 186339 Main Photo
Additional Finding Photos
Image of vertical displacement between concrete gutter and asphalt paving
Finding 186339 Additional Photo
Finding 186339 Additional Photo

BFID: 190651

There are multiple issues with this curb ramp including High running and cross slopes in the level landing and high cross slopes in wings and a high area of vertical displacement.
Citation:
2010 ADAS Section 406
Curb Ramps

Recommendation:
Remove and replace the curb ramp.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Image of finding
Additional Finding Photos
Finding 190651 Additional Photo

BFID: 186328

The surface of the pedestrian access route has vertical discontinuities greater than 1/2 inch or between 1/4 inch and 1/2 inch that are not beveled.

Vertical surface discontinuities shall be 0.5 inch maximum. Vertical surface discontinuities between 0.25 inch and 0.5 inch shall be beveled with a slope not steeper than 50 percent. The bevel shall be applied across the entire vertical surface discontinuity.
Citation:
2011 PROWAG Section R302.7.2
Vertical surface discontinuities shall be 13 mm (0.5 in) maximum. Vertical surface discontinuities between 6.4 mm (0.25 in) and 13 mm (0.5 in) shall be beveled with a slope not steeper than 50 percent. The bevel shall be applied across the entire vertical surface discontinuity.Advisory R302.7.2 Vertical Surface Discontinuities. The allowance for vertical surface discontinuities is for occasional expansion joints and objects such as utility covers, vault frames, and gratings that cannot be located in another portion of the sidewalk outside the pedestrian access route. However, objects such as utility covers, vault frames, and gratings should not be located on curb ramp runs, blended transitions, turning spaces, or gutter areas within the pedestrian access route. This may not always be possible in alterations, but should be avoided wherever possible. Vertical surface discontinuities between unit pavers should be minimized.

Recommendation:
Replace the pad.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Image of vertical displacement in the sidewalk
Image that depicts the citation requirements of the code or standard

BFID: 186329

The surface of the pedestrian access route has vertical discontinuities greater than 1/2 inch or between 1/4 inch and 1/2 inch that are not beveled.

Vertical surface discontinuities shall be 0.5 inch maximum. Vertical surface discontinuities between 0.25 inch and 0.5 inch shall be beveled with a slope not steeper than 50 percent. The bevel shall be applied across the entire vertical surface discontinuity.

There are four brick areas, and each is about 25 sq. ft.
Citation:
2011 PROWAG Section R302.7.2
Vertical surface discontinuities shall be 13 mm (0.5 in) maximum. Vertical surface discontinuities between 6.4 mm (0.25 in) and 13 mm (0.5 in) shall be beveled with a slope not steeper than 50 percent. The bevel shall be applied across the entire vertical surface discontinuity.Advisory R302.7.2 Vertical Surface Discontinuities. The allowance for vertical surface discontinuities is for occasional expansion joints and objects such as utility covers, vault frames, and gratings that cannot be located in another portion of the sidewalk outside the pedestrian access route. However, objects such as utility covers, vault frames, and gratings should not be located on curb ramp runs, blended transitions, turning spaces, or gutter areas within the pedestrian access route. This may not always be possible in alterations, but should be avoided wherever possible. Vertical surface discontinuities between unit pavers should be minimized.

Recommendation:
Remove the brick pavers and either replace with concrete or adjust the height of the base layer.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Finding 186329 Main Photo
Image that depicts the citation requirements of the code or standard
Additional Finding Photos
Image of vertical discontinuities between concrete and pavers
Additional image of vertical discontinuities
Finding 186329 Additional Photo

BFID: 186327

There are multiple issues with the ramp, including high running slopes on each leg of the ramp, high slopes in turning areas and unlevel landings, an area of vertical displacement and the handrails do not come out as much as needed (12") in multiple areas.
Citation:
2010 ADAS Section 405
Ramps

Recommendation:
Replace this ramp.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Image of fractured concrete
Additional Finding Photos
Finding 186327 Additional Photo
Finding 186327 Additional Photo
Finding 186327 Additional Photo

BFID: 186341

The cross slope of the pedestrian access route is excessive.

The cross slope of pedestrian access routes shall be 2 percent maximum.
Citation:
2011 PROWAG Section R302.6
Except as provided in R302.6.1 and R302.6.2 (Pedestrian Street Crossings Without Yield or Stop Control and Midblock Pedestrian Street Crossings), the cross slope of pedestrian access routes shall be 2 percent maximum.

Advisory R302.6 Cross Slope. The cross slope requirements in R302.6 apply to sidewalks and other pedestrian circulation paths, pedestrian street crossings and at-grade rail crossings, and pedestrian overpasses and underpasses and similar structures (see R302.2). The cross slope of the pedestrian access route is measured perpendicular to the direction of pedestrian travel. Cross slope requirements are contained in R304.5.3 for curb ramps and blended transitions, and in R407.3 for ramps.

Recommendation:
Replace all pads with cross-slope issues. Short term the vertical displacement should be ground.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Image of vertical displacement in the sidewalk

BFID: 190660

The walkway contains abrupt vertical edges and/or variations over 1/4 inch.

1/4 inch is the maximum vertical rise. Changes in level between 1/4 inch and 1/2 inch must be beveled at 1:2 or less.

Changes in level greater than 1/2 inch must be by way of a ramp.
Citation:
2010 ADAS Section 303.3
Changes in level between 1/4 inch (6.4 mm) high minimum and 1/2 inch (13 mm) high maximum shall be beveled with a slope not steeper than 1:2.

2010 ADAS Section 303.2
Changes in level of 1/4 inch (6.4 mm) high maximum shall be permitted to be vertical.

Recommendation:
Grind everything to under 1/2" bevel.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Corrected Condition:
Concrete was bevel cut to compliance.
Image of finding
Finding 190660 Corrected Photo
Additional Finding Photos
Finding 190660 Corrected Photo

BFID: 190659

The concrete expansion joint is spaced greater than 1/2 inch.

Openings in floor or ground surfaces shall not allow passage of a sphere more than 1/2 inch diameter. Elongated openings shall be placed so that the long dimension is perpendicular to the dominant direction of travel.
Citation:
2010 ADAS Section 302.3
Openings in floor or ground surfaces shall not allow passage of a sphere more than 1/2 inch (13 mm) diameter except as allowed in 407.4.3, 409.4.3, 410.4, 810.5.3 and 810.10. Elongated openings shall be placed so that the long dimension is perpendicular to the dominant direction of travel.

Recommendation:
Fill the gaps.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Image of finding
Additional Finding Photos
Finding 190659 Additional Photo
Finding 190659 Additional Photo
Finding 190659 Additional Photo
Finding 190659 Additional Photo

BFID: 186344

The accessible route has running slopes greater than 5% and has not been constructed as a ramp (i.e. handrails,edge protection, etc.). Cross slopes are greater than 2% across the width of the walk.

When the slope in the direction of travel of any walk exceeds 1 unit vertical in 20 units horizontal (5-percent slope), it must be constructed as a ramp. Surface cross slopes must not exceed 1 unit vertical in 48 units horizontal (2-percent slope).
Citation:
2010 ADAS Section 403.3
The running slope of walking surfaces shall not be steeper than 1:20. The cross slope of walking surfaces shall not be steeper than 1:48.

Recommendation:
Replace all cross-slope pads to 2% or under. Reduce the slope on the two running slope pads as much as feasible.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Finding 186344 Main Photo
Image that depicts the citation requirements of the code or standard
Additional Finding Photos
Image of sidewalk with excessive running slope
Finding 186344 Additional Photo
Finding 186344 Additional Photo

BFID: 190661

The walkway contains abrupt vertical edges and/or variations over 1/4 inch.

1/4 inch is the maximum vertical rise. Changes in level between 1/4 inch and 1/2 inch must be beveled at 1:2 or less.

Changes in level greater than 1/2 inch must be by way of a ramp.
Citation:
2010 ADAS Section 303.3
Changes in level between 1/4 inch (6.4 mm) high minimum and 1/2 inch (13 mm) high maximum shall be beveled with a slope not steeper than 1:2.

2010 ADAS Section 303.2
Changes in level of 1/4 inch (6.4 mm) high maximum shall be permitted to be vertical.

Recommendation:
Grind to under 1/2" bevel.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Corrected Condition:
Concrete was bevel cut to compliance.
Image of finding
Finding 190661 Corrected Photo

BFID: 190663

The T-shaped or circular turning space contains excessive slopes.

Surface slopes greater than 1:48 (2.08%) are not permitted.
Citation:
2010 ADAS Section 304.2
Floor or ground surfaces of a turning space shall comply with 302. Changes in level are not permitted.

2010 ADAS Section 304.2 Exception
Slopes not steeper than 1:48 shall be permitted.

Recommendation:
Flatten this area if feasible.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Image of finding
Image that depicts the citation requirements of the code or standard

BFID: 186349

The accessible route on the site has running slopes greater than 5 percent and has not been constructed as a ramp (i.e. handrails, edge protection, etc.).

When the slope in the direction of travel of any walk exceeds 1 unit vertical in 20 units horizontal (5-percent slope), it must be constructed as a ramp. Surface cross slopes must not exceed one unit vertical in 48 units horizontal (2-percent slope).
Citation:
2010 ADAS Section 403.3
The running slope of walking surfaces shall not be steeper than 1:20. The cross slope of walking surfaces shall not be steeper than 1:48.

Recommendation:
Do nothing as this is not feasible to fix. The route very roughly follows the street grade and there is another park entry point from the public right of way.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Finding 186349 Main Photo
Image that depicts the citation requirements of the code or standard
Additional Finding Photos
Image of sidewalk with excessive slopes

BFID: 190664

The T-shaped or circular turning space contains excessive slopes.

Surface slopes greater than 1:48 (2.08%) are not permitted.
Citation:
2010 ADAS Section 304.2
Floor or ground surfaces of a turning space shall comply with 302. Changes in level are not permitted.

2010 ADAS Section 304.2 Exception
Slopes not steeper than 1:48 shall be permitted.

Recommendation:
Flatten this area if feasible.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Image of finding
Image that depicts the citation requirements of the code or standard

BFID: 186350

The curb ramps do not have detectable warnings along with other issues.
Citation:
2011 PROWAG Section R208.1
Detectable warning surfaces complying with R305 shall be provided at the following locations on pedestrian access routes and at transit stops:
1. Curb ramps and blended transitions at pedestrian street crossings;
2. Pedestrian refuge islands;
3. Pedestrian at-grade rail crossings not located within a street or highway;
4. Boarding platforms at transit stops for buses and rail vehicles where the edges of the boarding platform are not protected by screens or guards; and
5. Boarding and alighting areas at sidewalk or street level transit stops for rail vehicles where the side of the boarding and alighting areas facing the rail vehicles is not protected by screens or guards.Advisory R208.1 Where Required. On pedestrian access routes, detectable warning surfaces indicate the boundary between pedestrian and vehicular routes where there is a flush rather than a curbed connection. Detectable warning surfaces should not be provided at crossings of residential driveways since the pedestrian right-of-way continues across residential driveway aprons. However, where commercial driveways are provided with yield or stop control, detectable warning surfaces should be provided at the junction between the pedestrian route and the vehicular route. Where pedestrian at-grade rail crossings are located within a street or highway, detectable warning surfaces at the curb ramps or blended transitions make a second set of detectable warning surfaces at the rail crossing unnecessary.
Detectable warning surfaces are not intended to provide wayfinding for pedestrians who are blind or have low vision. Wayfinding can be made easier by:
•Sidewalks that provide a clear path free of street furniture;
•Visual contrast between walking and non-walking areas (e.g., planted borders);
•Route edges that are clear and detectable by cane;
•Direct pedestrian street crossings and curb ramps that are in-line with direction of travel;
•Small corner radiuses that permit pedestrian street crossings to be as short and direct as possible;
•Orthogonal intersections that facilitate navigation using parallel and perpendicular vehicle sound cues;
•and barriers where pedestrian travel or crossing is not permitted.

Recommendation:
Due to other issues with this and the other ramp, remove and replace both of them.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Corrected Condition:
Both ramps were replaced.
Image of curb ramp without detectable warnings
Finding 186350 Corrected Photo
Additional Finding Photos
Finding 186350 Corrected Photo
Finding 186350 Corrected Photo
Finding 186350 Corrected Photo

BFID: 186352

The landing at the top of the curb ramp has running slope and/or cross slope exceeding 2%.
Citation:
2010 ADAS Section 406.4
Landings shall be provided at the tops of curb ramps. The landing clear length shall be 36 inches (915 mm) minimum. The landing clear width shall be at least as wide as the curb ramp, excluding flared sides, leading to the landing.

Recommendation:
Replace the curb ramps.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Corrected Condition:
The curb ramps were replaced.
Finding 186352 Main Photo
Finding 186352 Corrected Photo

BFID: 186353

The curb ramps do not have detectable warnings.
Citation:
2011 PROWAG Section R208.1
Detectable warning surfaces complying with R305 shall be provided at the following locations on pedestrian access routes and at transit stops:
1. Curb ramps and blended transitions at pedestrian street crossings;
2. Pedestrian refuge islands;
3. Pedestrian at-grade rail crossings not located within a street or highway;
4. Boarding platforms at transit stops for buses and rail vehicles where the edges of the boarding platform are not protected by screens or guards; and
5. Boarding and alighting areas at sidewalk or street level transit stops for rail vehicles where the side of the boarding and alighting areas facing the rail vehicles is not protected by screens or guards.Advisory R208.1 Where Required. On pedestrian access routes, detectable warning surfaces indicate the boundary between pedestrian and vehicular routes where there is a flush rather than a curbed connection. Detectable warning surfaces should not be provided at crossings of residential driveways since the pedestrian right-of-way continues across residential driveway aprons. However, where commercial driveways are provided with yield or stop control, detectable warning surfaces should be provided at the junction between the pedestrian route and the vehicular route. Where pedestrian at-grade rail crossings are located within a street or highway, detectable warning surfaces at the curb ramps or blended transitions make a second set of detectable warning surfaces at the rail crossing unnecessary.
Detectable warning surfaces are not intended to provide wayfinding for pedestrians who are blind or have low vision. Wayfinding can be made easier by:
•Sidewalks that provide a clear path free of street furniture;
•Visual contrast between walking and non-walking areas (e.g., planted borders);
•Route edges that are clear and detectable by cane;
•Direct pedestrian street crossings and curb ramps that are in-line with direction of travel;
•Small corner radiuses that permit pedestrian street crossings to be as short and direct as possible;
•Orthogonal intersections that facilitate navigation using parallel and perpendicular vehicle sound cues;
•and barriers where pedestrian travel or crossing is not permitted.

Recommendation:
Due to other issues with this curb ramp, remove and replace them.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Corrected Condition:
This ramp was replaced and the other connection point was done away with.
Finding 186353 Main Photo
Finding 186353 Corrected Photo

BFID: 186354

The landing at the top of the curb ramp has running slope and/or cross slope exceeding 2%.
Citation:
2010 ADAS Section 406.4
Landings shall be provided at the tops of curb ramps. The landing clear length shall be 36 inches (915 mm) minimum. The landing clear width shall be at least as wide as the curb ramp, excluding flared sides, leading to the landing.

Recommendation:
Due to other issues with this ramp, remove and replace it.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Corrected Condition:
N/A
Image of noncompliant curb ramp
Finding 186354 Corrected Photo

BFID: 186355

The curb ramp on the accessible route contains cross slopes greater than 2%.

Surface cross slopes shall not exceed one unit vertical in 48 units horizontal (2-percent slope).
Citation:
2010 ADAS Section 405.3
Cross slope of ramp runs shall not be steeper than 1:48.

2010 ADAS Section 406.1
Curb ramps on accessible routes shall comply with 406, 405.2 through 405.5, and 405.10.

Recommendation:
Due to other issues with this curb ramp, remove and replace it.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Corrected Condition:
This curb ramp issue was fixed.
Image of curb ramp with excessive cross slope and fracturing
Finding 186355 Corrected Photo
Additional Finding Photos
Finding 186355 Corrected Photo

BFID: 186356

The surface of the pedestrian access route has vertical discontinuities greater than 1/2 inch or between 1/4 inch and 1/2 inch that are not beveled.

Vertical surface discontinuities shall be 0.5 inch maximum. Vertical surface discontinuities between 0.25 inch and 0.5 inch shall be beveled with a slope not steeper than 50 percent. The bevel shall be applied across the entire vertical surface discontinuity.

This is on the south side of the intersection at Allegheny and White Buffalo Rd.
Citation:
2011 PROWAG Section R302.7.2
Vertical surface discontinuities shall be 13 mm (0.5 in) maximum. Vertical surface discontinuities between 6.4 mm (0.25 in) and 13 mm (0.5 in) shall be beveled with a slope not steeper than 50 percent. The bevel shall be applied across the entire vertical surface discontinuity.Advisory R302.7.2 Vertical Surface Discontinuities. The allowance for vertical surface discontinuities is for occasional expansion joints and objects such as utility covers, vault frames, and gratings that cannot be located in another portion of the sidewalk outside the pedestrian access route. However, objects such as utility covers, vault frames, and gratings should not be located on curb ramp runs, blended transitions, turning spaces, or gutter areas within the pedestrian access route. This may not always be possible in alterations, but should be avoided wherever possible. Vertical surface discontinuities between unit pavers should be minimized.

Recommendation:
Grind edges if possible and fill gaps. This was partially done. The far edge is now ground. The nearer edge can probably only be filled.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Image of vertical displacement at the storm channel
Image that depicts the citation requirements of the code or standard
Additional Finding Photos
Finding 186356 Additional Photo

BFID: 190652

The T-shaped or circular turning space contains excessive slopes.

Surface slopes greater than 1:48 (2.08%) are not permitted.
Citation:
2010 ADAS Section 304.2
Floor or ground surfaces of a turning space shall comply with 302. Changes in level are not permitted.

2010 ADAS Section 304.2 Exception
Slopes not steeper than 1:48 shall be permitted.

Recommendation:
Replace this pad when the curb ramps are replaced.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Image of finding
Image that depicts the citation requirements of the code or standard

BFID: 190653

The dog waste receptacle is a little too high and is out of the maximum reach range for a side approach.

Where a clear floor or ground space allows a parallel approach to an element and the high side reach is over an obstruction, the height of the obstruction shall be 34 inches maximum and the depth of the obstruction shall be 24 inches maximum. Where the reach depth exceeds 10 inches, the high side reach shall be 46 inches maximum.
Citation:
2010 ADAS Section 308.3.2
Where a clear floor or ground space allows a parallel approach to an element and the high side reach is over an obstruction, the height of the obstruction shall be 34 inches (865 mm) maximum and the depth of the obstruction shall be 24 inches (610 mm) maximum. The high side reach shall be 48 inches (1220 mm) maximum for a reach depth of 10 inches (255 mm) maximum. Where the reach depth exceeds 10 inches (255 mm), the high side reach shall be 46 inches (1170 mm) maximum for a reach depth of 24 inches (610 mm) maximum

Recommendation:
Either move closer to the walkway or pave concrete level
Barrier Priority:
Low (4): Should be completed as soon as possible due to being a technical violation, but may not result in providing greater access to persons with disabilities. (Includes findings that are technically violations but provide a moderate to low increase in accessibility compared to the financial impact on the entity)
Department:
Parks & Recreation
Image of finding
Image that depicts the citation requirements of the code or standard

BFID: 190665

The accessible route on the site has running slopes greater than 5 percent and has not been constructed as a ramp (i.e. handrails, edge protection, etc.).

When the slope in the direction of travel of any walk exceeds 1 unit vertical in 20 units horizontal (5-percent slope), it must be constructed as a ramp. Surface cross slopes must not exceed one unit vertical in 48 units horizontal (2-percent slope).
Citation:
2010 ADAS Section 403.3
The running slope of walking surfaces shall not be steeper than 1:20. The cross slope of walking surfaces shall not be steeper than 1:48.

Recommendation:
Do nothing at this time. It is not feasible to correct these slopes and they generally follow road grades.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Image of finding
Image that depicts the citation requirements of the code or standard

BFID: 190666

The accessible route has running slopes greater than 5% and has not been constructed as a ramp (i.e. handrails,edge protection, etc.). Cross slopes are greater than 2% across the width of the walk.

When the slope in the direction of travel of any walk exceeds 1 unit vertical in 20 units horizontal (5-percent slope), it must be constructed as a ramp. Surface cross slopes must not exceed 1 unit vertical in 48 units horizontal (2-percent slope).
Citation:
2010 ADAS Section 403.3
The running slope of walking surfaces shall not be steeper than 1:20. The cross slope of walking surfaces shall not be steeper than 1:48.

Recommendation:
Do nothing for now as not part of the accessible route. At some point, the high cross slopes could be mitigated.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Image of finding
Image that depicts the citation requirements of the code or standard

BFID: 190667

The accessible path of travel has cross slopes greater than 2%.

Surface cross slopes shall not exceed one unit vertical in 48 units horizontal (2-percent slope). When the slope in the direction of travel of any walk exceeds 1 unit vertical in 20 units horizontal (5-percent slope), it must be constructed as a ramp.
Citation:
2010 ADAS Section 403.3
The running slope of walking surfaces shall not be steeper than 1:20. The cross slope of walking surfaces shall not be steeper than 1:48.

Recommendation:
Remove and replace 12 pads.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Image of finding
Image that depicts the citation requirements of the code or standard
Additional Finding Photos
Finding 190667 Additional Photo
Finding 190667 Additional Photo

BFID: 190668

The walkway contains abrupt vertical edges and/or variations over 1/4 inch.

1/4 inch is the maximum vertical rise. Changes in level between 1/4 inch and 1/2 inch must be beveled at 1:2 or less.

Changes in level greater than 1/2 inch must be by way of a ramp.
Citation:
2010 ADAS Section 303.3
Changes in level between 1/4 inch (6.4 mm) high minimum and 1/2 inch (13 mm) high maximum shall be beveled with a slope not steeper than 1:2.

2010 ADAS Section 303.2
Changes in level of 1/4 inch (6.4 mm) high maximum shall be permitted to be vertical.

Recommendation:
Grind the lip and fill the gap. This will also be resolved when the pads are replaced.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Corrected Condition:
Concrete was bevel cut to compliance.
Image of finding
Finding 190668 Corrected Photo
Additional Finding Photos
Finding 190668 Corrected Photo
Finding 190668 Corrected Photo

BFID: 190669

The concrete expansion joint is spaced greater than 1/2 inch.

Openings in floor or ground surfaces shall not allow passage of a sphere more than 1/2 inch diameter. Elongated openings shall be placed so that the long dimension is perpendicular to the dominant direction of travel.
Citation:
2010 ADAS Section 302.3
Openings in floor or ground surfaces shall not allow passage of a sphere more than 1/2 inch (13 mm) diameter except as allowed in 407.4.3, 409.4.3, 410.4, 810.5.3 and 810.10. Elongated openings shall be placed so that the long dimension is perpendicular to the dominant direction of travel.

Recommendation:
Fill in all gaps.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Image of finding
Additional Finding Photos
Finding 190669 Additional Photo

BFID: 190673

The concrete expansion joint is spaced greater than 1/2 inch.

Openings in floor or ground surfaces shall not allow passage of a sphere more than 1/2 inch diameter. Elongated openings shall be placed so that the long dimension is perpendicular to the dominant direction of travel.
Citation:
2010 ADAS Section 302.3
Openings in floor or ground surfaces shall not allow passage of a sphere more than 1/2 inch (13 mm) diameter except as allowed in 407.4.3, 409.4.3, 410.4, 810.5.3 and 810.10. Elongated openings shall be placed so that the long dimension is perpendicular to the dominant direction of travel.

Recommendation:
Fill in the gap.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Image of finding

BFID: 190670

The walkway contains abrupt vertical edges and/or variations over 1/4 inch.

1/4 inch is the maximum vertical rise. Changes in level between 1/4 inch and 1/2 inch must be beveled at 1:2 or less.

Changes in level greater than 1/2 inch must be by way of a ramp.
Citation:
2010 ADAS Section 303.3
Changes in level between 1/4 inch (6.4 mm) high minimum and 1/2 inch (13 mm) high maximum shall be beveled with a slope not steeper than 1:2.

2010 ADAS Section 303.2
Changes in level of 1/4 inch (6.4 mm) high maximum shall be permitted to be vertical.

Recommendation:
Grind all areas to under 1/2" bevel including the bolts in the concrete.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Corrected Condition:
The metal bolts and mounts were removed.
Image of finding
Finding 190670 Corrected Photo

BFID: 190671

The accessible path of travel has cross slopes greater than 2%.

Surface cross slopes shall not exceed one unit vertical in 48 units horizontal (2-percent slope). When the slope in the direction of travel of any walk exceeds 1 unit vertical in 20 units horizontal (5-percent slope), it must be constructed as a ramp.
Citation:
2010 ADAS Section 403.3
The running slope of walking surfaces shall not be steeper than 1:20. The cross slope of walking surfaces shall not be steeper than 1:48.

Recommendation:
Remove and replace 30 pads.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Image of finding
Image that depicts the citation requirements of the code or standard
Additional Finding Photos
Finding 190671 Additional Photo

BFID: 190672

The walkway contains abrupt vertical edges and/or variations over 1/4 inch.

1/4 inch is the maximum vertical rise. Changes in level between 1/4 inch and 1/2 inch must be beveled at 1:2 or less.

Changes in level greater than 1/2 inch must be by way of a ramp.
Citation:
2010 ADAS Section 303.3
Changes in level between 1/4 inch (6.4 mm) high minimum and 1/2 inch (13 mm) high maximum shall be beveled with a slope not steeper than 1:2.

2010 ADAS Section 303.2
Changes in level of 1/4 inch (6.4 mm) high maximum shall be permitted to be vertical.

Recommendation:
Grind the joint line and ultimately replace these two pads.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Finding 190672 Main Photo
Image that depicts the citation requirements of the code or standard
Additional Finding Photos
Finding 190672 Additional Photo

BFID: 190674

The T-shaped or circular turning space contains excessive slopes.

Surface slopes greater than 1:48 (2.08%) are not permitted.
Citation:
2010 ADAS Section 304.2
Floor or ground surfaces of a turning space shall comply with 302. Changes in level are not permitted.

2010 ADAS Section 304.2 Exception
Slopes not steeper than 1:48 shall be permitted.

Recommendation:
Remove and replace concrete at this turn to compliance.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Finding 190674 Main Photo
Image that depicts the citation requirements of the code or standard
Additional Finding Photos
Finding 190674 Additional Photo
Finding 190674 Additional Photo

BFID: 195110

The accessible route on the site has running slopes greater than 5 percent and has not been constructed as a ramp (i.e. handrails, edge protection, etc.).

When the slope in the direction of travel of any walk exceeds 1 unit vertical in 20 units horizontal (5-percent slope), it must be constructed as a ramp. Surface cross slopes must not exceed one unit vertical in 48 units horizontal (2-percent slope).
Citation:
2010 ADAS Section 403.3
The running slope of walking surfaces shall not be steeper than 1:20. The cross slope of walking surfaces shall not be steeper than 1:48.

Recommendation:
Remove and replace concrete to compliance.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Finding 195110 Main Photo
Image that depicts the citation requirements of the code or standard
Additional Finding Photos
Finding 195110 Additional Photo

Exterior - Restroom

BFID: 186340

The portable public restroom is not compliant.

If sanitary facilities are provided, they must be made accessible to persons with disabilities. If public restrooms are desired, It is recommended that the portable unit be replaced with a permanent built in compliant restroom. The utilization of an accessible portable unit may be a temporary solution and is not recommended as a permanent solution.
Citation:
2010 ADAS Section 213.1
Where toilet facilities and bathing facilities are provided, they shall comply with 213. Where toilet facilities and bathing facilities are provided in facilities permitted by 206.2.3 Exceptions 1 and 2 not to connect stories by an accessible route, toilet facilities and bathing facilities shall be provided on a story connected by an accessible route to an accessible entrance.

Recommendation:
Grind the edge and add an accessible porta-potty.
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes findings that have a high financial impact on the entity in relationship to the degree of access provided)
Department:
Parks & Recreation
Finding 186340 Main Photo
Additional Finding Photos
Finding 186340 Additional Photo

Exterior - Play Areas

BFID: 186343

The entry to the playground surface has drop offs at the side of the concrete ramp.
Citation:
2010 ADAS Section 303
Changes in Level

Recommendation:
Keep the engineered fill raked to prevent drop offs.
Barrier Priority:
Important (2): Should be completed as soon as possible. (Includes findings that would remove barriers to the greatest number of people to your goods and services)
Department:
Parks & Recreation
Corrected Condition:
The play area is now level to the surface due to the artificial grass application.
Image of ramp without side flares
Finding 186343 Corrected Photo
Additional Finding Photos
Finding 186343 Corrected Photo

BFID: 190654

The walkway contains abrupt vertical edges and/or variations over a 1/2 inch.

1/4 inch is the maximum vertical rise. Changes in level between 1/4 inch and 1/2 inch must be beveled at 1:2 or less.

Changes in level greater than 1/2 inch must be by way of a ramp.
Citation:
2010 ADAS Section 303.3
Changes in level between 1/4 inch (6.4 mm) high minimum and 1/2 inch (13 mm) high maximum shall be beveled with a slope not steeper than 1:2.

2010 ADAS Section 303.2
Changes in level of 1/4 inch (6.4 mm) high maximum shall be permitted to be vertical.

Recommendation:
Tack this backdown level.
Barrier Priority:
Important (2): Should be completed as soon as possible. (Includes findings that would remove barriers to the greatest number of people to your goods and services)
Department:
Parks & Recreation
Image of finding
Image that depicts the citation requirements of the code or standard
Additional Finding Photos
Finding 190654 Additional Photo

Shelter and Picnic Tables

BFID: 186346

The concrete expansion joint is spaced greater than a 3/4 inch.

Openings in floor or ground surfaces shall not allow passage of a sphere more than 1/2 inch diameter. Elongated openings shall be placed so that the long dimension is perpendicular to the dominant direction of travel.
Citation:
2011 PROWAG Section R302.7.3
Horizontal openings in gratings and joints shall not permit passage of a sphere more than 13 mm (0.5 in) in diameter. Elongated openings in gratings shall be placed so that the long dimension is perpendicular to the dominant direction of travel.

Recommendation:
Fill the gaps.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Image of gap in the sidewalk
Image that depicts the citation requirements of the code or standard
Additional Finding Photos
Additional image of gaps in sidewalk
Finding 186346 Additional Photo
Finding 186346 Additional Photo

BFID: 186345

The accessible route has running slopes greater than 5% and has not been constructed as a ramp (i.e. handrails,edge protection, etc.). Cross slopes are greater than 2% across the width of the walk.

When the slope in the direction of travel of any walk exceeds 1 unit vertical in 20 units horizontal (5-percent slope), it must be constructed as a ramp. Surface cross slopes must not exceed 1 unit vertical in 48 units horizontal (2-percent slope).
Citation:
2010 ADAS Section 403.3
The running slope of walking surfaces shall not be steeper than 1:20. The cross slope of walking surfaces shall not be steeper than 1:48.

Recommendation:
Make cross slope to under 2% if feasible. The running slope would be difficult to reduce and not everything must be accessible everywhere.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Image of sidewalk with excessive running slope
Image that depicts the citation requirements of the code or standard

Court Sport Areas

BFID: 186342

The concrete expansion joint is spaced greater than a 1/2 inch.

Openings in floor or ground surfaces shall not allow passage of a sphere more than 1/2 inch diameter. Elongated openings shall be placed so that the long dimension is perpendicular to the dominant direction of travel.
Citation:
2011 PROWAG Section R302.7.3
Horizontal openings in gratings and joints shall not permit passage of a sphere more than 13 mm (0.5 in) in diameter. Elongated openings in gratings shall be placed so that the long dimension is perpendicular to the dominant direction of travel.

Recommendation:
Clean out the gap and fill.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Finding 186342 Main Photo
Image that depicts the citation requirements of the code or standard
Additional Finding Photos
Finding 186342 Additional Photo

BFID: 186348

The surface of the pedestrian access route has vertical discontinuities greater than 1/2 inch or between 1/4 inch and 1/2 inch that are not beveled.

Vertical surface discontinuities shall be 0.5 inch maximum. Vertical surface discontinuities between 0.25 inch and 0.5 inch shall be beveled with a slope not steeper than 50 percent. The bevel shall be applied across the entire vertical surface discontinuity.
Citation:
2011 PROWAG Section R302.7.2
Vertical surface discontinuities shall be 13 mm (0.5 in) maximum. Vertical surface discontinuities between 6.4 mm (0.25 in) and 13 mm (0.5 in) shall be beveled with a slope not steeper than 50 percent. The bevel shall be applied across the entire vertical surface discontinuity.Advisory R302.7.2 Vertical Surface Discontinuities. The allowance for vertical surface discontinuities is for occasional expansion joints and objects such as utility covers, vault frames, and gratings that cannot be located in another portion of the sidewalk outside the pedestrian access route. However, objects such as utility covers, vault frames, and gratings should not be located on curb ramp runs, blended transitions, turning spaces, or gutter areas within the pedestrian access route. This may not always be possible in alterations, but should be avoided wherever possible. Vertical surface discontinuities between unit pavers should be minimized.

Recommendation:
Remove and replace the concrete panel.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Image of fractured sidewalk
Image that depicts the citation requirements of the code or standard

BFID: 190658

The accessible route on the site has running slopes greater than 5 percent and has not been constructed as a ramp (i.e. handrails, edge protection, etc.).

When the slope in the direction of travel of any walk exceeds 1 unit vertical in 20 units horizontal (5-percent slope), it must be constructed as a ramp. Surface cross slopes must not exceed one unit vertical in 48 units horizontal (2-percent slope).
Citation:
2010 ADAS Section 403.3
The running slope of walking surfaces shall not be steeper than 1:20. The cross slope of walking surfaces shall not be steeper than 1:48.

Recommendation:
Take out and replace to under 5% running slope or make to ramp provisions, under 8.3% running slope max, level landings and handrails, if not possible to make at 5%.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Image of finding
Image that depicts the citation requirements of the code or standard
Additional Finding Photos
Finding 190658 Additional Photo
Finding 190658 Additional Photo

BFID: 186347

The route of travel at this location does not provide the required minimum width.

The minimum clear width for sidewalks and walks is 36 inches. The disconnect for the chain is mounted at 80" above ground on the west entrance.
Citation:
2010 ADAS Section 403.5.1
Except as provided in 403.5.2 and 403.5.3, the clear width of walking surfaces shall be 36 inches (915 mm) minimum.

2010 ADAS Section 403.5.1 Exception
The clear width shall be permitted to be reduced to 32 inches (815 mm) minimum for a length of 24 inches (610 mm) maximum provided that reduced width segments are separated by segments that are 48 inches (1220 mm) long minimum and 36 inches (915 mm) wide minimum.

Recommendation:
Move the chain to 36 or 48" minimum.
Barrier Priority:
Important (2): Should be completed as soon as possible. (Includes findings that would remove barriers to the greatest number of people to your goods and services)
Department:
Parks & Recreation
Corrected Condition:
The west entrance has had the chain removed.
Image of narrow entrance to tennis courts
Finding 186347 Corrected Photo

BFID: 190655

There is not enough knee clearance under the drinking fountain.

The drinking fountain must have a clear knee space between the bottom of the drinking fountain and the floor not less than 27 inches in height, 30 inches in width, and 8 inches in depth.
Citation:
2010 ADAS Section 602.2
Units shall have a clear floor or ground space complying with 305 positioned for a forward approach and centered on the unit. Knee and toe clearance complying with 306 shall be provided.

Recommendation:
Raise the unit 1/2" as 27" is an absolute measurement.
Barrier Priority:
Low (4): Should be completed as soon as possible due to being a technical violation, but may not result in providing greater access to persons with disabilities. (Includes findings that are technically violations but provide a moderate to low increase in accessibility compared to the financial impact on the entity)
Department:
Parks & Recreation
Image of finding
Image that depicts the citation requirements of the code or standard

BFID: 190656

The accessible route on the site has running slopes greater than 5 percent and has not been constructed as a ramp (i.e. handrails, edge protection, etc.).

When the slope in the direction of travel of any walk exceeds 1 unit vertical in 20 units horizontal (5-percent slope), it must be constructed as a ramp. Surface cross slopes must not exceed one unit vertical in 48 units horizontal (2-percent slope).
Citation:
2010 ADAS Section 403.3
The running slope of walking surfaces shall not be steeper than 1:20. The cross slope of walking surfaces shall not be steeper than 1:48.

Recommendation:
Take out and replace and install to under 5% if feasible or add ramp provisions, meaning no more than 8.3%, level landings, and handrails.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Image of finding
Image that depicts the citation requirements of the code or standard

BFID: 190657

The T-shaped or circular turning space contains excessive slopes.

Surface slopes greater than 1:48 (2.08%) are not permitted.
Citation:
2010 ADAS Section 304.2
Floor or ground surfaces of a turning space shall comply with 302. Changes in level are not permitted.

2010 ADAS Section 304.2 Exception
Slopes not steeper than 1:48 shall be permitted.

Recommendation:
Level this area out to 2%.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Image of finding
Image that depicts the citation requirements of the code or standard
Additional Finding Photos
Finding 190657 Additional Photo

Exterior - Pool

BFID: 186380

At the time of the evaluation the lift could not be operated or tested.

The lift should be accessible and available at all times the area is open for use.
Citation:
2010 ADAS Section 242.2
At least two accessible means of entry shall be provided for swimming pools. Accessible means of entry shall be swimming pool lifts complying with 1009.2; sloped entries complying with 1009.3; transfer walls complying with 1009.4; transfer systems complying with 1009.5; and pool stairs complying with 1009.6. At least one accessible means of entry provided shall comply with 1009.2 or 1009.3.

Recommendation:
Repair or replace the pool lift.
Barrier Priority:
Important (2): Should be completed as soon as possible. (Includes findings that would remove barriers to the greatest number of people to your goods and services)
Department:
Parks & Recreation
Corrected Condition:
The portable lift was replaced.
Finding 186380 Main Photo
Finding 186380 Corrected Photo

BFID: 186382

The stairs project more than 4 inches into the circulation path.

Protruding objects that extend to the floor or within 27 inches of the floor are cane detectable and are therefore not hazardous. Where it is necessary or desirable to have objects protrude from the wall, a manner of cane detection must be provided.
Citation:
2010 ADAS Section 307.2
Objects with leading edges more than 27 inches (685 mm) and not more than 80 inches (2030 mm) above the finish floor or ground shall protrude 4 inches (100 mm) maximum horizontally into the circulation path.

Recommendation:
Install a barrier under the stairs, even with the edge of the stairs, to provide cane detection.
Barrier Priority:
Important (2): Should be completed as soon as possible. (Includes findings that would remove barriers to the greatest number of people to your goods and services)
Department:
Parks & Recreation
Image of stairs without cane detection underneath
Image that depicts the citation requirements of the code or standard

Interior - General

BFID: 186373

The transaction counter is too high.

A portion of the counter surface that is 36 inches long minimum and 36 inches high maximum above the finish floor shall be provided. Knee and toe space must be provided for a forward approach. A 30 inch by 48 inch clear floor space on an accessible route must be provided for either a forward or parallel approach.
Citation:
2010 ADAS Section 904.4.1
A portion of the counter surface that is 36 inches (915 mm) long minimum and 36 inches (915 mm) high maximum above the finish floor shall be provided. A clear floor or ground space complying with 305 shall be positioned for a parallel approach adjacent to the 36 inch (915 mm) minimum length of counter.

Recommendation:
Lower a 36" wide section of the counter to 36" maximum height. Until then, staff must be ready, willing and able to accommodate at a side table, with a clipboard, or some other method.
Barrier Priority:
Important (2): Should be completed as soon as possible. (Includes findings that would remove barriers to the greatest number of people to your goods and services)
Department:
Parks & Recreation
Finding 186373 Main Photo
Image that depicts the citation requirements of the code or standard
Additional Finding Photos
Image of noncompliant transaction counter

BFID: 190686

The coat hook is mounted too high. Unobstructed coat hooks should be no higher than 48".
Citation:
2010 ADAS Section 308.2.2
Where a high forward reach is over an obstruction, the clear floor space shall extend beneath the element for a distance not less than the required reach depth over the obstruction. The high forward reach shall be 48 inches (1220 mm) maximum where the reach depth is 20 inches (510 mm) maximum. Where the reach depth exceeds 20 inches (510 mm), the high forward reach shall be 44 inches (1120 mm) maximum and the reach depth shall be 25 inches (635 mm) maximum.

Recommendation:
Add another lower coat hook.
Barrier Priority:
Low (4): Should be completed as soon as possible due to being a technical violation, but may not result in providing greater access to persons with disabilities. (Includes findings that are technically violations but provide a moderate to low increase in accessibility compared to the financial impact on the entity)
Department:
Parks & Recreation
Image of finding

BFID: 190685

The sanitizer is too high and is out of the maximum reach range for a side approach. This should be no higher than 46" due to bench obstruction.

Where a clear floor or ground space allows a parallel approach to an element and the high side reach is over an obstruction, the height of the obstruction shall be 34 inches maximum and the depth of the obstruction shall be 24 inches maximum. Where the reach depth exceeds 10 inches, the high side reach shall be 46 inches maximum.
Citation:
2010 ADAS Section 308.3.2
Where a clear floor or ground space allows a parallel approach to an element and the high side reach is over an obstruction, the height of the obstruction shall be 34 inches (865 mm) maximum and the depth of the obstruction shall be 24 inches (610 mm) maximum. The high side reach shall be 48 inches (1220 mm) maximum for a reach depth of 10 inches (255 mm) maximum. Where the reach depth exceeds 10 inches (255 mm), the high side reach shall be 46 inches (1170 mm) maximum for a reach depth of 24 inches (610 mm) maximum

Recommendation:
Move the sanitizer down and also move the benches out of the way.
Barrier Priority:
Low (4): Should be completed as soon as possible due to being a technical violation, but may not result in providing greater access to persons with disabilities. (Includes findings that are technically violations but provide a moderate to low increase in accessibility compared to the financial impact on the entity)
Department:
Parks & Recreation
Image of finding
Image that depicts the citation requirements of the code or standard

BFID: 186374

The wall sign is mounted too high.

Tactile Characters on signs shall be located 48 inches minimum above the finish floor or ground surface, measured from the baseline of the lowest tactile character and 60 inches maximum above the finish floor or ground surface, measured from the baseline of the highest tactile character. Mounting location shall be determined so that a person may approach within 3 inches of signage without encountering protruding objects and shall be located so that a clear floor space of 18 inches minimum by 18 inches minimum, centered on the tactile Characters, is provided beyond the arc of any door swing between the closed position and 45 degree open position.
Citation:
2010 ADAS Section 703.4.1
Tactile characters on signs shall be located 48 inches (1220 mm) minimum above the finish floor or ground surface, measured from the baseline of the lowest tactile character and 60 inches (1525 mm) maximum above the finish floor or ground surface, measured from the baseline of the highest tactile character.

Recommendation:
Install a compliant sign.
Barrier Priority:
Important (2): Should be completed as soon as possible. (Includes findings that would remove barriers to the greatest number of people to your goods and services)
Department:
Parks & Recreation
Image of noncompliant signage
Image that depicts the citation requirements of the code or standard

BFID: 190682

The wall sign is mounted too high.

Tactile Characters on signs shall be located 48 inches minimum above the finish floor or ground surface, measured from the baseline of the lowest tactile character and 60 inches maximum above the finish floor or ground surface, measured from the baseline of the highest tactile character. Mounting location shall be determined so that a person may approach within 3 inches of signage without encountering protruding objects and shall be located so that a clear floor space of 18 inches minimum by 18 inches minimum, centered on the tactile Characters, is provided beyond the arc of any door swing between the closed position and 45 degree open position.
Citation:
2010 ADAS Section 703.4.1
Tactile characters on signs shall be located 48 inches (1220 mm) minimum above the finish floor or ground surface, measured from the baseline of the lowest tactile character and 60 inches (1525 mm) maximum above the finish floor or ground surface, measured from the baseline of the highest tactile character.

Recommendation:
Install a compliant sign.
Barrier Priority:
Important (2): Should be completed as soon as possible. (Includes findings that would remove barriers to the greatest number of people to your goods and services)
Department:
Parks & Recreation
Image of finding
Image that depicts the citation requirements of the code or standard

BFID: 190683

The door has a door stop which prevents it from having a smooth surface at the bottom.

Swinging door surfaces within 10 inches of the finish floor or ground measured vertically must have a smooth surface on the push side extending the full width of the door. Parts creating horizontal or vertical joints in these surfaces shall be within 1/16 inch of the same plane as the other. Cavities created by added kick plates shall be capped. This is required to allow those that use wheelchairs to use their footrests to push the door open without getting trapped or injured by the gate material. All gates, including ticket gates, shall meet all applicable specifications for doors.
Citation:
2010 ADAS Section 404.2.10
Swinging door and gate surfaces within 10 inches (255 mm) of the finish floor or ground measured vertically shall have a smooth surface on the push side extending the full width of the door or gate. Parts creating horizontal or vertical joints in these surfaces shall be within 1/16 inch (1.6 mm) of the same plane as the other. Cavities created by added kick plates shall be capped.

Recommendation:
Remove the doorstop.
Barrier Priority:
High (1): Should be completed immediately. (Includes findings that have little or no cost, were in violation of the codes at the time of construction, or pose an imminent safety threat)
Department:
Parks & Recreation
Image of finding
Image that depicts the citation requirements of the code or standard

BFID: 190684

The money insert and credit payment system is positioned too high for either a side or front approach.

Where a clear floor or ground space allows a parallel approach to an element and the side reach is unobstructed, the high side reach shall be 48 inches maximum and the low side reach shall be 15 inches minimum above the finish floor or ground.

Where a forward reach is unobstructed, the high forward reach shall be 48 inches maximum and the low forward reach shall be 15 inches minimum above the finish floor or ground.
Citation:
2010 ADAS Section 308.1
Reach ranges shall comply with 308.

Recommendation:
Contact the vendor for the new door plate to lower these to no higher than 48".
Barrier Priority:
Low (4): Should be completed as soon as possible due to being a technical violation, but may not result in providing greater access to persons with disabilities. (Includes findings that are technically violations but provide a moderate to low increase in accessibility compared to the financial impact on the entity)
Department:
Parks & Recreation
Image of finding
Image that depicts the citation requirements of the code or standard
Additional Finding Photos
Finding 190684 Additional Photo

Interior - Women's Restroom

BFID: 186358

The wall sign is mounted too high.

Tactile Characters on signs shall be located 48 inches minimum above the finish floor or ground surface, measured from the baseline of the lowest tactile character and 60 inches maximum above the finish floor or ground surface, measured from the baseline of the highest tactile character. Mounting location shall be determined so that a person may approach within 3 inches of signage without encountering protruding objects and shall be located so that a clear floor space of 18 inches minimum by 18 inches minimum, centered on the tactile Characters, is provided beyond the arc of any door swing between the closed position and 45 degree open position.
Citation:
2010 ADAS Section 703.4.1
Tactile characters on signs shall be located 48 inches (1220 mm) minimum above the finish floor or ground surface, measured from the baseline of the lowest tactile character and 60 inches (1525 mm) maximum above the finish floor or ground surface, measured from the baseline of the highest tactile character.

Recommendation:
Install a compliant sign on the latch side of the door.
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes findings that have a high financial impact on the entity in relationship to the degree of access provided)
Department:
Parks & Recreation
Image of noncompliant restroom signage
Image that depicts the citation requirements of the code or standard

BFID: 186359

The door exceeds the maximum pressure to open the door.

Interior doors shall have a maximum opening force of 5 pounds.

These forces do not apply to the force required to retract latch bolts or disengage other devices that hold the door or gate in a closed position. Door closers and gate closers shall be adjusted so that from an open position of 90 degrees, the time required to move the door to a position of 12 degrees from the latch is 5 seconds minimum.

Door and gate spring hinges shall be adjusted so that from the open position of 70 degrees, the door or gate shall move to the closed position in 1.5 seconds minimum.
Citation:
2010 ADAS Section 404.2.9
Fire doors shall have a minimum opening force allowable by the appropriate administrative authority. The force for pushing or pulling open a door or gate other than fire doors shall be as follows: 1. Interior hinged doors and gates: 5 pounds (22.2 N) maximum. 2. Sliding or folding doors: 5 pounds (22.2 N) maximum. These forces do not apply to the force required to retract latch bolts or disengage other devices that hold the door or gate in a closed position.

Recommendation:
Adjust the door closer.
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes findings that have a high financial impact on the entity in relationship to the degree of access provided)
Department:
Parks & Recreation
Image of restroom door

BFID: 186361

The water closet compartment door is missing a loop handle on the inside.

Water closet compartments must be equipped with a door that has a loop or U-shaped handle on both sides of the door immediately below the latch. The latch must be flip-over style, sliding or other hardware not requiring the user to grasp or twist.
Citation:
2010 ADAS Section 604.8.1.2
Toilet compartment doors, including door hardware, shall comply with 404 except that if the approach is to the latch side of the compartment door, clearance between the door side of the compartment and any obstruction shall be 42 inches (1065 mm) minimum. Doors shall be located in the front partition or in the side wall or partition farthest from the water closet. Where located in the front partition, the door opening shall be 4 inches (100 mm) maximum from the side wall or partition farthest from the water closet. Where located in the side wall or partition, the door opening shall be 4 inches (100 mm) maximum from the front partition. The door shall be self-closing. A door pull complying with 404.2.7 shall be placed on both sides of the door near the latch. Toilet compartment doors shall not swing into the minimum required compartment area.

Recommendation:
Install a handle.
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes findings that have a high financial impact on the entity in relationship to the degree of access provided)
Department:
Parks & Recreation
Image of stall door without loop handle
Image that depicts the citation requirements of the code or standard

BFID: 186362

The compartment door is not self closing.

The water closet compartment shall be equipped with a door that has an automatic-closing device.
Citation:
2010 ADAS Section 604.8.1.2
Toilet compartment doors, including door hardware, shall comply with 404 except that if the approach is to the latch side of the compartment door, clearance between the door side of the compartment and any obstruction shall be 42 inches (1065 mm) minimum. Doors shall be located in the front partition or in the side wall or partition farthest from the water closet. Where located in the front partition, the door opening shall be 4 inches (100 mm) maximum from the side wall or partition farthest from the water closet. Where located in the side wall or partition, the door opening shall be 4 inches (100 mm) maximum from the front partition. The door shall be self-closing. A door pull complying with 404.2.7 shall be placed on both sides of the door near the latch. Toilet compartment doors shall not swing into the minimum required compartment area.

Recommendation:
Change or adjust the hinges.
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes findings that have a high financial impact on the entity in relationship to the degree of access provided)
Department:
Parks & Recreation
Image of stall door that is not self-closing
Image that depicts the citation requirements of the code or standard

BFID: 186365

The coat hook is installed greater than 48 inches above the finished floor.

Where a forward reach is unobstructed, the high forward reach shall be 48 inches maximum above the finished floor.
Citation:
2010 ADAS Section 308.2.1
Where a forward reach is unobstructed, the high forward reach shall be 48 inches (1220 mm) maximum and the low forward reach shall be 15 inches (380 mm) minimum above the finish floor or ground.

Recommendation:
Install another coat hook at 48" maximum.
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes findings that have a high financial impact on the entity in relationship to the degree of access provided)
Department:
Parks & Recreation
Image of coat hook mounted too high
Image that depicts the citation requirements of the code or standard

BFID: 186366

The coat hook is installed greater than 48 inches above the finished floor.

Where a forward reach is unobstructed, the high forward reach shall be 48 inches maximum above the finished floor.
Citation:
2010 ADAS Section 308.2.1
Where a forward reach is unobstructed, the high forward reach shall be 48 inches (1220 mm) maximum and the low forward reach shall be 15 inches (380 mm) minimum above the finish floor or ground.

Recommendation:
Move one of the hooks down, or install an additional hook, at 48" maximum.
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes findings that have a high financial impact on the entity in relationship to the degree of access provided)
Department:
Parks & Recreation
Image of towel hooks mounted too high
Image that depicts the citation requirements of the code or standard

BFID: 186368

The baby changing table operating mechanism is outside reach range.

The maximum high reach allowed is 48 inches
Citation:
2010 ADAS Section 308.3.1
Where a clear floor or ground space allows a parallel approach to an element and the side reach is unobstructed, the high side reach shall be 48 inches (1220 mm) maximum and the low side reach shall be 15 inches (380 mm) minimum above the finish floor or ground.

Recommendation:
Lower the changing station to 34" to the lip. Technically this is compliant at the work area is 34"
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes findings that have a high financial impact on the entity in relationship to the degree of access provided)
Department:
Parks & Recreation
Image of baby changing station mounted too high
Image that depicts the citation requirements of the code or standard

BFID: 186369

The soap dispenser's operation mechanism is too high off the floor.

Dispensers must have all operable parts a maximum of 48 inches above the floor.
Citation:
2010 ADAS Section 308.2.1
Where a forward reach is unobstructed, the high forward reach shall be 48 inches (1220 mm) maximum and the low forward reach shall be 15 inches (380 mm) minimum above the finish floor or ground.

Recommendation:
Move the soap dispenser down to 48" maximum.
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes findings that have a high financial impact on the entity in relationship to the degree of access provided)
Department:
Parks & Recreation
Finding 186369 Main Photo
Image that depicts the citation requirements of the code or standard
Additional Finding Photos
Image of soap dispenser mounted too high

BFID: 186371

The bench is not affixed to a wall or provides back support.

The bench shall provide for back support or shall be affixed to a wall along its long dimension. Back support shall be 42 inches long minimum and shall extend from a point 2 inches maximum above the seat surface to a point 18 inches minimum above the seat surface. Back support shall be 2 -1/2 inches maximum from the rear edge of the seat measured horizontally.
Citation:
2010 ADAS Section 903.4
The bench shall provide for back support or shall be affixed to a wall. Back support shall be 42 inches (1065 mm) long minimum and shall extend from a point 2 inches (51 mm) maximum above the seat surface to a point 18 inches (455 mm) minimum above the seat surface. Back support shall be 2 1/2 inches (64 mm) maximum from the rear edge of the seat measured horizontally.

Recommendation:
Provide back support on one of the benches, at least 42" long, or provide another bench against the wall.
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes findings that have a high financial impact on the entity in relationship to the degree of access provided)
Department:
Parks & Recreation
Finding 186371 Main Photo
Additional Finding Photos
Image of bench without back support

Interior - Men's Restroom

BFID: 186357

The wall sign is mounted too high.

Tactile Characters on signs shall be located 48 inches minimum above the finish floor or ground surface, measured from the baseline of the lowest tactile character and 60 inches maximum above the finish floor or ground surface, measured from the baseline of the highest tactile character. Mounting location shall be determined so that a person may approach within 3 inches of signage without encountering protruding objects and shall be located so that a clear floor space of 18 inches minimum by 18 inches minimum, centered on the tactile Characters, is provided beyond the arc of any door swing between the closed position and 45 degree open position.
Citation:
2010 ADAS Section 703.4.1
Tactile characters on signs shall be located 48 inches (1220 mm) minimum above the finish floor or ground surface, measured from the baseline of the lowest tactile character and 60 inches (1525 mm) maximum above the finish floor or ground surface, measured from the baseline of the highest tactile character.

Recommendation:
Install a compliant sign on the latch side of the door.
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes findings that have a high financial impact on the entity in relationship to the degree of access provided)
Department:
Parks & Recreation
Image of noncompliant restroom signage
Image that depicts the citation requirements of the code or standard

BFID: 186370

The door has a door stop which prevents it from having a smooth surface at the bottom.

Swinging door surfaces within 10 inches of the finish floor or ground measured vertically must have a smooth surface on the push side extending the full width of the door. Parts creating horizontal or vertical joints in these surfaces shall be within 1/16 inch of the same plane as the other. Cavities created by added kick plates shall be capped. This is required to allow those that use wheelchairs to use their footrests to push the door open without getting trapped or injured by the gate material. All gates, including ticket gates, shall meet all applicable specifications for doors.
Citation:
2010 ADAS Section 404.2.10
Swinging door and gate surfaces within 10 inches (255 mm) of the finish floor or ground measured vertically shall have a smooth surface on the push side extending the full width of the door or gate. Parts creating horizontal or vertical joints in these surfaces shall be within 1/16 inch (1.6 mm) of the same plane as the other. Cavities created by added kick plates shall be capped.

Recommendation:
Remove the doorstop and replace with an overhead hold open device.
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes findings that have a high financial impact on the entity in relationship to the degree of access provided)
Department:
Parks & Recreation
Image of doorstop on restroom door
Image that depicts the citation requirements of the code or standard

BFID: 186360

The water closet compartment door is missing a loop handle on the inside.

Water closet compartments must be equipped with a door that has a loop or U-shaped handle on both sides of the door immediately below the latch. The latch must be flip-over style, sliding or other hardware not requiring the user to grasp or twist.
Citation:
2010 ADAS Section 604.8.1.2
Toilet compartment doors, including door hardware, shall comply with 404 except that if the approach is to the latch side of the compartment door, clearance between the door side of the compartment and any obstruction shall be 42 inches (1065 mm) minimum. Doors shall be located in the front partition or in the side wall or partition farthest from the water closet. Where located in the front partition, the door opening shall be 4 inches (100 mm) maximum from the side wall or partition farthest from the water closet. Where located in the side wall or partition, the door opening shall be 4 inches (100 mm) maximum from the front partition. The door shall be self-closing. A door pull complying with 404.2.7 shall be placed on both sides of the door near the latch. Toilet compartment doors shall not swing into the minimum required compartment area.

Recommendation:
Install a handle.
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes findings that have a high financial impact on the entity in relationship to the degree of access provided)
Department:
Parks & Recreation
Image of stall door without loop handle.
Image that depicts the citation requirements of the code or standard

BFID: 186363

The toilet paper is not installed within the compliant range.

Toilet paper dispensers shall be 7 inches minimum and 9 inches maximum in front of the water closet measured to the centerline of the dispenser. The outlet of the dispenser shall be 15 inches minimum and 48 inches maximum above the finish floor and shall not be located behind grab bars. Dispensers shall not be of a type that controls delivery or that does not allow continuous paper flow. There shall be a clearance of 1 1/2 inches minimum below the grab bar.
Citation:
2010 ADAS Section 604.7
Toilet paper dispensers shall comply with 309.4 and shall be 7 inches (180 mm) minimum and 9 inches (230 mm) maximum in front of the water closet measured to the centerline of the dispenser. The outlet of the dispenser shall be 15 inches (380 mm) minimum and 48 inches (1220 mm) maximum above the finish floor and shall not be located behind grab bars. Dispensers shall not be of a type that controls delivery or that does not allow continuous paper flow.

Recommendation:
Move the toilet paper closer to the toilet.
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes findings that have a high financial impact on the entity in relationship to the degree of access provided)
Department:
Parks & Recreation
Image of noncompliant toilet paper dispenser
Image that depicts the citation requirements of the code or standard

BFID: 186364

The coat hook is installed greater than 48 inches above the finished floor.

Where a forward reach is unobstructed, the high forward reach shall be 48 inches maximum above the finished floor.
Citation:
2010 ADAS Section 308.2.1
Where a forward reach is unobstructed, the high forward reach shall be 48 inches (1220 mm) maximum and the low forward reach shall be 15 inches (380 mm) minimum above the finish floor or ground.

Recommendation:
Install another coat hook at 48" maximum.
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes findings that have a high financial impact on the entity in relationship to the degree of access provided)
Department:
Parks & Recreation
Image of coat hook mounted too high
Image that depicts the citation requirements of the code or standard

BFID: 186367

The baby changing table operating mechanism is outside reach range.

The maximum high reach allowed is 48 inches
Citation:
2010 ADAS Section 308.3.1
Where a clear floor or ground space allows a parallel approach to an element and the side reach is unobstructed, the high side reach shall be 48 inches (1220 mm) maximum and the low side reach shall be 15 inches (380 mm) minimum above the finish floor or ground.

Recommendation:
Lower the baby changing station lip to 34" to the work surface.
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes findings that have a high financial impact on the entity in relationship to the degree of access provided)
Department:
Parks & Recreation
Image of baby changing station mounted too high
Image that depicts the citation requirements of the code or standard

BFID: 190675

The bench is not affixed to a wall or provides back support.

The bench shall provide for back support or shall be affixed to a wall along its long dimension. Back support shall be 42 inches long minimum and shall extend from a point 2 inches maximum above the seat surface to a point 18 inches minimum above the seat surface. Back support shall be 2 -1/2 inches maximum from the rear edge of the seat measured horizontally.
Citation:
2010 ADAS Section 903.4
The bench shall provide for back support or shall be affixed to a wall. Back support shall be 42 inches (1065 mm) long minimum and shall extend from a point 2 inches (51 mm) maximum above the seat surface to a point 18 inches (455 mm) minimum above the seat surface. Back support shall be 2 1/2 inches (64 mm) maximum from the rear edge of the seat measured horizontally.

Recommendation:
Move bench set or add back support or add a bench.
Barrier Priority:
Low (4): Should be completed as soon as possible due to being a technical violation, but may not result in providing greater access to persons with disabilities. (Includes findings that are technically violations but provide a moderate to low increase in accessibility compared to the financial impact on the entity)
Department:
Parks & Recreation
Image of finding

BFID: 190676

The soap dispenser's operation mechanism is too high off the floor.

Dispensers must have all operable parts a maximum of 48 inches above the floor.
Citation:
2010 ADAS Section 308.2.1
Where a forward reach is unobstructed, the high forward reach shall be 48 inches (1220 mm) maximum and the low forward reach shall be 15 inches (380 mm) minimum above the finish floor or ground.

Recommendation:
Lower the dispenser to 48" maximum to the operable portion.
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes findings that have a high financial impact on the entity in relationship to the degree of access provided)
Department:
Parks & Recreation
Image of finding
Image that depicts the citation requirements of the code or standard

BFID: 190677

The transfer shower compartment is not the minimum required size.

Transfer type shower compartments shall be 36 inches by 36 inches clear inside dimensions measured at the center points of opposing sides and shall have a 36 inch wide minimum entry on the face of the shower compartment.
Citation:
2010 ADAS Section 608.2.1
Transfer type shower compartments shall be 36 inches (915 mm) by 36 inches (915 mm) clear inside dimensions measured at the center points of opposing sides and shall have a 36 inch (915 mm) wide minimum entry on the face of the shower compartment. Clearance of 36 inches (915 mm) wide minimum by 48 inches (1220 mm) long minimum measured from the control wall shall be provided.

Recommendation:
Determine how to make another 3/4" wide to make it 36".
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes findings that have a high financial impact on the entity in relationship to the degree of access provided)
Department:
Parks & Recreation
Image of finding

Interior - Family Changing Area #1

BFID: 186376

The wall sign is mounted too high.

Tactile Characters on signs shall be located 48 inches minimum above the finish floor or ground surface, measured from the baseline of the lowest tactile character and 60 inches maximum above the finish floor or ground surface, measured from the baseline of the highest tactile character. Mounting location shall be determined so that a person may approach within 3 inches of signage without encountering protruding objects and shall be located so that a clear floor space of 18 inches minimum by 18 inches minimum, centered on the tactile Characters, is provided beyond the arc of any door swing between the closed position and 45 degree open position.
Citation:
2010 ADAS Section 703.4.1
Tactile characters on signs shall be located 48 inches (1220 mm) minimum above the finish floor or ground surface, measured from the baseline of the lowest tactile character and 60 inches (1525 mm) maximum above the finish floor or ground surface, measured from the baseline of the highest tactile character.

Recommendation:
Install a compliant sign.
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes findings that have a high financial impact on the entity in relationship to the degree of access provided)
Department:
Parks & Recreation
Image of noncompliant signage
Image that depicts the citation requirements of the code or standard

BFID: 186378

The toilet paper is not installed within the compliant range.

Toilet paper dispensers shall be 7 inches minimum and 9 inches maximum in front of the water closet measured to the centerline of the dispenser. The outlet of the dispenser shall be 15 inches minimum and 48 inches maximum above the finish floor and shall not be located behind grab bars. Dispensers shall not be of a type that controls delivery or that does not allow continuous paper flow. There shall be a clearance of 1 1/2 inches minimum below the grab bar.
Citation:
2010 ADAS Section 604.7
Toilet paper dispensers shall comply with 309.4 and shall be 7 inches (180 mm) minimum and 9 inches (230 mm) maximum in front of the water closet measured to the centerline of the dispenser. The outlet of the dispenser shall be 15 inches (380 mm) minimum and 48 inches (1220 mm) maximum above the finish floor and shall not be located behind grab bars. Dispensers shall not be of a type that controls delivery or that does not allow continuous paper flow.

Recommendation:
Move the toilet paper dispenser to 7" to 9" in front of the toilet.
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes findings that have a high financial impact on the entity in relationship to the degree of access provided)
Department:
Parks & Recreation
Finding 186378 Main Photo
Image that depicts the citation requirements of the code or standard
Additional Finding Photos
Image of noncompliant toilet paper dispenser

BFID: 186379

The baby changing table operating mechanism is outside reach range.

The maximum high reach allowed is 48 inches to the handle, and 34" to the work surface.
Citation:
2010 ADAS Section 308.3.1
Where a clear floor or ground space allows a parallel approach to an element and the side reach is unobstructed, the high side reach shall be 48 inches (1220 mm) maximum and the low side reach shall be 15 inches (380 mm) minimum above the finish floor or ground.

Recommendation:
Move the baby changing station down to 34" to the lip.
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes findings that have a high financial impact on the entity in relationship to the degree of access provided)
Department:
Parks & Recreation
Image of baby changing station mounted too high.
Image that depicts the citation requirements of the code or standard

BFID: 190680

The clearance in front of the transfer type compartment is not the minimum required size.

Clearance of 36 inches wide minimum by 48 inches long minimum measured from the control wall shall be provided.

Transfer type shower compartments shall be 36 inches by 36 inches clear inside dimensions measured at the center points of opposing sides and shall have a 36 inch wide minimum entry on the face of the shower compartment.
Citation:
2010 ADAS Section 608.2.1
Transfer type shower compartments shall be 36 inches (915 mm) by 36 inches (915 mm) clear inside dimensions measured at the center points of opposing sides and shall have a 36 inch (915 mm) wide minimum entry on the face of the shower compartment. Clearance of 36 inches (915 mm) wide minimum by 48 inches (1220 mm) long minimum measured from the control wall shall be provided.

Recommendation:
Determine if feasible to move the controls and seating to opposite sides. If so, then do this. If not post a sign indicating the other family room has an accessible shower.
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes findings that have a high financial impact on the entity in relationship to the degree of access provided)
Department:
Parks & Recreation
Image of finding
Image that depicts the citation requirements of the code or standard

Interior - Family Changing Area #2

BFID: 190678

The wall sign is mounted too high.

Tactile Characters on signs shall be located 48 inches minimum above the finish floor or ground surface, measured from the baseline of the lowest tactile character and 60 inches maximum above the finish floor or ground surface, measured from the baseline of the highest tactile character. Mounting location shall be determined so that a person may approach within 3 inches of signage without encountering protruding objects and shall be located so that a clear floor space of 18 inches minimum by 18 inches minimum, centered on the tactile Characters, is provided beyond the arc of any door swing between the closed position and 45 degree open position.
Citation:
2010 ADAS Section 703.4.1
Tactile characters on signs shall be located 48 inches (1220 mm) minimum above the finish floor or ground surface, measured from the baseline of the lowest tactile character and 60 inches (1525 mm) maximum above the finish floor or ground surface, measured from the baseline of the highest tactile character.

Recommendation:
Install a compliant sign.
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes findings that have a high financial impact on the entity in relationship to the degree of access provided)
Department:
Parks & Recreation
Image of finding
Image that depicts the citation requirements of the code or standard

BFID: 186377

The toilet seat is not located within the range allowed off the floor.

The height of accessible water closets shall be a minimum of 17 inches and a maximum of 19 inches measured to the top of a maximum 2-inch high toilet seat.
Citation:
2010 ADAS Section 604.4
The seat height of a water closet above the finish floor shall be 17 inches (430 mm) minimum and 19 inches (485 mm) maximum measured to the top of the seat. Seats shall not be sprung to return to a lifted position.

Recommendation:
Install a lower profile toilet seat or install a shorter toilet.
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes findings that have a high financial impact on the entity in relationship to the degree of access provided)
Department:
Parks & Recreation
Finding 186377 Main Photo
Image that depicts the citation requirements of the code or standard
Additional Finding Photos
Image of toilet mounted too high

BFID: 190679

The baby changing table operating mechanism is outside reach range.

The maximum high reach allowed is 48 inches to the handle, and 34" to the work surface.
Citation:
2010 ADAS Section 308.3.1
Where a clear floor or ground space allows a parallel approach to an element and the side reach is unobstructed, the high side reach shall be 48 inches (1220 mm) maximum and the low side reach shall be 15 inches (380 mm) minimum above the finish floor or ground.

Recommendation:
Move the baby changing station down to 34" to the lip.
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes findings that have a high financial impact on the entity in relationship to the degree of access provided)
Department:
Parks & Recreation
Image of finding
Image that depicts the citation requirements of the code or standard

BFID: 190681

The threshold has a vertical change greater than 1/4 inch.

The threshold at a doorway shall be no higher than 1/2 inch. Changes in level between 1/4 inch and 1/2 inch must be beveled at 1:2 or less. The maximum vertical rise shall be 1/4 inch.
Citation:
2010 ADAS Section 404.2.5
Thresholds, if provided at doorways, shall be 1/2 inch (13 mm) high maximum. Raised thresholds and changes in level at doorways shall comply with 302 and 303.

Recommendation:
Add strip plate or something similar to reduce to under 1/4".
Barrier Priority:
Moderate (3): Should be completed as soon as possible, but there may be other items that will provide greater access to persons with disabilities. (Includes findings that have a high financial impact on the entity in relationship to the degree of access provided)
Department:
Parks & Recreation
Image of finding
Image that depicts the citation requirements of the code or standard